30
June 2012
Gas Controller
AUTOMATIKPRODUKTER
4.8.16 Relay Multiplication
This function is available from version 9.02.
With the relay multiplication table, it is possible in the CGD-05 system to assign an alarm to several
relays.
There is a maximum of 20 entries for IN relays and OUT relays. Thus it is possible to expand one relay to
20 others or to double max. 15 relays.
In the column IN, the relay assigned to an alarm in the menu MP Parameter is set.
In the column OUT, the additionally needed relay is entered.
Note:
Manual intervention on IN or Out relays in the menu Relay Status or via external DI will only affect the
single relay, not the relays assigned in this table!
Number Description Default Status
Function
0-30
IN Relay
0
0 = Function off
X = Relay X should be multiplied (information source)
0-30
OUT Relay
0
0 = Function off
X = Relay X should switch together with In-Relay.
Example 1:
3 relay contacts are needed with the same effect of relay 3. (See assignment of the relays in chapter MP
Parameter)
Entry: 1: IN R3 OUT R7
Entry: 2: IN R3 OUT R8
If relay 3 is activated via an alarm, relays R3, R7 and R8 switch at the same time.
Example 2:
2 relay contacts each are needed from 3 relays (for ex. R7, R8, R9).
Entry: 1: IN R7 OUT R12 (Relay 12 switches at the same time with relay R7)
Entry: 2: IN R8 OUT R13 (Relay 13 switches at the same time with relay R8)
Entry: 3: IN R9 OUT R14 (Relay 14 switches at the same time with relay R9)
This means that relay R7 switches with R12; R8 with R13; R9 with R14.
The two examples can be mixed up, too.