ViewStat Communicating Thermostat
String Feedback (Cont.)
String Description
'T-<tstat> HMODE-<val>'
Reports current humidify mode.
Parameters:
• <tstat> : id of thermostat/zone
• <val> :
OFF = disabled (no humidity control)
HUMID = humidify mode
DEHUM = dehumidify mode
AUTO = automatically controlled based on humidify and
dehumidify set points.
Example:
'T-6 HMODE-AUTO'
'T-<tstat> HOLD-<val>'
Reports current thermostat hold state.
Parameters:
• <tstat> : id of thermostat/zone
• <val> :
ON = thermostat in hold mode
OFF = thermostat no in hold mode
Example:
'T-2 HOLD-ON'
'T-<tstat> HUM-<val>'
Reports current inside humidity.
Parameters:
• <tstat> : id of thermostat/zone
• <val> : 0..100 = humidity level (%)
Example:
'T-14 HUM-56'
'T-<tstat> HUMIDIFY-val>'
Reports current humidify set point.
Parameters:
<tstat> : id of thermostat/zone
<val> : 0-97 = humidify point (in percent)
Example:
'T-6 HUMIDIFY-30'
'T-<stat> ID-<val>'
Reports identification number of thermostat.
'T-<tstat> LOCK-<val>'
Reports current thermostat lock state.
Parameters:
• <tstat> : id of thermostat/zone
• <val> :
ON = thermostat is locked
OFF = thermostat is unlocked
Example:
'T-2 LOCK-ON'
'T-<stat> MENU-<val>'
Reports Menu state, ON/OFF.
Summary of Contents for ViewStat
Page 1: ...instruction manual HVAC Controls ViewStat Communicating Thermostat...
Page 6: ...iv ViewStat Communicating Thermostat Table of Contents...
Page 12: ...Product Information 6 ViewStat Communicating Thermostat...
Page 42: ...ViewStat Installation and Wiring 36 ViewStat Communicating Thermostat...
Page 50: ...Support Module Installation and Wiring 44 ViewStat Communicating Thermostat...
Page 74: ...Operating the Thermostat 68 ViewStat Communicating Thermostat...
Page 75: ...Operating the Thermostat 69 ViewStat Communicating Thermostat...