SECTION XI
UL EX-4510 12-1-01 Page 11-4
Typical Applications
ANSUL INERGEN DESIGNER
Version 5. 0.1
Job:
Manual Example
Customer:
Ansul Incorporated
Address:
One Stanton Street
Marinette Wl 54143
Country:
USA
REMARKS:
Computer Room Example
HAZARD AREA INFORMATION
Area:
Computer Room
Design concentration 34.2% at 60°Fahrenheit
Estimated maximum concentration 40.6% at maximum hazard temperature 80°Fahrenheit
Gross volume of enclosure 2600 cubic feet
Structural volume reductions 100 cubic feet
Net volume of enclosure 2500 cubic feet
Minimum INERGEN required 907.4 cubic feet
Approximate INERGEN supplied 1040 cubic feet
Flooding factor .427 cubic feet of INERGEN per cubic feet of enclosure volume
Maximum allowable wall strength 5. Ibs./sq. ft
Area consists of one volume
Volume 1: Length 20 ft Width 13 ft Height 10 ft
1 nozzles. Nozzle identifiers: 301
Area:
Subfloor
Design concentration 34.2% at 60°Fahrenheit
Estimated maximum concentration 40.6% at maximum hazard temperature 80°Fahrenheit
Gross volume of enclosure 260 cubic feet
Structural volume reductions 10 cubic feet
Net volume of enclosure 250 cubic feet
Minimum INERGEN required 90.7 cubic feet
Approximate INERGEN supplied 104 cubic feet
Flooding factor .427 cubic feet of INERGEN per cubic feet of enclosure volume
Maximum allowable wall strength 5. Ibs./sq. ft
Area consists of one volume
Volume 1: Length 20 ft Width 13 ft Height 1 ft
1 nozzles. Nozzle identifiers: 401
AGENT STORAGE CONDITIONS
Number of cylinders: 2 each containing 572 cubic feet of INERGEN. Total agent 1144 cubic feet
Engineering units (ft, cu ft, psia) are specified
Calculation based on 70 degree Fahrenheit pre-discharge Pipeline Temperature