27
7.6
Serial Port Configuration – Type 6
The Messenger has 4 serial ports (1-4). Port 1 is dedicated to the on-board cellular
modem.
CAUTION: Do not modify the parameters of Port 1.
Port 2 is set to RS485 by the factory. Port 3 is set to RS232 at the factory. NOTE: Not
all parameters shown below apply to every port.
Parameters for Serial Port Configuration
Parameter
Code
Reference
Description
Default
1
Mode
Range 0 – 7
0 = none
1 = debug (port 3)
2 = MODBUS RTU Slave
4 = MODBUS RTU Master (port 2)
Port
Specific
2
Physical
Interface
Port 2 is the only port that has an RS485
transceiver. To enable RS485 for Port 2,
set this parameter to 1 and set
accordingly.
RS232
[0]
0 = RS232 1 = RS485
3
Modbus
Slave ID
This sets the Slave ID when port mode is
set to MODBUS RTU Slave.
126
Range 1 - 247
4
Baud
Defines the port baud rate.
57600
Valid baud rates:
1200
2400
4800
9600
19200
38400
57600
115200
5
Max Idle
Defines the period of inactivity before the
active receive buffer is closed.
5
Range 1 – 32000 msecs
6
Response
Timeout
Maximum time to wait for a response.
2
Range 1 – 60 seconds
7
RS485 pre-
Tx delay
Defines the duration of time between
enabling the RS485 transmitter and starting
transmission.
2
Range 1 – 20 msecs
8
RS485 post-
Tx delay
Defines the duration of time after
transmission of the last character to
disabling the RS485 transmitter.
4
Range 1-20 msecs