c. Insert anchor stud through valve body and actuator pivot
member.
The Quick-Opening lever may be moved slightly forward,
approximately 1/4 inch (6.4 mm), to permit installation of
the anchor stud.
Forward movement in excess of 1/4 inch (6.4 mm) may
cause actuation of the valve resulting in a high velocity of
unrestrricted escaping gas forceful enough to cause injury,
especially about the face and head.
d. Engage and secure cap nut to anchor stud.
13. Remove safety plug from nitrogen cylinder valve. (Retain plug
for future use.)
Do not place body or head in front of cylinder valve outlet. If
valve is accidentally operated, velocity of unrestricted
escaping gas is forceful enough to cause injury, especially
about the face and head.
14. Connect high pressure hose to nitrogen cylinder valve and
wrench tighten.
Do not strike “pull” lever when connecting hose to cylinder
valve, velocity of unrestricted escaping gas is forceful
enough to cause injury, especially about the face and head.
15. Make certain visual inspection seals on cylinder valve are still
intact. Replace any broken or missing visual inspection seals
(Part No. 197).
16. Return dry chemical tank valve handles to the operating posi-
tion:
BLUE Hose Clean-Out Valve. . . . . . . . . . . . . . . . . . Closed
BLACK Dry Chemical Valve. . . . . . . . . . . . . . . . . . . . Open
17. Insert ring pins through handles into brackets and seal with
visual inspection seals (Part No. 15999).
18. Return ANSULITE AFFF solution tank valve handles to the
operating position:
BLUE Hose Clean-Out Valve. . . . . . . . . . . . . . . . . . Closed
BLACK AFFF Valve . . . . . . . . . . . . . . . . . . . . . . . . . . Open
19. Insert ring pins through handles into brackets and seal with
visual inspection seals (Part No. 15999).
20. Record date of recharge and notify operating personnel that
system is back in service.
!
WARNING
!
WARNING
!
CAUTION
RECHARGE
2012-MAR-22
REV. 01 PAGE 7
ANSUL Fire Suppression/Securing Systems
Operation and Maintenance – Model 100/30