AMPW 400-1000L I&O Manual
XII. Electrical
NOTICE
NOTICE
All wires, wire nuts, controls etc. are installer sup
-
plied unless otherwise noted.
When making low voltage connections, make
sure that no external power source is present in
the thermostat or limit circuits. If such a power
source is present, it could destroy the micropro
-
cessor control. One example of an external power
source that could be inadvertently connected to
the low voltage connections is a transformer with
old thermostat wiring.
To obtain total system power consumption add all
selected circulator and component current draws
Label all wires prior to servicing controls. Wiring er
-
rors can cause improper and dangerous operation.
Verify Proper operation after servicing.
A. General.
Install wiring and electrically ground the appliance in
accordance with authority having jurisdiction or, in the
absence of such requirements, follow the
National
Electrical Code
, NFPA 70, and/or
Canadian Electrical
Code
Part 1, CSA C22.1.
1. A separate electrical circuit must be run from
the main electrical service with an over-current
device/disconnect in the circuit. A service switch
is recommended and may be required by some
local jurisdictions. Install the service switch in the
line voltage “Hot” leg of the power supply. Locate
the service switch such that the appliance can be
shut-off without exposing personnel to danger in
the event of an emergency.
B. Power Requirements
1. Nominal appliance current draw is provided in
29. These values are for planning purposes only
and represent the appliance's maximum power
consumption.
AMP
Model
Voltage Phase
Hz
Appliance
Amperage
400
120
1
60
7
500
7
650
8
800
8
1000L
8
Table 29: Electrical Ratings
DANGER
DANGER
Electrical Shock Hazard:
Ensure all electrical
connections are disconnected before attempting
installation or service of electrical components or
connections of the appliance or building. Lockout
all electrical boxes with padlock once power is
turned off.
!
WARNING
WARNING
Electrical Shock Hazard:
Failure to properly wire
electrical connections on the appliance may result
in serious physical harm.
Electrical power may be from more than one
source. Make sure all power is off before attempt
-
ing any electrical work.
Each appliance must be protected with a properly
sized over-current device.
Never jump out or make inoperative any safety or
operating controls.
The wiring diagrams contained in this manual
are for reference purposes only. Each appliance
is shipped with a wiring diagram attached to the
front door. Refer to this diagram and the wiring
diagram of any controls used. Read, understand
and follow all wiring instructions supplied with
the control.
!
C. Appliance Wiring
1. Connect to the field wiring PCB's inside the rear
control box.
a. Low voltage PCB has connections for the tank
sensor, external limits, Alarm, 4-20 mA, etc. One
24V fuse and spare are provided. See Figure 24.
b. 120 VAC PCB (Figure 23) has connections for line
voltage and pumps. Do not exceed 5.6A total
pump current draw (system + DHW + boiler
pumps). One 6.3A slow-blow pump fuse and
spare are provided.
D. Routing Field Connections
1.
1. Route all field connections through conduits into
Route all field connections through conduits into
the rear control box.
the rear control box.