5.0 TROUBLESHOOTING
This chapter covers the troubleshooting of the 3400 Series UPS,
including identifying the UPS Status, UPS emergency troubleshooting
measures and so on. Please remember that any necessary service
or repairs should be performed only by factory authorized service
personnel
5.1 UPS Status
Table 5-1 Common abnormal problems diagnosis
No. Phenomena
Fault diagnois and check-
ing points
Solution
1
SYS green
indicator on panel
is off.
Check if the mains switch is
on and if the fuse is OK.
——
Check if the mains input volt-
age is within the rated range. ——
2
The touch screen
displays wrong
phase sequence,
the buzzer beeps
continuously.
AC input phase is wrong.
Change the phase
sequence of
rectifier’s mains input
wires. Generally,
it only needs to
change two phases
among L1, L2, L3.
3
The inverter
does not operate
normally, and the
buzzer beeps
continuously.
The rectifier is not completely
started; the buzzer beeps
continuously and battery
low-voltage indicator is on;
battery input switch is not
closed.
Please wait until
rectifier finishes
starting.
Output is overload; the LOAD
overload indicator on the
panel is on.
Decrease the load.
4
During power
outage, the UPS
shuts down with
no output.
Battery input switch is
opened; check if battery
return circuit alarms
abnormally.
Close the battery
switch.
Summary of Contents for Powervar 3400 Series
Page 1: ...3400 Series UPS User s Manual 80 100 125kVA ...
Page 9: ...9 A01 00119 Rev B Tools Tools ...
Page 26: ...26 A01 00119 Rev B Figure 2 5 Normal System operation Figure 2 6 System on battery ...
Page 64: ...64 A01 00119 Rev B 9 0 PRODUCT DRAWINGS ...
Page 65: ...65 A01 00119 Rev B ...
Page 66: ...66 A01 00119 Rev B ...
Page 67: ...67 A01 00119 Rev B ...