ViewStat Installation and Wiring
15
ViewStat Communicating Thermostat
Connecting to an Axcess Control System (via AXC-232++, AXB-EM232, or Axcent3/
PRO)
To connect the ViewStat to an Axcess control system via an Axcess Cardframe (cardframe must be
equipped with an AXC-232 232/422/485 Control Card), AXB-EM232 Enhanced Master, or
Axcent3(PRO) Controller, refer to the card-edge pinout information below:
FIG. 8 shows the wiring configuration for Axcess systems:
Axcess System Card Edge Pinouts
Pin
Signal
Function
1
GND
Ground (RS-232)
2
RX
Receive data (RS-232)
3
TX
Transmit data (RS-232)
4
+12V
Power
5
RX -
Receive data (RS-422)
6
RX +
Receive data (RS-422)
7
TX -
Transmit data (RS-422)
8
TX +
Transmit data (RS-422)
9
GND
Ground
10
CTS
Clear-to-send (hardware handshaking)
11
RTS
Ready-to-send (hardware handshaking)
12-16
not used
FIG. 8
Connecting the ViewStat to an Axcess Control System
ViewStat
(Communication
terminal)
Axcess
Control
System
AXC-232(++)
or
AXB-232(++)
Summary of Contents for ViewStat
Page 1: ...instruction manual HVAC Controls ViewStat Communicating Thermostat...
Page 6: ...iv ViewStat Communicating Thermostat Table of Contents...
Page 12: ...Product Information 6 ViewStat Communicating Thermostat...
Page 42: ...ViewStat Installation and Wiring 36 ViewStat Communicating Thermostat...
Page 50: ...Support Module Installation and Wiring 44 ViewStat Communicating Thermostat...
Page 74: ...Operating the Thermostat 68 ViewStat Communicating Thermostat...
Page 75: ...Operating the Thermostat 69 ViewStat Communicating Thermostat...