Status:D.P. Fault
Time: 4:23:35
To Release D.P.
Fault <ENTER>
H. Handling faults
Amiad’s flushing controller can detect and respond to filter clogs. This is done by monitoring the status of the D.P. signal.
The user can configure the controller’s response through the following two screens:
Number
Screen
Description
6
Flu Til Fault: 3
Delay: 10
If by the end of a flushing cycle the D.P signal remains ON the controller
counts down the delay entered in this screen
(in seconds),
and if by the end
of this delay the D.P. is still ON a new flushing cycle starts. In case the
D.P. remains permanently ON the delay is counted again and this process
repeats till the “maximum number of flushing cycles till fault” entered at
this screen is exceeded.
Once this happens the controller enters into a Fault Status as described
below this table.
Please note that if zero is entered at the “maximum flushing cycles till
fault”, the controller never enters to “D.P. Fault Status” and continues to
initiate new flushing cycles constantly whenever the D.P. signal remains
ON.
17
DP Input: *yes
Disc filter: *no
If the lower line parameter of this screen is set to “Disc filter *yes” the
controller immediately enters to “D.P. Fault Status” whenever the D.P.
signal remains ON at the end of the first flushing cycle.
When the controller enters to D.P. Fault the main status screen
(
Screen number 2
)
shows the fault status and time.
A new screen appears to the right of the main status screen
(
Between screens 2 and 3
)
displaying the option to reset and
release the fault and the controller’s buzzer is activated.
When the controller enters to D.P. Fault check if the filters are clogged and if needed clean them manually. Check the D.P.
switch and then cancel the fault by navigating to and pressing Enter in the “Release Fault Screen” which appears between
screens 2 and 3.
Define controler
Press code - XXX
AC CONTROLLER v9
18/12/05 00:42
Status: D.P. Fault
Time: 4:23:35
For manual flush
Press <ENTER>
To Release D.P.
Fault <ENTER>
Define controler
Press code - XXX
AC CONTROLLER v9
18/12/05 00:42
Status: D.P. Fault
Time: 4:23:35
For manual flush
Press <ENTER>
To Release D.P.
Fault <ENTER>
Summary of Contents for Filtomat MG-110P
Page 5: ...MG110P 7 2013 Page 5 of 51 DIMENSIONAL DRAWINGS www irrigationglobal com ...
Page 37: ...MG110P 7 2013 Page 37 of 51 I O Terminal Connections Drawing ...
Page 42: ...MG110P 7 2013 Page 42 of 51 PARTS DRAWING 1 Page 1 ...
Page 43: ...MG110P 7 2013 Page 43 of 51 PARTS DRAWING 1 Page 2 ...
Page 45: ...MG110P 7 2013 Page 45 of 51 PARTS DRAWING 2 ...
Page 47: ...MG110P 7 2013 Page 47 of 51 PARTS DRAWING 3 www irrigationglobal com ...