9
8
MOUNTING
Mount the unit in a WELL VENTILATED location. Allow at
least 1 inch (2.54 cm) of clearance surrounding the unit
for adequate cooling.
The PWS1005W is designed to meet IP66 rating,and is
resistant to water spray from any direction. These units
can be mounted in wet locations but are not suitable for
submersion.
WARNING:
TO PREVENT THE RISK OF ELECTRIC SHOCK, NEVER DISCONNECT THE
INPUT OR OUTPUT WHILE THE UNIT IS ENERGIZED.
Installation
DC OUTPUT CONNECTION
This unit is equipped with two 8AWG TEW-type stranded leads terminating bare copper. The
wiring for this connection can be found on the units front panel label and is as follows:
Wire color
Polarity
Black
AC Live/Hot
Gray
AC Neutral
Green/Yellow
AC Ground
Wire color
Polarity
Black
DC Output Negative
Red
DC Output Positive
This unit’s maximum continuous output current is 40A. When connecting devices to the power
supply, ensure total connected load is less than 40A and that the wiring used is rated for this
current.
*This unit shown with the Portable Option
AC INPUT CONNECTION
This unit is equipped with a 3.05m/10.00ft 3x14AWG power cord ending in a NEMA 5-15
compatible plug suitable for connection to any typical North American AC Mains outlet. If
you need to hard-wire this connection, cut the plug off the cord and strip the wires inside, the
wiring for this cord as follows:
CAUTION:
DO NOT CONNECT THE LOAD IN THE REVERSE POLARITY!!
This will activate the reverse connection protection which will blow the output fuses inside the unit
in order to protect the device.The unit will be inoperable until these fuses have been replaced.