36
code HC0100.00GB ed.A-1509
HY
AQUAPUMP HYBRID
HYBRID HEATER
5.8.
SmartWEB/EASY configuration
AQUAPUMP HYBRID can operate only if combined with the
SMARTEASY or SMARTWEB touchscreen remote control.
SmartWEB/EASY touchscreen control has been designed to
control several ApenGroup equipment for heating, ventilation
and cooling. When used for control and parametrisation of
AQUAPUMP HYBRID it must be configured for this purpose.
This operation is simple and quick.
Press "menu" on the main screen, then press "system" icon to
enter the first level password (111).
Once the first level password has been entered, select "system
configuration" menu and then "Hybrido" option.
Now from "Hybrido Management" menu, select "System type"
menu to define AQUAPUMP HYBRID mode by choosing among
the 4 types of system available:
0 - Fan heater
This type of system must be selected to use AQUAPUMP HYBRID
together with one or more fan heaters code ABXXXIT-00H0.
In this case the reference temperature (T
REF
) controlled by
SmartWEB/EASY is the ambient air temperature.
1 - Tank
This type of system must be selected to use AQUAPUMP
HYBRID together with a technical water tank, a hydraulic
separator or a reservoir.
In this case the reference temperature (T
REF
) controlled by
SmartWEB/EASY is the device water temperature.
2 - Tank + DHW
This type of system must be selected to use AQUAPUMP HYBRID
together with a technical water tank, a hydraulic separator or
a reservoir and, at the same time, to control a domestic water
boiler with a second setpoint for domestic hot water supply.
In this case the reference temperature (T
REF
) controlled by
SmartWEB/EASY is the device water temperature and the
domestic temperature (T
SAN
) is the reading of the probe positioned
in the domestic water boiler.
3 - Fan DHW
This type of system must be selected to use AQUAPUMP HYBRID
together with one or more fan heaters code ABXXXIT-00H0
and, at the same time, to control a domestic water boiler with
a second setpoint for domestic hot water supply.
In this case the reference temperature (T
REF
) controlled by
SmartWEB/EASY is the ambient air temperature and the
domestic temperature (T
DOM
) is the reading of the probe positioned
in the domestic water boiler.
10:15
Mon 01 Jan
HOME
20.0
SET: OFF
°C
10:15
Mon 01 Jan
MENU
Time Ranges
System
Settings
Mode
Adjustment
10:15
Mon 01 Jan
System
OK
***
1
2
0
3
4
5
6
7
8
9
X
MENU
SYSTEM
System
10:15
Mon 01 Jan
System
Initial Setting Reset
System Configuration
Ethernet
RS485
OK
10:15
Mon 01 Jan
System Configuration
Hybrido
Hot Air Heaters
Boilers
None
OK
10:15
Mon 01 Jan
Hybrido Management
Probe Management
Hybrido Setpoint
OK
System type
0
HYBRIDO
SYSTEM
CONFIGURATION
10:15
Mon 01 Jan
System Type
0 - Fan heater
1 - Tank
2 - Tank + DHW
3 - Fan DHW
OK
In type 2 and 3 systems the production of domestic
hot water has always priority over T
REF
control. When
in DHW production mode, the relay output is activated
for the control of a diverting valve to be positioned in
the system by the installer.
Summary of Contents for Aermax Series
Page 2: ...2 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...
Page 4: ...4 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...
Page 5: ...5 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...
Page 6: ...6 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...
Page 60: ...60 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...