IQ-636X-2/E Installation Manual —
P/N 52853:K3 9/28/15
69
Appendix C: Canadian Applications
C.1 Standalone Application
C.1.1 IQ-636X-2/E with KDM-R2
If using KDM-R2 as the primary display for IQ-636X-2/E, an ACS series annunciator must be
mounted adjacent to the panel or within IQ-636X-2/E enclosure.
C.1.2 IQ-636X-2/E with AutoPulse-NCA-2
Network Control Annunciator (AutoPulse-NCA-2) with 640-character, multi-line display complies
with ULC requirements when used as the primary display for IQ-636X-2/E.
C.2 Manual Controls
To meet ULC requirements, the system’s Manual Controls may only be operated from one location
at any given time. No networking functions are available with AutoPulse-NCA-2; therefore the
AutoPulse-NCA-2 must always be mounted within the same enclosure as the IQ-636X2.
C.3 Automatic Alarm Signal Silence
If selecting this feature for a system requiring annunciators, consult the Authority Having
Jurisdiction.
C.4 Annunciator Applications
1. In Canada, the ACM series annunciator modules must be used to annunciate the fire alarm
input points/zones only, if no multi-line sequential display is installed.
2. For Canadian applications, the following LED colors must be employed:
– Red must be used to indicate active alarm inputs.
– Yellow must be used to indicate supervisory, burglary or trouble signals.
– Green must be used to indicate the presence of power or an activated output.
C.5 Releasing Devices
Supervision for shorts is required; use REL devices and type code R
EL
C
KT
ULC.
(With on-board NACs, use REL-2.2K; with FCM-1 modules use REL-47K. Refer to Section 4.7.5
“Connecting Releasing Devices to the FCM-1-REL Control Module” for details.)