12
June 2012
Gas Controller
AUTOMATIKPRODUKTER
4.5
Menu Relay Parameter
Reading and changes of the parameter for each single alarm relay.
(Main menu)
(Selection relay No. – only possible for registered modules)
Relay mode
See 4.5.1
Relay function
See 4.5.2
Activation of latching mode
See 4.5.3
Definition horn function
See 4.5.4
Definition external operation
See 4.5.5
Delay time for relay ON
See 4.5.6
Delay time for relay OFF
See 4.5.6
4.5.1
Relay Mode
Definition of the relay mode
Symbol
Description
Setting Status Function
R 01
Relay No.
Selection of relay
De-energized
Relay Mode
De- energized
Relay de-energized
Relay energized
= Alarm OFF = Relay OFF
= Alarm ON = Relay OFF
4.5.2
Relay Function Static / Flash
Definition of the relay function
Symbol
Description
Setting Status
Function
R 01
Relay No.
Selection of relay
0
Function
0
0 = Relay function static
> 0 = Relay function flashing (= time interval in sec.)
Impulse / Break = 1:1
Relay Mode
De- energized
Static / Flash
0 s
Relay Parameter
R 01
Latching mode
No
Time Recurr. DI
0s 0 0
External mode
DI: ON = 0: OFF = 0
ON-Delay time
0 s
OFF-Delay time
0 s