background image

Commissioning

28

Combustion analysis

Combustion check at full load

Start  the  boiler  in  controller  stop 

mode and go to 50% load. Now the 

boiler  operates  at  50%  load.  Allow 

the  boiler  to  stabilise  the  combus

-

tion  for  3  minutes.  Then  increase 

the  boiler  load  step  by  step  up  to 

100%. 

Check the gas pressure on the inlet 

of the gas valve while increasing the 

boiler load:

the gas pressure should never go be

-

low the minimum required value 

 

 

see technical data. 

When  an  (optional)  minimum  gas 

pressure  switch  is  connected,  this 

must be set to 75% of the required 

gas pressure.

Check  the  combustion  settings  via 

the  test  point  in  the  chimney  con

-

nection (1). 

If  necessary,  correct  the  settings 

with the small adjustment screw (2) 

under the cap (3) at the top of the 

gas valve.

Combustion settings max. load

for natural gas G20 / G25

CO

2

  max. G20 / G25

%

10,2 ± 0.2

Combustion settings min. load

for natural gas G20 / G25

CO

2

  min. G20 / G25

%

9,4± 0.2

Combustion check at minimum load

Switch the boiler to minimum load 

(0%).

Check the combustion settings the

same way as described for full load. 

If  necessary,  correct  the  settings 

with the large adjustment screw at 

the top of the gas valve (4).

Combustion check at 50% load

An  additional  reference  check  of 

combustion  values  at  50%  load  is 

recommended  in  order  to  check  if 

the gas valve is set in such way, that 

the modulating behaviour is normal. 

The CO2 value should be in between 

the  settings  of  full  load  and  minu

-

mum load. 

CO value should be equal to full load 

and minimum load values.

Make  sure  that  the  boiler  is  set  to 

automatic  operation  and  controller 

stop mode is disabled after the com

-

bustion test is finished.

Combustion settings max. load

for G31 (I3P)*

CO

2

  max. G31 (I3P)

%

11,9± 0.2

Combustion settings min. load

for G31 (I3P)*

CO

2

  min. G31 (I3P)

%

10,0± 0.2

1

4

2

3

Combustion settings max. load

for G30 / G31 (I3B/P)*

CO

2

  max. G30 (I3B/P)

%

12,7± 0.2

CO

2

  max. G31 (I3B/P)

%

10,9± 0.2

Combustion settings min. load

for G30/G31 (I3B/P)*

CO

2

  min. G30 (I3B/P)

%

11,9± 0.2

CO

2

  min. G31 (I3B/P)

%

10,0± 0.2

*Use conversion kit for I3P and I3B/P

Summary of Contents for SUPAflo EVO SF60 EVO

Page 1: ...INSTALLATION AND SERVICE MANUAL SUPAflo EVO Water Heater SF60 EVO...

Page 2: ......

Page 3: ...system 2 7 Neutralisation systems 2 8 Gas supply 2 9 Flue and air intake connections 2 9 Condensate connection 2 9 Prepare boiler for first startup 3 0 Combustion analysis 3 1 Check gas Valve 3 2 Che...

Page 4: ...lity EMC Direc tive 2014 35 EU Low Voltage Direc tive EN 13203 2 2015 Gas fired do mestic appliances producing hot water Part 2 Assessment of en ergy consumption EN 15036 1 2006 Heating boilers Test r...

Page 5: ...e governing legal regulations and the instructions provided by the manufacturer Incorrect installation can harm persons animals and pos sessions the manufacturing compa ny shall not be held responsibl...

Page 6: ...Power output heating 16 Gases which may be used 17 Ambient operating temp 18 Max central heating temp Operating principle The SUPAflo EVO is a fully modulat ing boiler The control unit of the boiler...

Page 7: ...9 Flow water connection 10 Return water connection 11 Electrical input entries HV LV 12 Viewing glass 13 Burner 1st heat exchanger assembly 14 2nd 3rd heat exchanger assembly 15 Syphon 16 Ignition an...

Page 8: ...H gas m3 h 188 43 251 57 313 64 CO2 level G20 G25 max min 10 2 9 4 0 2 Restriction type 570 delta max min 0 8 CO2 level G31 max min 11 9 10 0 0 2 NOx 80 60 C max min mg kWh 38 19 38 19 36 18 CO 80 60...

Page 9: ...Flue gas quantity max min H gas m3 h 377 77 502 102 628 128 712 161 CO2 level G20 G25 max min 10 2 9 4 0 2 Restriction type 570 delta max min 0 8 CO2 level G31 max min 11 9 10 0 0 2 NOx 80 60 C max mi...

Page 10: ...kW 47 5 63 5 79 3 95 3 127 1 Seasonal space heating energy efficiency hs 93 4 93 5 93 6 93 6 93 6 At rated heat output and high tem perature regime 2 h4 88 4 88 4 88 4 88 4 88 5 At 30 of rated heat ou...

Page 11: ...104 178 0 D 482 602 723 967 W3 1124 1130 G W1 W2 S A Dimensions SUPAflo EVO Models SF61 SF62 SF63 SUPAflo EVO Models SF64 SF65 SF66 SF67 SUPAflo EVO model SF61 SF62 SF63 SF64 SF65 SF66 SF67 L1 mm 134...

Page 12: ...Gas filter incl connection kit Max gas pressure switch External high limit thermostat Gas valve leakage tester 2nd Return connection for Split System use Bypass incl pump Plate heat exchanger dT 10K 1...

Page 13: ...fore con necting the boiler to the crane Al ways connect the crane to the frame of the boiler by using straps Component SF61 SF62 SF63 SF64 SF65 SF66 SF67 Burner 1st heat exchanger assembly Weight kg...

Page 14: ...s sembling the casing is done ac cording the following steps For re assembly of the casing the same steps have to be tak en but reversed Starting with the top casing Make sure the earth cable and scre...

Page 15: ...Installation 15 EN Disassemble the casing 7 8 9...

Page 16: ...orrectly Make sure that the boiler is set up for operation with the type of gas available read the informa tion on the packaging label and on the boiler data plate Make sure that there are no ob stacl...

Page 17: ...6 is the high tempera ture return The optional accessory kit with safety valve manometer and deaer ator should be mounted on the flow connection 4 of the boiler before connecting to the system The op...

Page 18: ...ssive condensate and CE approved may be used In particular for flue gas system see the following data Air Flue gas system Plastic PP Stainless steel Temperature class T120 T250 Pressure class P1 P1 Co...

Page 19: ...by calcula tion according to the national regulations Construct the flue gas system as short as possible for maximum length see page20 Construct horizonal ways with a minimum angle of 3 Connecting th...

Page 20: ...e following table shows two ex amples of possible flue gas systems including the maximum possible length of the system These examples only give an indica tion of the possible length but they can not b...

Page 21: ...t opening of at least 3 mm within the boiler room This switch can be used to switch off the power supply for maintenance purposes All cables should be lead through the cable glant from the back of the...

Page 22: ...ree programmable l 120 m NTC 10K 104 105 GND BX2 Header temp Sensor l 120 m NTC 10K 108 109 GND B3 B38 DHW thermostat temp sensor Parameter l 10 m 5VDC 110 111 GND B9 Outside temp sensor l 120 m NTC 1...

Page 23: ...Installation 23 EN Wiring diagram Boiler...

Page 24: ...usion should be pre vented at all times Damage to the heat exchanger be cause of oxygene diffusion will not be taken under warranty In installations with higher water volumes it s necessary to respect...

Page 25: ...nd outlet connection Boiler connection adapter For the neutralisation are avaiable two different systems Standard neutralisation system DN The standard neutrlisation system is used when the public dra...

Page 26: ...alled with natural gas L or LPG Gas supply Flue and air intake connections Condensate connection Condenstate connection Fill the syphon as shown on the pic tures with water Check the connections make...

Page 27: ...mperature control Confirmation OK Manual mode Chimney sweeper mode Info mode Reset button Operation mode heating zone s Display Operation mode DHW Initial procedures To guarantee safety and the correc...

Page 28: ...9 4 0 2 Combustion check at minimum load Switch the boiler to minimum load 0 Check the combustion settings the same way as described for full load If necessary correct the settings with the large adju...

Page 29: ...ual p must be within 1 0 pnom P 4 0 pnom An indication of the actual flow rate can be found with the following cal culation see table below for nomi nal data Water flow data SUPAflo EVO SF61 SF62 SF63...

Page 30: ...as the plug is placed back in position the boiler will restart Flue gas temperature sensor 3 Disconnect the plug from the sensor while the boiler is switched on This should result in a lockout no 28...

Page 31: ...of mixing system etc Boiler shut down When the boiler will not be used for longer periods shut down the boiler by following procedure Switch the boiler in standby operation b Switch off the boiler wi...

Page 32: ...r kPa Plated heat exchanger Water flow m3 h Bypass boiler Pump setting Other Safety devices High limit settng C Water flow sensor checked Temp limiter setting C Fluegas sensor checked Min gas pressure...

Page 33: ...ues are not taken over by the controller By pressing the OK button it s pos sible to arrive in the next level or confirm changed values Manual mode E This button is used for switching the boiler into...

Page 34: ...OG Programming activated Heating temporarily switched off ECO ECO function active Holiday function active Reference to heating circuit Maintenance special operation No Parameter number Enduser choose...

Page 35: ...de on with Heating by time programm Temperature setpoint by heating programm Safety functions activated Summer Winter automatic switching activated ECO functions activated see indication below operati...

Page 36: ...ner symbol disappears Deaeration Press button 3 sec Press button 3 sec again 312 Deaeration on Deaeration off j Activate chimney sweeper mode Press button 3 sec Press button again 3 sec Chimney sweepe...

Page 37: ...s are positioned on the right side of the boiler Replace the ignition electrode 1 and ionisa tion electrode 2 as shown on the picture Replace the ignition and ionisa tion electrodes Clean the condens...

Page 38: ...y 1 Clean the tray Close the condens tray Cleaning and refilling the syphon Remove the syphon 3 from the condensate connection 2 Clean and fill it with fresh water Mount the syphon back in the origina...

Page 39: ...nd side of the boiler Inspect the combustion chamber by viewing through the sight glass 6 Cleaning the dirt collector Remove the syphon from the condensate connection Remove the cap 5 from the dirt co...

Page 40: ...ysis Check the combustion at full load and minumum load correct the settings if necessary An additional reference check at 50 load is rec ommended Consult the chapter commissioning combustion analy si...

Page 41: ...ump setting Safety devices High limit setting C Water flow sensor checked Temp limiter setting C Fluegas sensor checked Min gas pressure switch setting mbar Ignition time burner sec Combustion analysi...

Page 42: ...erature sensor thermostat 2 fault DHW temperature sensor thermostat 2 fault B31 78 Water pressure sensor fault water pressure sensor fault short or open circuit 81 LPB short circuit or no bus power su...

Page 43: ...Unit in parameterization mode Unit in parameterization mode para meter stick 322 Water pressure 3 too high Water pressure on input H3 too high 323 Water pressure 3 too low Water pressure on input H3 t...

Page 44: ...Resistance Ohm The diagrams show the sensor val ues for all boiler sensors and op tional sensors available in accessory kits The diagrams contain average values as all sensors are liable to tolerances...

Page 45: ...d Products 811 813 814 2013 EU Regulation This product is designated with CE number CE 0063CQ3970 EN 15502 1 EN 15502 2 1 EN 55014 1 2 EN 61000 3 2 3 EN 60 335 1 2 SUPAflo EVO Kerkrade 21 11 2016 Decl...

Page 46: ...Note 46 Note...

Page 47: ...Note 47 EN Note...

Page 48: ...proof of purchase for your warranty to be monitored All descriptions and illustrations provided in this document have been carefully prepared but we reserve the right to make changes and improvements...

Reviews: