Technical data
8
Measure
unit
SUPAflo EVO
SF61
SF62
SF63
Nominal heat output at 80/60ºC max/min
kW
142,3/31,3
190,4/42,0
237,6/47,0
Nominal heat output at 40/30ºC max/min
kW
151,2/35,4
202,3/47,4
252,3/53,4
Nominal heat input Hi max/min
kW
145,0/32,2
194,0/43,1
242,0/48,4
Efficiency at 80/60ºC
%
98,2
98,2
98,2
Efficiency at 40/30ºC
%
104,3
104,3
104,2
Annual efficiency (NNG 40/30ºC)
%
110,4
110,4
110,4
Max. condensate flow
l/h
9,2
12,4
15,4
Gas consumption G20 max/min (10,9 kWh/m3)
m
3
/h
13,3/3,0
17,8/4,0
22,2/4,4
Gas consumption G25 max/min (8,34 kWh/m3)
m
3
/h
17,4/3,9
23,3/5,2
29,0/5,8
Gas consumption G31 max/min (12,8 kWh/kg)
kg/h
11,3/2,5
15,2/3,4
18,9/3,8
Gas pressure G20
mbar
20
Gas pressure G25
mbar
25
Gas pressure G31
mbar
30/50
Maximum gas pressure
mbar
50
Max. temperature flue gas
°C
90
Flue gas temperature at 80/60ºC max/min
°C
75/58
75/58
75/58
Flue gas temperature at 40/30ºC max/min
°C
54/30
54/30
55/30
Flue gas quantity max/min H-gas
m3/h
188/43
251/57
313/64
CO2 level G20/G25 max/min
%
10,2/9,4 ±0,2 (Restriction type 570 delta max/min ≥0,8%)
CO2 level G31 max/min
%
11,9/10,0 ±0,2
NOx 80/60ºC max/min
mg/kWh
38/19
38/19
36/18
CO 80/60ºC max/min
mg/kWh
14/3
14/3
14/5
Max. permissible flue resistance max/min
Pa
200/10
200/10
200/10
Water volume
l
26
31
33
Water pressure max/min
bar
8/1
Max. water temperature (High limit thermostat)
°C
100
Maximum temperature setpoint
°C
90
Nominal water flow at dT=20K
m3/h
6,1
8,1
10,1
Hydraulic resistance at nominal water flow
kPa
11,2
26,8
31,2
Electrical connection
V
230/400
Frequency
Hz
50
Mains connection fuse
A
16
IP class
IP20
Power consumption boiler max/min (excl. pump)
W
176/48
267/48
286/53
Power consumption speed controlled pump (opt)
W
190/9
190/9
310/12
Weight (empty)
Kg
290
332
366
Sound Power Level (LWA)
dB
70,3
70,3
70,3
Ionisation current average
μA
10,0/4,5
pH value condensate
-
3,2
CE certification code
-
CE - 0063CQ3970
Water connections
-
R2”
R2”
R2”
Gas connection
-
R1.1/2”
R1.1/2”
R1.1/2”
Flue gas connection (DN)
mm
150
150
200
Air intake connection (for room sealed use) (DN)
mm
130
130
130
Condensate connection
mm
32
Technical data
Summary of Contents for SUPAflo EVO SF60 EVO
Page 1: ...INSTALLATION AND SERVICE MANUAL SUPAflo EVO Water Heater SF60 EVO...
Page 2: ......
Page 15: ...Installation 15 EN Disassemble the casing 7 8 9...
Page 23: ...Installation 23 EN Wiring diagram Boiler...
Page 46: ...Note 46 Note...
Page 47: ...Note 47 EN Note...