SECTION X
UL EX-4510 12-1-01 Page 10-3
Maintenance
ANNUAL MAINTENANCE EXAMINATION (Continued)
Thermal Detection/Electric ANSUL AUTOMAN II-C
Release
1. Make certain ring pin is in place in ANSUL AUTOMAN
II-C release mechanism. See Figure 1.
FIGURE 1
001894
2. Remove cartridge.
3. Remove ring pin and manually test system by operating
the remote manual pull station or push “STRIKE” button
on ANSUL AUTOMAN II-C release.
4. After operating manually, check that all functions have
been accomplished.
5. Cock ANSUL AUTOMAN II-C release mechanism using
cocking lever, Part No. 26310, and install ring pin.
6. Remove gasket from cartridge receiver in ANSUL
AUTOMAN II-C release mechanism. Check gasket for
elasticity or cuts and replace if necessary. Clean and
coat gasket lightly with a good grade of extreme tem-
perature grease such as Dow Corning No. 4. Reinstall
gasket into cartridge receiver. Do not install cartridge
at this time.
7. Make certain the release mechanism is cocked and ring
pin is removed.
8. Test each thermal detector by using an approved heat
lamp. Test each detector individually and recock release
mechanism after each test.
NOTICE
If system does not fire, check the integrity
of the solenoid by using an ohmmeter and
measure the resistance of the solenoid
coil. If it is not within the resistance range,
replace solenoid. There are two different
solenoids used in the ANSUL AUTOMAN
II-C release and their resistance is as fol-
lows:
Number Stamped
Resistance
on Solenoid
Measurement
P4-2025
12-18 ohms
TBX16-C-12 VDC
21-32 ohms
9. With release mechanism cocked, install ring pin. See
Figure 1.
10. Before installing cartridge, reset all additional equip-
ment by referring to appropriate section of Resetting
and Recharge, Section VIII.
11. Remove shipping cap and weigh each nitrogen car-
tridge. Replace if weight is 1/2 ounce (14.2 g), or more,
below weight stamped on cartridge.
12. Make certain release mechanism is cocked and ring pin
is installed, screw replacement cartridge into release
mechanism and hand tighten.
13. Remove ring pin.
14. Install cover on enclosure, install ring pin through
“STRIKE” button, and secure with visual seal, Part
No. 197.
15. Record annual maintenance date on tag attached to
unit and/or in a permanent file.
Electric Detection/AUTOPULSE Control System
On selector valve systems, it is not necessary to remove
the actuator on the selector valve during this test.
RESET LEVER
RING PIN
CAUTION
!
Remove the electric valve actuator from the cylinder
valve prior to testing the AUTOPULSE Control System.
Failure to do so will cause accidental system discharge.