User Interface
|
4-23
Data Type
Description
MB Starting
Regs
MB Reg Size
uint16
Current Output 2 Over range Enable. 0=dis-
abled, 1=enabled
143
1
uint16
Current Output 2 Fault Option. 0=No fault,
1=Low fault, 2=High fault.
If high fault (2):
High end of range becomes 22 mA
Output ratio becomes 1
If low fault (1) AND in 4-20 mode (ANAOUT2T
= 0):
Low end of range becomes 3 mA
Output ratio becomes 0.
144
1
uint16
Relay 1. 0=OPEN, 1=CLOSED
145
1
uint16
Relay 1 Delay. Holds the relay output for this
set amount of time.
146
1
uint16
Relay 1 Function. 0=Disabled, 1=Concentra-
tion, 3=Data Valid, 4=System alarm
147
1
uint16
Relay 1 Source. The source parameter num-
ber used to evaluated the relay function.
148
1
float
Relay 1 Value. The value used to evaluate the
relay function.
149
2
uint16
Relay 2. 0=OPEN, 1=CLOSED
151
1
uint16
Relay 2 Delay. Holds the relay output for this
set amount of time.
152
1
uint16
Relay 2 Function. 0=Disabled, 1=Concentra-
tion, 3=Data Valid, 4=System alarm
153
1
uint16
Relay 2 Source. The source parameter num-
ber used to evaluated the relay function.
154
1
float
Relay 2 Value. The value used to evaluate the
relay function.
155
2
uint16
Relay 3. 0=OPEN, 1=CLOSED
157
1
uint16
Relay 3 Delay. Holds the relay output for this
set amount of time.
158
1
uint16
Relay 3 Function. 0=Disabled, 1=Concentra-
tion, 3=Data Valid, 4=System alarm
159
1
uint16
Relay 3 Source. The source parameter num-
ber used to evaluated the relay function.
160
1
float
Relay 3 Value. The value used to evaluate the
relay function.
161
2
uint16
Relay 4. 0=OPEN, 1=CLOSED
163
1
uint16
Relay 4 Delay. Holds the relay output for this
set amount of time.
164
1
uint16
Relay 4 Function. 0=Disabled, 1=Concentra-
tion, 3=Data Valid, 4=System alarm
165
1
uint16
Relay 4 Source. The source parameter num-
ber used to evaluated the relay function.
166
1
float
Summary of Contents for 5100 HD
Page 23: ...Overview 1 11 Space Coupled Option Schematic...
Page 24: ...1 12 Model 5100 HD Analyzer This page intentionally left blank...
Page 39: ...Installation Start Up 3 11 I O Signals...
Page 50: ...3 22 Model 5100 HD Analyzer This page intentionally left blank...
Page 100: ...5 16 Model 5100 HD Analyzer This page intentionally left blank...
Page 120: ...6 20 Model 5100 HD Analyzer...