NetLinx Programming
23
NXB-KNX KNX Communications Gateway
NetLinx SEND_COMMANDs (Cont.)
Command
Description
DEBUGOFF
Deactivate debug reports
Syntax:
DEBUGOFF
Example:
SEND_COMMAND dvKNX,'DEBUGOFF'
DEL
Delete Actuator from Table
Syntax:
DEL <Value>
Parameters:
<Value> = AMX Number of Actuator (range = 1 - 3000)
Example:
SEND_COMMAND dvKNX,'DEL 3'
EIS5=
Setting an EIS5 value. Converts a floating-point value mapped in ASCII into 2Byte EIS5 value before
transfer.
Note: Only valid for 2Byte Actuators
Syntax:
EIS5=<No>:<floating point value>
Parameters:
• <No> = AMX Number of Actuator (range = 1 - 3000)
• <Floating Point Value> = Number (range = –671088.64 - 670760.96)
Example:
SEND_COMMAND dvKNX,'EIS5=12:24.3'
Returns: Feedback of a value in ASCII floating point display. The actuator value to be coded
according to EIS5.
EIS5=<No>:<Value>
Note: Is transmitted as ADDITIONAL feedback, if in actuator <No> the EIS5 flag is set.
• <No> = AMX Number of Actuator
• <Value> = Floating Point Value (String), converted according to EIS Specification
Example:
EIS5=12:20.25
EIS5?
Request EIS5 value. Converts the 2Byte raw data into ASCII string with floating point notation.
Note: Only valid for 2Byte Actuators
Syntax:
EIS5?<No>
Parameters:
• <No> = AMX Number of Actuator (range = 1 - 3000)
Example:
SEND_COMMAND dvKNX,'EIS5?12'
ERRORM=
(Feedback Only)
Error message from NXB-KNX and/or bus.
Note: The messages are only for information.
Each message may reflect an actual command, followed by the error condition encountered.
Example feedback:
ERRORM=(del 99) 99 not found