Anywire Corporation

 

 
 
 

AnyWireASLINK System 

Ethernet Gateway 

B2G78-E1 

 

User's Manual 

 
 
 

Version 1.4 September 14, 2017 

 
 
 
 
 
 
 
 
 

AnyWireASLINK System

PMA-12813F

Summary of Contents for B2G78-E1

Page 1: ...Anywire Corporation AnyWireASLINK System Ethernet Gateway B2G78 E1 User s Manual Version 1 4 September 14 2017 AnyWireASLINK System PMA 12813F...

Page 2: ...r system The Safety precautions rank safety precaution items into WARNING and CAUTION categories Precautions for design The AnyWireASLINK system has high noise resistance however keep transmission lin...

Page 3: ...e of the power supply to the remote slave unit may become insufficient due to the voltage drop Therefore please connect an external power source to ensure the specified voltage Do not turn on the 24V...

Page 4: ...ge to the screws or unit resulting in it falling down a short circuit or malfunction Do not disassemble or modify each unit Doing so may result in failure malfunction injury or fire During installatio...

Page 5: ...or 6 9 6 9 AnyWire filter 6 10 6 10 Address setting reference 6 12 7 Software functions 7 1 7 1 Modbus TCP 7 1 7 1 1 Input memory map 7 1 7 1 1 1 Input memory map details 7 2 7 1 1 2 Calendar clock 7...

Page 6: ...9 Default setting 7 24 8 Monitoring function 8 1 8 1 Overview 8 1 8 2 Automatic address recognition 8 1 8 3 Monitoring operation 8 1 9 Required transmission time 9 1 9 1 Input 9 1 9 2 Output 9 1 10 D...

Page 7: ...it therefore it can bundle even in a narrow device in which a BOX is not placed In addition this system also proposes Digital Link Sensors that incorporate the AnyWireASLINK sensing function and wirin...

Page 8: ...points Input 256 points output 256 points RAS function Transmission line disconnection detection function transmission line short circuit detection function transmission circuit drive power voltage d...

Page 9: ...Specifications 2 2 2 3 Outside dimensions Unit mm Board guide Board guide DIN hook 105 8...

Page 10: ...Specifications 2 3 2 4 Name of each part LED display RESET switch SET switch Monitor connector AnyWireASLINK connector terminal block Ethernet connector terminal block LINK E LED ACT LED...

Page 11: ...DIN rail Fit C into the DIN rail while pressing this device upward from underneath 2 DIN rail detachment procedure When the knob B is pulled downward with a flat blade screwdriver C is removed and th...

Page 12: ...ireASLINK slave unit Pressing the SET switch for approximately two seconds or more lights up the SET LED to start automatic address recognition In addition when the B2G78 E1 is turned on or reset whil...

Page 13: ...ly operating ERR Red Master unit alarm status Lit DP DN disconnection No slave unit response Normally operating Slow flashing every second Short circuit between DP DN Quick flashing every 0 2 seconds...

Page 14: ...ing shows the terminal arrangement Signal name Dedicated flat cable wire color Link connector 0 75sq 1 25sq Pin number Type 24V 0V DP DN LG Green White Red Black Brown White Red Black 4 3 2 1 0 75sq L...

Page 15: ...onitor Signals are RS232 compatible 5 4 3 2 1 SG RXD TXD MRXD MTXD 5 4 3 2 1 SG RXD TXD 9 8 7 6 Connect the above extension cable and the personal computer with a cross cable Connector Manufactured by...

Page 16: ...NK 6 1 6 AnyWireASLINK 6 1 System configuration The AnyWireASLINK system consists of a master unit slave units and their peripheral devices For output For input For input For output Terminator Slave u...

Page 17: ...ave units and the total consumption current of the transmission line do not exceed the maximum number of transmission points and the allowable supply current Connection of slave units There are roughl...

Page 18: ...annels 6 4 Connection mode The AnyWireASLINK system allows for various connections such as T branching multi drop tree branching and star branching T branching method The T branching method is a conne...

Page 19: ...cables Conversion to a dedicated flat cable Multi drop method The multi drop method is a way to connect slave units directly to cables Use of this method eliminates the need for new cables or other co...

Page 20: ...method The star branching method is a way to connect the master unit and lay cable radially from a certain branching point to connect the slave unit This method makes it easy to bundle transmission ch...

Page 21: ...can be established with only two transmission lines DP DN The two transmission lines DP DN support a maximum total length of 200m See P2 1 This total length also includes the length of the cable comi...

Page 22: ...25mm 2 rated temperature 90 C Shielded cable Since AnyWire has high noise resistance it is unnecessary to use shielded cable Please note that if the shielded cable shielding is not properly grounded...

Page 23: ...l as power for the slave unit and whatever is connected to the load side of the slave unit are superimposed on these two wires The allowable supply current transmission line supply current value from...

Page 24: ...onnected at the farthest end of the trunk line When extending branch lines out from the trunk line one terminator must be connected at the end of the branch line if the length of the branch lines is m...

Page 25: ...system or using a local power supply Filter allowable current Model Type Allowable current ASLINK filter ANF 01 MAX 5A 24V DC COSEL filter EAC 06 472 MAX 6A 24V DC ASLINK filter ANF 01 connection exa...

Page 26: ...of 50m Filter notation in the drawing For more details regarding the ANF 01 please refer to the ANF 01 Products Guide Two wire terminal Four wire terminal 24V DC stabilized power supply General purpos...

Page 27: ...ecimal number Write the value that you want to set to the slave unit using a dedicated address writer ARW 04 ARW 03 The address of the slave unit is set to 255 before shipment The slave unit does not...

Page 28: ...m reserved 04 30254 30254 253 253 1 word Check setting for number of transmission points 04 30255 30255 254 254 1 word Flag for ASLINK communication 04 30256 30256 255 255 1 word System reserved 04 30...

Page 29: ...esses are 0 255 bit type and when the input signal is specified with function code 04 input register reading the corresponding memory addresses are 0 15 word type Since the only difference is the data...

Page 30: ...ory address Offset address 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 30165 164 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit Error content ERR LED status Remarks 0 ON Short circuit between DP and DN OFF Norma...

Page 31: ...ASLINK communication Each AnyWireASLINK communication status is shown The relationship between error flags and data memory is as follows Modbus TCP address Data Memory address Offset address 15 14 13...

Page 32: ...No 8 Year Last two digits of Western year format ex Year xx13 0x0D Month ex August 0x08 30293 292 Day ex 30th day 0x1E Hour ex 13 00 0x0D 30294 293 Minute ex 26 minutes 0x1A Second ex 21 seconds 0x15...

Page 33: ...ly to lie within the rated range 21 6 to 27 6V Recommended voltage is 26 4V Check that the power line 24V 0V is not disconnected or short circuited Check that the pin assignment was correct when the l...

Page 34: ...units and addresses are the same as those of the actual system If the slave unit LINK LED is not flashing check the transmission line for disconnection short circuit miswiring or contact failure near...

Page 35: ...set the ID so that there will be no redundancy 401 191 ID not set error Occurrence ID is stored 255 or 767 There is a slave unit whose address has not been set default setting Perform the following S...

Page 36: ...o 1 target ID 30837 836 No 1 error code 30838 837 No 2 Year Last two digits of Western year format ex Year xx13 0x0D Month ex August 0x08 30839 838 Day ex 30th day 0x1E Hour ex 13 00 0x0D 30840 839 Mi...

Page 37: ...of each parameter area block is as follows Offset Parameter name R W Classification 0 Slave unit ID R W ASLINK access not required referred from internal memory 1 Device parameter 1 R W Interrupt acce...

Page 38: ...nker non isolated I O Bit status Meaning Slave judgment method ON I O disconnection Input judgment value 0 3mA or less is judged as a disconnection Output judgment value 2mA or less is judged as a dis...

Page 39: ...6 5 4 3 2 1 0 39872 9871 Registration ID number 39873 9872 Registration ID1 39874 9873 Registration ID2 39875 9874 Registration ID3 39999 9998 Registration ID127 40000 9999 Registration ID128 The ID f...

Page 40: ...ctual specified start address is the offset address 7 1 2 1 Output area Output signals of AnyWireASLINK are stored in this memory map When output area is specified with a Modbus TCP function code 01 0...

Page 41: ...9 1188 Set with 0 1 7 1 2 3 Error clear If an error such as wire disconnection is resolved the disconnection flag and number of error IDs are both reset to 0 by writing 1 in Modbus TCP address 1202 Br...

Page 42: ...ss redundancy check for the currently connected device Even if automatic address recognition is not carried out only the redundancy check is carried out 4 Parameter access command Applies the paramete...

Page 43: ...ss method Modbus TCP address Value Description Memory address Offset address 41825 1824 0 Read 1 Write Parameter access target ID Modbus TCP address Value Memory address Offset address 41826 1825 Acce...

Page 44: ...t access initial access 3 Device parameter 3 R W Interrupt access initial access 4 Device parameter 4 R W Interrupt access initial access 15 Device parameter 15 R W Interrupt access initial access 16...

Page 45: ...y to the B2G78 E1 with a LAN cable Either a cross or straight LAN cable is acceptable Set the connected LAN interface as follows IP address 192 168 0 xx Excluding 36 0 and 255 for xx Sub net mask 255...

Page 46: ...teway has the following setting items 7 4 2 Own station information Settings Default setting IP address 192 168 0 36 Sub net mask 255 255 255 0 Default gateway address 192 168 0 1 Changes to settings...

Page 47: ...to settings are applied after writing settings and restart and Stop for the default setting An I O of a up to 4 blocks can be set for each socket If the number of transfer words is set to 0 transfer o...

Page 48: ...and Stop for the default setting The area to be transferred with EtherNet IP can be selected from this screen Note This unit is an adapter It is necessary to also set the same content on the scanner s...

Page 49: ...oint number setting MODE can be carried out Frame length 32 64 128 256 clock can be changed Changes to settings are applied immediately when settings are written The default setting is 256 7 4 5 Time...

Page 50: ...ettings can be applied in real time from this screen Put a tick in the Auto start check box of a protocol that you want to start and press the Auto start register button Each protocol can be started a...

Page 51: ...he procedure is as follows Turn off the power Turn on the power while holding the SET button Place your finger so that the LED on the side of the button is visible at this time The LED on the side of...

Page 52: ...ss and hold the SET switch of this device until the SET LED yellow lights up 3 The SET LED lights up for a while and then turns off when address storage has been completed Input output may not be carr...

Page 53: ...performed on that side Terminology Cycle time Repeated transmission time of actual data transmitted Maximum transmission delay time Processing time on master side Refresh time Signal delay time on sla...

Page 54: ...Device profile 10 1 10 Device profile Use the following EDS file B2G78 E1 eds EDS files can be downloaded from the AnyWire Homepage http www anywire jp Top page Support Download Download Software...

Page 55: ...ress setting The ACT LED is unlit Normal or the power is off P4 1 2 LED display on the AnyWireASLINK side Check the LINK LED The LINK LED is flashing Normal If the LED is unlit check that 24V power is...

Page 56: ...d in the alarm ID number information storage area input offset byte address 3 Remove any problems until the error number or alarm number becomes 0 P7 3 3 Check error occurrence ID information Error oc...

Page 57: ...ve voltage drop error Items to check Description of measures Check the voltage of the 24V DC external supply power Make adjustments so that the voltage of the 24V DC external supply power does not exc...

Page 58: ...Under normal conditions a voltage of approximately 17V to 18V is observed using a tester in DC mode When the transmission line is disconnected or suffers a similar fault the position can also be ident...

Page 59: ...User s Manual the Company shall replace or repair the defect free of charge except when it arises as a result of 1 Misuse or abuse of the Product by the owner 2 Faults due to a cause other than the de...

Page 60: ...RoHS Directive for the Chinese version 13 1 13 RoHS Directive for the Chinese version SJ T11364 2006 10 Pb Hg Cd Cr VI PBB PBDE SJ T11364 GB T26572 GB T26572...