Display Functionality

The location should provide adequate airflow around the UPM. Pro-

vide a minimum 3” clearance on all sides for proper ventilation.

Applying Power to the UPM

Connect the power cord to a verified grounded 3 wire receptacle. Verify 

that the Site Wiring Fault “SF” is off (120 VAC models only). Once properly 

connected and initially checked, turn on the UPM by pressing and holding the 

front panel On/Off switch for 3 seconds.

Operational Tests

Observe the front panel of the UPM. The following table shows system status 

behavior.

UPM LED DISPLAY UNIT STATUS 

UPM output on

Battery charge status in 20% increments 

UPM in battery operation due to improper incoming AC voltage

Battery fault or battery disconnected

UPM load status in 20% increments

UPM overloaded

Unit in buck operation due to high incoming AC voltage

Unit in boost operation due to low incoming AC voltage
Fault
UPM over temperature

UPM Front Panel

Output

Battery

System Status

Summary of Contents for ABCE1002-11R 58100-01R

Page 1: ...Security II Rackmount Series Uninterruptible Power Manager For use with 700VA 1000VA 1440VA 2200VA and 3000VA...

Page 2: ...0071 Rev F www powervar com 1 0 Introduction 6 2 0 Safety Instructions 8 3 0 Installation 12 4 0 Operation 17 5 0 Maintenance 22 6 0 Troubleshooting 27 7 0 Warranty 29 8 0 Specifications 30 TABLE OF C...

Page 3: ...ed to AC mains power except during utility outages Products regularly and intentionally disconnected from AC mains power will experience substantially reduced battery life AMETEK Powervar s standard w...

Page 4: ...s and conditions that can cause operator injury and or equipment damage Other warning symbols may appear along with the Danger and Caution symbol and are used to specify special hazards These warnings...

Page 5: ...5 A01 00071 Rev F www powervar com Alternating Current Refer to instruction manual booklet Two person lift...

Page 6: ...ual you have any questions at all please feel free to contact our technical support team by phone 1 800 369 7179 or email us at service powervar ametek com AMETEK Powervar is a global provider of powe...

Page 7: ...M contains a low impedance isolation transformer it completely eliminates common mode neutral to ground voltages that are a constant threat to the reliable operation of microprocessor based systems Wh...

Page 8: ...ad acid and are maintenance free Proper disposal of batteries is required Refer to your local codes for disposal of batteries UPM Rating Quantity and Battery Rating 700 VA 4 X 23W 12 VOLT 1000 VA 4 X...

Page 9: ...f a life support device Do not use this UPM near or around flammable gases Do not use this UPM within oxygen enriched atmospheres Do not disassemble the UPM UPM is CLASS 1 equipment Do not attempt to...

Page 10: ...by unplugging at its quick connectors when maintenance or service work inside the UPM is necessary Do not dispose of batteries in a fire batteries may explode Do not open or mutilate batteries Doing s...

Page 11: ...ause harmful interference to radio communications However there is no guaran tee that interference will not occur in a particular installation If this equipment does cause harmful interference to radi...

Page 12: ...uide This unit is shipped with the internal batteries disconnected Before starting the UPM please follow these battery connection instructions 1 Remove UPM from the box 2 Attached included outlet cord...

Page 13: ...13 A01 00071 Rev F www powervar com...

Page 14: ...r carton 3 Store the carton for future use Place the unit in a protected area that has adequate airflow and is free of humidity flammable gas and corrosion NOTE Before installation please read and und...

Page 15: ...cabinet using the 8 screws provided 6 For 4U UPMs attach 2 angled mounting brackets to each side of the UPM using the 16 screws provided 7 Lift the battery cabinets and UPM onto the mounting rails an...

Page 16: ...2 Send a copy of the damage claim within 15 days to your service representative WARNINGS Use all supplied mounting hardware on each UPM and External Battery Cabinet NEVER depend on devices installed...

Page 17: ...ry with no incoming AC present When the UPM is on pressing the On Off button for more than 2 seconds will turn off the UPM output power Test Silence Button The Test Silence button is a dual function c...

Page 18: ...nt panel of the UPM if it is connected to an improperly wired AC receptacle This is to indicate a missing safety ground wire or a reversal in phase and neutral wiring If the SF is displayed on the fro...

Page 19: ...on the UPM by pressing and holding the front panel On Off switch for 3 seconds Operational Tests Observe the front panel of the UPM The following table shows system status behavior UPM LED DISPLAY UNI...

Page 20: ...UPM backup function by pressing the Test Silence button on the front pan el During this test the Battery LED on the front panel should briefly illuminate It is also possible to test the backup functio...

Page 21: ...f test periodically The UPM is shipped with a charged battery but some discharge naturally occurs during storage and shipment You may use the UPM immediately but you should realize that backup time ma...

Page 22: ...hysical orientation The batteries are designed to last from two to five years Their actual life span will depend on several factors including how often power outages occur how long power outages last...

Page 23: ...re contained in this UPM Do not remove any cover other than the front battery access panels A battery even a depleted one can deliver very high currents when short circuited There is a danger of elect...

Page 24: ...while the system is running NOTE Changing the batteries in this UPM is designed to be a safe and simple procedure Batteries may be replaced while the UPM is on and providing power to the connected loa...

Page 25: ...rcuit current The following precautions should be observed when working with batteries Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not...

Page 26: ...ery s to AMETEK Powervar A01 00074 Rev C AMETEK Powerver battery packs can be replaced without turning off the power or disrupting the protected equipment After replacing the batteries in the Security...

Page 27: ...anel circuit breaker is tripped 1 Press and hold the On Off switch for 3 seconds min 2 Check wall socket and test for proper line voltage 3 Plug in input power cord 4 Reduce load and reset circuit bre...

Page 28: ...50 VAC 5 A ABCE1442 11R ABCE1442 11RMED 250 VAC 12 5 A ABCE1442 22R ABCE1442 22RMED 250 VAC 6 3 A Technical Support AMETEK Powervar provides technical product support during our regular business hours...

Page 29: ...hipment from AMETEK Powervar on the batteries This warranty is limited to repairing replacing or refurbishing at AMETEK Powervar s option any defective component circuit board or module within the Pro...

Page 30: ...20 120 Input Current 8 70 Amps 8 70 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 5 85 5 25 Amps 5 85 5 25 Amps Output Regul...

Page 31: ...52 38 23 20 15 12 10 9 Internal 1 E4804 12 1030 480 292 188 143 110 85 77 66 64 Internal 2 E4804 12 1930 870 532 338 263 200 155 142 122 119 Internal 3 E4804 12 2830 1260 772 488 383 290 225 207 178...

Page 32: ...Input Voltage 120 120 Input Current 8 70 Amps 8 70 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 5 85 5 25 Amps 5 85 5 25 A...

Page 33: ...ernal 2 E4804 12 1930 870 532 338 263 200 155 142 122 119 Internal 3 E4804 12 2830 1260 772 488 383 290 225 207 178 174 Internal 4 E4804 12 3730 1650 1012 638 503 380 295 272 234 229 Internal 5 E4804...

Page 34: ...nline Efficiency w o Charger 91 Input Voltage 230 Input Current 4 54 Amps Output Voltage 230 Output Current VA Watts 3 05 2 75 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regula...

Page 35: ...378W 70 441W 80 504W 90 567W 100 630W Internal Batteries Only 130 90 52 38 23 20 15 12 10 9 Internal 1 E4804 12 1030 480 292 188 143 110 85 77 66 64 Internal 2 E4804 12 1930 870 532 338 263 200 155 14...

Page 36: ...ry Online Efficiency w o Charger 91 Input Voltage 230 Input Current 4 54 Amps Output Voltage 230 Output Current VA Watts 3 05 2 75 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Re...

Page 37: ...0 292 188 143 110 85 77 66 64 Internal 2 E4804 12 1930 870 532 338 263 200 155 142 122 119 Internal 3 E4804 12 2830 1260 772 488 383 290 225 207 178 174 Internal 4 E4804 12 3730 1650 1012 638 503 380...

Page 38: ...t Voltage 120 120 Input Current 12 0 Amps 12 0 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 8 35 7 5 Amps 8 35 7 5 Amps Out...

Page 39: ...90 810W 100 900W Internal Batteries Only 105 52 30 20 15 12 10 8 6 5 Internal 1 E4804 12 585 292 180 120 90 72 66 53 41 35 Internal 2 E4804 12 1065 532 330 220 165 132 122 98 76 65 Internal 3 E4804 12...

Page 40: ...1 Input Voltage 120 120 Input Current 12 0 Amps 12 0 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 8 35 7 5 Amps 8 35 7 5 Am...

Page 41: ...Internal 2 E4804 12 1065 532 330 220 165 132 122 98 76 65 Internal 3 E4804 12 1545 772 480 320 240 192 178 143 111 95 Internal 4 E4804 12 2025 1012 630 420 315 252 234 188 146 125 Internal 5 E4804 12...

Page 42: ...nline Efficiency w o Charger 91 Input Voltage 230 Input Current 6 25 Amps Output Voltage 230 Output Current VA Watts 4 35 3 90 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regula...

Page 43: ...450W 60 540W 70 630W 80 720W 90 810W 100 900W Internal Batteries Only 105 52 30 20 15 12 10 8 6 5 Internal 1 E4804 12 585 292 180 120 90 72 66 53 41 35 Internal 2 E4804 12 1065 532 330 220 165 132 122...

Page 44: ...ry Online Efficiency w o Charger 91 Input Voltage 230 Input Current 6 25 Amps Output Voltage 230 Output Current VA Watts 4 35 3 90 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Re...

Page 45: ...85 292 180 120 90 72 66 53 41 35 Internal 2 E4804 12 1065 532 330 220 165 132 122 98 76 65 Internal 3 E4804 12 1545 772 480 320 240 192 178 143 111 95 Internal 4 E4804 12 2025 1012 630 420 315 252 234...

Page 46: ...Using Battery 96 to 144 Volts 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 120 Output Current VA Watts 12 0 10 8 Amps 12 0 10 8 Amps 12 0 10 8 Amps Output Regulation On Mains 10 10 10 Output...

Page 47: ...Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290 192 159...

Page 48: ...Using Battery 96 to 144 Volts 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 120 Output Current VA Watts 12 0 10 8 Amps 12 0 10 8 Amps 12 0 10 8 Amps Output Regulation On Mains 10 10 10 Output...

Page 49: ...Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290 192 159...

Page 50: ...Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 12 0 10 8 Amps 12 0 10 8 Amps Output Regulation On Mains 10 10 Output Regulation O...

Page 51: ...0 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290 192 159 141 95 82 71 8 68 5 Internal 4 E4804 12 1650 618 380 252 209 186 125 108 94 8 90 5 Internal 5 E4804 12 2040 763 470 312 259 231 15...

Page 52: ...iciency w o Charger 91 Input Voltage 230 Input Current 8 54 Amps Output Voltage 230 Output Current VA Watts 6 30 5 65 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On M...

Page 53: ...1296W Internal Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260...

Page 54: ...e Efficiency w o Charger 91 Input Voltage 230 Input Current 8 54 Amps Output Voltage 230 Output Current VA Watts 6 30 5 65 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation...

Page 55: ...8W 70 907W 80 1036W 90 1166W 100 1296W Internal Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48...

Page 56: ...ut Voltage 120 Input Current 24 0 Amps Output Voltage 120 Output Current VA Watts 18 5 16 5 Amps Input Voltage Range w o Using Battery 96 to 144 Volts Output Regulation On Mains 10 Output Regulation O...

Page 57: ...5 23 5 19 5 Internal 3 E4804 12 653 315 195 139 98 76 5 53 44 32 5 27 Internal 4 E4804 12 839 405 250 179 126 98 5 68 56 5 41 5 34 5 Internal 5 E4804 12 1025 495 305 219 154 120 5 83 69 50 5 42 Intern...

Page 58: ...ut Voltage 230 Input Current 16 0 Amps Output Voltage 230 Output Current VA Watts 9 55 8 60 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On Mains 10 Output Regulation...

Page 59: ...4 12 467 225 140 99 70 54 5 38 31 5 23 5 19 5 Internal 3 E4804 12 653 315 195 139 98 76 5 53 44 32 5 27 Internal 4 E4804 12 839 405 250 179 126 98 5 68 56 5 41 5 34 5 Internal 5 E4804 12 1025 495 305...

Page 60: ...ge 230 and 115 230 and 115 Output Current VA Watts 12 0 11 5 and 24 0 21 6 Amps 12 0 11 5 and 24 0 21 6 Amps Input Voltage Range w o Using Battery 166 to 250 Volts 184 to 276 Volts Output Regulation O...

Page 61: ...389 298 104 70 50 41 26 16 8 15 2 12 Internal 3 E4804 12 539 418 146 98 70 58 36 22 8 21 2 16 5 Internal 4 E4804 12 689 538 188 126 90 75 46 28 8 27 2 21 Internal 5 E4804 12 839 658 230 154 110 92 56...

Page 62: ...Input Voltage 230 Input Current 16 0 Amps Output Voltage 230 Output Current VA Watts 12 0 10 8 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On Mains 10 Output Regulat...

Page 63: ...2 E4804 12 389 298 104 70 50 41 26 16 8 15 2 12 Internal 3 E4804 12 539 418 146 98 70 58 36 22 8 21 2 16 5 Internal 4 E4804 12 689 538 188 126 90 75 46 28 8 27 2 21 Internal 5 E4804 12 839 658 230 15...

Page 64: ...tput Voltage 120 120 Output Current VA Watts 15 0 13 5 Amps 15 0 13 5 Amps Input Voltage Range w o Using Bat tery 96 to 144 Volts 96 to 144 Volts Output Regulation On Mains 10 10 Output Regulation On...

Page 65: ...300 188 115 96 72 54 43 35 5 29 5 Internal 3 E4804 12 975 420 263 160 136 101 76 60 49 5 41 5 Internal 4 E4804 12 1265 540 338 205 176 130 98 77 63 5 53 5 Internal 5 E4804 12 1555 660 413 250 216 159...

Page 66: ...egan IL 60085 1 800 369 7179 P 847 596 7000 F 847 596 7100 Canada Address 700 Finley Avenue Unit 3 Ajax Ontario L1S 3Z2 P 905 239 9284 Europe Asia Address Unit 5 Birch Kembrey Park Swindon Wilts SN2 8...

Reviews: