background image

Configuration / Schematic

PAGE 4

LS4600 | 6 CHANNEL SPEAKER LINE SURVEILLANCE

Zone 1

Speakers Parallel

ZONE 6

 RACK MOUNT

ZONE 

VOL.CTRL.

SPEAKER 

ZONE 

SELECTOR

POWER  AMPLIFIERS

LS4600

24V DC VOLTAGE

AUDIO SIGNAL

INPUTS NOT 

SHOWN

VOLUME 

CONTROLLERS / 

PATCH PANEL

AUDIO SIGNAL

24V DC OVERRIDING

The  LS4600  detects  circuit  faults  using  impedance  measurement  method.  In  general,  there  is  no  limitation  on  how  the 

external cabling to speakers or volume controller are run, ie. branching is allow and does not need end line resistors as well 

as speaker capacitor couplings.

LS4600  have  been  improve  all  accuracy.  It  is  recommended  that  periodical  manual  checking  or  setup  to  be  made  as 

connections may deteriorate over time and thus affecting overall impedance value.

Only 4 wire system is suitable for measurement. 3 wire system may cause undesirable result each time checking is being 

made due to the presence of volume controllers.

PUBLIC ADDRESS POWER AMPLIFIER

SIGNAL -40 dB

SIGNAL -10 dB

POWER

PROTECT

CLIP

PA 2480

amperes

PUBLIC ADDRESS POWER AMPLIFIER

SIGNAL -40 dB

SIGNAL -10 dB

POWER

PROTECT

CLIP

PA 2480

amperes

ZS5121

OVERRIDE

2

1

3

5

4

SPEAKER ZONE SELECT

6

7

8

9

10

12

11

CALL

ALL

Zone 2

Direct VC

Zone 3

VC Parallel

Zone 6

Summary of Contents for LS 4600

Page 1: ...ct tapping of line to speakers as well as easier setup without having to trim impedance against a preset reference LS4600 is built and run by a micro controller thus providing a digital platform in se...

Page 2: ...N in default Menu switch is used to access main menus Once pressed momentarily it shall revert to Menu 1 0 Setup Use Next and Prev keys to scroll through other main menus Once the relevant menu is fou...

Page 3: ...ollers set in various position shall have different impedances and such circumstances shall provide false alarm or alert Recommended practice is that every zone shall have its own 24V overriding circu...

Page 4: ...resistors as well as speaker capacitor couplings LS4600 have been improve all accuracy It is recommended that periodical manual checking or setup to be made as connections may deteriorate over time an...

Page 5: ...hus a burst of audio shall be heard such as BGM being currently played Programming And Setup MAIN MENU 1 0 SETUP o 2 0 MANUAL TEST o 3 0 MEM RECALL o 4 0 AUTO TEST o 5 0 BUZZER o 6 0 LCD LIGHT o 7 0 M...

Page 6: ...ccept for monitoring or NEXT to bypass In BASIC Mode Hi and Lo function will be disabled only OPEN and SHORT monitoring available To enable Hi and Lo function use ADVANCE setup in menu 1 0 SETUP The s...

Page 7: ...for high limit and low limits are from 00 ohm to 500 ohm with incremental of 20 Ohms We recommend 50 higher or lower values to avoid unnecessary false triggering Once the required value is selected p...

Page 8: ...re To obtain the actual value use a dedicated Impedance Measurement meter This menu enable the user to view the values of impedance of selected channels which had been accepted earlier during setup Me...

Page 9: ...nu key Return to Submenu 4 0 If Off is selected If a test interval is selected from 1 min to 24 hours By default auto mode is set to off Use or key to select time ENTER If NO is selected Return to Sub...

Page 10: ...y 7 0 MEMORY o 7 0 MEMORY O RESET ENTER Press NEXT to Menu 1 0 PRE to Menu 6 0 7 1 MEMORY SAVE O Y N 7 0 MEMORY O SAVE If earlier settings are to be wiped off use this memory reset and the system shal...

Page 11: ...ut for volume controller overriding during testing mode Operating voltage 24V DC via PS9400 PSU Power consumption 3 5W Capacity 6 channel and expandable Processor PIC micro controller with 12 bit ADC...

Page 12: ...f the purchaser or the dealer for the period out of use of the unit moreover the warranty does not cover any damages which may be caused to people and things when using the product This warranty certi...