29
June 2012
Gas Controller
AUTOMATIKPRODUKTER
Symbol Description Default
Function
Module
Address
Analog
Input
Relay
No.
Analog
Output
Module
PE- Mod. 0
Relay
Relay active: =
Only alarm relay active
Relay + MP active =
Alarm relay + analog
inputs active
01 - 04 01 - 05 01 - 02
CG-05
Inactive
PE- Mod. 1
Inactive Inactive = Module not active
Relay active: =
Only alarm relay active
Relay + MP active =
Alarm relay + analog
inputs active
1
05 - 08 06 - 10 03 - 04
PE-05
PE- Mod. 2
Inactive
2
09 - 12 11 - 15 05 - 06
PE-05
PE- Mod. 3
Inactive
3
13 - 16 16 - 20 07 - 08
PE-05
PE- Mod. 4
Inactive
4
17 - 20 21 - 25 09 - 10
PE-05
PE- Mod. 5
Inactive
5
21 - 24 26 -30 11 - 12
PE-05
PE-Mod. 6
Inactive
Inactive = Module not active
MP active =
Analog inputs active
6
25 - 28
----
----
PE-05
PE-Mod. 7
7
29 - 32
----
----
PE-05
PE Mod. 8
8
33 - 36
----
----
PE-05
PE Mod. 9
1
37 - 40
----
----
PE-05A
PE Mod. 16
8
65 - 68
----
----
PE-05A
PE Mod. 17
1
69 - 72
----
----
PE-05B
PE Mod. 23
7
93 - 96
----
----
PE-5B
4.8.14 Error Indicator System Bus
All data packets received by the CG-05 are checked for completeness and compatibility.
Missing data packets count up the counter “missing”. The reasons are missing, defective or wrongly addressed
bus components.
Faulty data packets are recorded by the counter “wrong”. Max. 1-2 faulty data packets are admissible per day.
A higher error rate mostly comes from incorrect laying of the field bus line.
4.8.15 Analog Output
The Gas Controller Module as well as the PE-05 Modules 1 to 5 have two analog outputs (AO) with 4 to 20 mA
signal each. The signal of one or more measuring points can be assigned to each of the analog outputs. The
assignment is effected in the menu “MP Parameter” for each MP. The measuring point sends the signal, which
is defined in the menu “C/A Mode”.
Out of the signals of all assigned measuring points the Gas Controller determines the minimum, the maximum
or the average value and displays it at the analog output. The definition, which value is transmitted, is effected
in the menu “Analog Output X”.
The analog output can be calibrated at 4 and at 20 mA. Therefore an ampere meter (measuring range 25 mA)
can be attached to the AO and the respective factor has to be changed until the analog output corresponds to 4
and/or 20 mA. During calibration evaluation of the measuring point signals is not possible. This calibration is
effected by the factory. The factors should not be changed.
Symbol
Description
Default
Status
Function
Max.
Select
Output mode
Max.
Min. = Displays the minimum value of all assigned MP
Max. = Displays the maximum value of all assigned MP
Average = Displays the average value of all assigned MP
4.0
20.0
Calibration
4.0
20.0
4.0 = Calibration factor at 4 mA
20.0 = Calibration factor at 20 mA