22
AMPW 400-1000L I&O Manual
NOTICE
NOTICE
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (poly
-
phenylsulfone) in non-metallic venting systems is prohibited.
Covering non-metallic vent pipe and fittings with thermal insulation is pro
-
hibited.
. Venting
(continued)
Table 11: Approved Vent Manufacturers and Materials
Make
Stainless Steel Brand
Polypropylene Brand
DuraVent
FasNSeal
PolyPro
Heat Fab
Saf-T Vent EZ Seal*
-
Z-Flex (Nova Flex Group)
Z-Vent
Z-DENS
Centrotherm
-
InnoFlue SW Rigid
Note: Included appliance connection is a 3-in-1 adapter that permits Stainless Steel,
Polypropylene, or CPVC.
Adapting to Z-DENS requires 4" increaser 2ZDI44 or 6" adapter 2ZDCPVCG6.
Adapting to InnoFlue requires 4" adapter ISAAL0404 or 6" adapter ISAAL0606
Table 12: Stainless Steel Vent Terminations
AMP
Model
Vent
Diameter (in.)
Style
Heat Fab Part #
Saf-T Vent
DuraVent Part #
FasNSeal
400
500
4
Tee
9490TEE
FSTT4
Elbow
9414TERM
Straight
9492
FSBS4
650
800
1000L
6
Tee
9690TEE
FSTT6
Elbow
9614TERM
Straight
9692
FSBS6
Table 13: Polypropylene Vent Terminations
AMP
Model
Vent
Diameter (in.)
Style
DuraVent Part #
PolyPro
Centrotherm Part #
InnoFlue
Z-Flex Part #
Z-DENS
400
500
4
Tee
4PPS-TTBL
ISTT0420
2ZDTT4
Elbow
4PPS-E90BC
-
2ZDE487UV
Straight
4PPS-12BC
ISEP04
2ZDES4
Screen
4PPS-BG
IASPP04
2ZDES4
650
800
1000L
6
Tee
6PPS-TTBC
ISTT0620
2ZDTT6
Elbow
6PPS-E90BC
-
2ZDE687
Straight
6PPS-12BC
-
2ZDES6
Screen
6PPS-BG
IASPP06
2ZDES6