Ampco Pumps Company K-Series Metric Maintenance Manual M-033 Rev A 11.16
5
3.
Start the motor and immediately check the pump and suction piping for leaks.
4.
As soon as the pump reaches operating speed, open the discharge gate slowly until
complete system flow is achieved. There may be valve chatter during transient period
during valve adjustment. Be aware that the pump’s motor is specified for the flow and
pressure specified by the customer and that higher flow rates could damage the motor.
5.
Check for leaks in the discharge piping.
6.
(For pumps with pressure gauges) Open gauge cocks and record pressure reading.
Check that the pump is performing as specified by the performance curve.
Shut Down Instructions
(Note: If the pump will be shut down for an extended period refer to the Extended Duration
Shutdown)
1.
Slowly close the discharge piping gate valve. (Closing valve too quickly can cause
hydraulic shock)
2.
Turn off power supply to the pump.
Short Duration Shutdown
For short shutdown periods the pump can remain filled but make sure the pump is
fully primed prior to restarting. If the pump is subject to freezing conditions then the pump
exterior should be insulated or heated and the fluid within the pump casing must be kept
moving in order to prevent freezing.
Extended Duration Shutdown
For extended duration shutdowns close the suction piping gate valve or if no suction
valve is installed then drain the suction line to stop liquid flow to the suction nozzle. Remove
pump drain and vent tap plugs as required and completely drain the pump casing. If the pump
will be subjected to freezing conditions during shutdown then all liquid must be completely
blown out of all passages and pockets using compressed air or the pump must be filled with an
antifreeze solution to prevent damage.