IQ-636X-2/E Installation Manual —
P/N 52853:K3 9/28/15
49
Fire/Security Applications
Applications
2. Install the magnet on the same side of the cabinet door as the lock. Push the magnet through
the opening in the door until it snaps into place.
3. Connect the STS-1 connector to J5 (Security Tamper) on the Control Panel. (As shown in
Figure 4.5, J5 is located on the circuit board, underneath the edge of KDM-R2.)
4.6.3 Receiving Unit
For applications requiring transmission of security alarm information to a central receiving unit, the
control panel may be connected via the UDACT or UDACT-2 to a compatible receiving unit (see
the
UDACT Manual
or
UDACT-2 Manual
). For information on configuring the Receiving unit for
Combination Fire/Security applications, refer to the documentation for that control panel.
4.6.4 Programming
The control panel can communicate with any number of security devices. To do so, program the
points as follows:
1. Select the address of the module(s) to be used for security.
2. Select the Type Code
SECURITY
.
4.6.5 Wiring for Proprietary Security Alarm Applications
Table 4.6 shows typical wiring for proprietary security alarm applications with FMM-1 modules.
Note the following:
•
The module is programmed with software
SECURITY
Type Code.
•
For use with UL listed systems only; application not for ULC security usage.
•
NAC devices used for security cannot be shared with fire NAC devices.
•
Refer to the
Device Compatibility Document
for compatible NAC devices.
•
All monitor modules used for security application must be installed in the IQ-636X-2/E
cabinet with STS-1 Security Tamper Switch.
J5
J6
LED1
LE
D
2
LE
D
3
LE
D
4
LE
D
5
LE
D
6
LE
D
7
C
P
U
2-6
40
-st
s1_C
P
S
.w
m
f
STS-1 mounting location
(side opposite of door hinges)
Connect to
J5 “Security Tamper”
Figure 4.5 Installing the STS-1 Security Tamper Switch
NOTE:
For detailed instruction on programming Type Codes, refer to the IQ-636X-2/E
Programming Manual.