-BL296*B16F*4A20 10/11-
[Specifications]
[Outside dimensions]
■
The dimensions are common to all models.
(200)
(57)
14.6
37.1
91
(21)
38.5
19.25
84.5
3.25
2-
Φ
3.5
24V
NC
0V
OUT
OUT
0
OUT
8
R/W
LINK ALM
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
24V
NC
0V
OUT
Unit: mm
*The figure is an example of BL296PB-16F-4A-20.
UL style 20276
4 wires × No.23AWG Ø 4.6 Gray
BL296PB-
16F-4A-20
68.7
15.7
6.6
4.5
Detecting transmission signal level reduction
Defecting I/O voltage reduction
BL296SB-16F-4A-20
BL296SB-16FS-4A-20
BL296XB-16F-4A-20
BL296XB-16FS-4A-20
NPN
Input 16 point
PNP
Input 16 point
NPN
Input 8 point, Output 8 point
PNP
Input 8 point, Output 8 point
BL296PB-16F-4A-20
BL296PB-16FS-4A-20
NPN
Output 16 point
PNP
Output 16 point
■
Individual Specifications
■
General Specifications
■
Transmission Specifications
Number of
occupied
data items
Response time
*
3
BL296SB-16F-4A-20
:
60g
BL296XB-16F-4A-20
:
60g
BL296PB-16F-4A-20
:
60g
BL296SB-16FS-4A-20
:
60g
BL296XB-16FS-4A-20
:
60g
BL296PB-16FS-4A-20
:
60g
Monitoring
function
Mass
BL296SB-16F-4A-20
BL296XB-16F-4A-20
BL296PB-16F-4A-20
BL296SB-16FS-4A-20
BL296XB-16FS-4A-20
BL296PB-16FS-4A-20
Consumption
current
Transmission side I/O side
*
4
8 mA
8 mA
8 mA
8 mA
8 mA
8 mA
80 mA
50 mA
80 mA
50 mA
15 mA
15 mA
Up to 1ms
Ambient temperature use
Ambient humidity use
Temperature/humidity storage
Atmosphere
Altitude use
*
1
Pollution level
*
2
Noise resistance
0 - +55
℃
10 - 90%RH No condensation
-25 - +75
℃
No corrosive gas
0 - 2000m
2 or less
1200Vp-p (pulse width 1μs)
(Do not preserve or use under an environment pressurized equal to
or higher than the atmospheric pressure at the altitude of 0m)
Power supply voltage use
Transmission method
Synchronization method
Transmission procedure
Connection mode
Number of connection points
Number of connection points
24V DC +15% to -10% (21.6 to 27.6V DC) with a ripple of 0.5Vp-p or less
DC power supply superimposed total frame/cyclic method
Frame/bit synchronization method
Dedicated protocol
Bus type (Multi-drop method, T-branch method, Tree branch method)
512 max. (IN: 256, OUT: 256)
Up to 128 units
*1 Do not use or store AnyWireASLINK equipment under an environment pressurized higher
than the atmospheric pressure at an altitude of 0m. Otherwise, a malfunction may occur.
*2 This is an index that shows the occurrence level of conductive substances in the
environment where the equipment is used.
In the case of pollution level 2, only non-conductive pollution occurs.
However, this is an environment where temporary conductivity can occur by accidental
condensation.
*3: The time from detection of ON or OFF to sending of a transmission
signal. This time + 2 transmission cycle times is the transmission
delay time.
*4: * The value on the input terminal is the value when all points between
IN and 0V (NPN) or between 24V and IN (PNP) are shorted.
When connecting a 3-wire sensor, add the total consumption current
of the sensor.
* The value on the output terminal is the value when all points are ON.
Add the total connected load consumption current.
* The value on the output terminal is the value when all points are ON.
Add the total connected load consumption current.