Configuration / Schematic
PAGE 4
LS4600 | 6 CHANNEL SPEAKER LINE SURVEILLANCE
Zone 1
Speakers Parallel
ZONE 6
RACK MOUNT
ZONE
VOL.CTRL.
SPEAKER
ZONE
SELECTOR
POWER AMPLIFIERS
LS4600
24V DC VOLTAGE
AUDIO SIGNAL
INPUTS NOT
SHOWN
VOLUME
CONTROLLERS /
PATCH PANEL
AUDIO SIGNAL
24V DC OVERRIDING
The LS4600 detects circuit faults using impedance measurement method. In general, there is no limitation on how the
external cabling to speakers or volume controller are run, ie. branching is allow and does not need end line resistors as well
as speaker capacitor couplings.
LS4600 have been improve all accuracy. It is recommended that periodical manual checking or setup to be made as
connections may deteriorate over time and thus affecting overall impedance value.
Only 4 wire system is suitable for measurement. 3 wire system may cause undesirable result each time checking is being
made due to the presence of volume controllers.