Commissioning operation
25
MAXXfl o EVO Lite
4.4 Source
This function displays information about the live internal
operational status of the heater and it’s sensors.
.
Highlight “Source” by rotating and select the function by
pressing enter.
Use to scroll through the three pages of information avail-
able.
NB. It is not possible to reset the counters on page 3 in com-
missioning mode. Log into the heater as an “Engineer” to reset
these counters (see installation and maintenance manual sec-
tion 9.2.1).
1
Input/output test
Communication
Source
Consumer
Versions
Boiler (1/3)
8005 State boiler
Off
8009 State burner
Standby
Back
1
Useful parameters viewable in commissioning mode:
PARAMETER DESCRIPTION
NOTES
8005
State boiler
Current state of boiler
8009
State burner
Current state of burner
8316
Flue gas temp
Current temperature measured at fl ue outlet
8330
Hours run 1st stage
Total operational burner hours recorded
8331
Start counter 1st stage
Total number of burner operations started