Troubleshooting
32
5.6 Testing the
Spark Protector
Refer to Figure 5-4 to test the spark protector.
Figure 5-4
Testing the Spark Protector
SCREW
TO COAX CABLE
CENTER CODUCTOR
TAB
TO SENSOR
CENTER ROD
TO
GROUND
Testing 377-1-19 Remote Spark Protector
tab - screw 47 OHMS
tab - green wire OPEN CIRCUIT
screw - green wire OPEN CIRCUIT
GREEN WIRE
METAL TAB
TO
SENSING ELEMENT
GREEN
GROUND
WIRE
TO COAX
CENTER
CONDUCTOR
TO COAX
SHIELD
WIRE
Testing 377-1-24 Integral Spark Protector
CORRECT METER READINGS
CENTER CONDUCTOR - TAB = 47 OHMS
CENTER CONDUCTOR - SHIELD WIRE = OPEN
CENTER CONDUCTOR - GROUND = OPEN
SHIELD WIRE - GROUND WIRE = OPEN
SHIELD WIRE - TAB = OPEN
TAB TO GROUND = OPEN = OPEN