Commissioning operation
24
MAXXfl o EVO Lite
4.3 Communication
This function gives access to the Local Process Bus and is
useful, should the optional web server be fi tted to communi-
cate with the heater.
.
Highlight “Communication” by rotating and select the func-
tion by pressing enter.
In commissioning mode only parameter line 6640 is visible.
When other compatible equipment is connected to this heater
(e.g. the optional web server) only one of the connected items
can be the clock master.
If the optional web server is connected to this heater, then
parameter line 6640 must be changed to “Slave without local
setting”, as the web server will act as the time clock master and
will provide all of connected heaters with a common time taken
from the Internet.
No adjustment for summer and winter times will be necessary if
the web server is installed, as time adjustments will be carried
out automatically.
Input/output test
Communication
Source
Consumer
Versions
LPB system
6640 Clock mode
Master
Back
1