Parameters for Digital Channel Configuration
(channel numbers 1-50 are pre-defined digital channels)
Parameter
Code
Reference
Description
Default
1
Name
A representative name used to
reference the channel by.
Channel
Specific
ASCII Text
30 characters max
2
Mode
Defines operating mode of channel.
Status
Only [1]
0= Disabled
1 = Status Only (value is monitored, no
testing of value against limits)
2 = Report on Alarm (value is
monitored and tested against limits)
3
Alarm
Delay
The continuous time the value must be
not normal before it is considered in
alarm.
10
Range 0 – 65535 seconds
0 = no delay time, immediate alarm
6
Normal
(Idle) State
State of input when condition being
monitored is normal.
Normally
Open [0]
0 – open or > 3.0V
1 – closed to ground
16
Alarm
Output
A digital output channel that can be
activated when this channel goes into
alarm (referenced as channel number).
Disabled
[0]
0 = disabled
xxx = any MODBUS channel
configured as a Write Coil channel
Channel numbers 301-900 are user configurable MODBUS
channels. The following parameters are specific to those channels
when configured as type digital.
20
Slave ID
Modbus ID of slave unit.
-1
Range -1 to 255
-1,0 = disabled
1-227 = for direct connect slave devices
228-239 = reserved
240-255 = for peer to peer devices
21
Register
Number
Register number in slave to read/write
1
Range = 1 – 65535
22
Defines the type of data register to
read/write in the slave.
None [0]