background image

45

A01-00071 Rev F

www.powervar.com

A03-00406 Rev. C

www.powervar.com

Security II Rackmount UPM Specifications

International 1000 VA Models - Medical

Front Panel Controls 

•  Power On/Off

•  Test

•  Load Level LED Gauge

•  Battery Charge LED Gauge

•  Voltage Manager Boost LED

•  Voltage Output On LED

•  Voltage Manager Buck LED

•  On Battery LED

•  Replace Battery LED

•  Overload LED

•  Fault Code LED

•  System Over Temperature LED

Rear Panel Information and Controls 

•  6 Foot Power Cord with IEC320 Plug

•  Integrated Switched Power Distribution Unit

(Requires SNMP / Web Card)

• 

Configuration Manager DIP Switches

•  Communications Manager DB9 Port, USB Port

•  Circuit Breaker (AC and DC)

•  AC Inlet Module

•  Communication Option Slot: SNMP / Web Card, Isolated

Relay Contacts Card, or Remote Off Card

•  DC External Battery Cabinet Connector

•  Fan (Forced Cooling)

Internal Batteries 

•  User Hot-Swappable (See Instruction Manual)

•  Type: 12 Volt, High Rate 23W

•  Quantity: 4 Batteries

•  Recharge Time: 6 Hours to 80%, 24 Hours to Full Charge

  (For Internal Batteries Only)

Environmental 

• 

Temperature:  0 - +40℃(32 to 104℉) Operating

-20 to 60℃(-40 to 140℉) Shipment/

Storage

•  Humidity:  

5 to 90% Non-Condensing (Operating,

Shipment/Storage)

•  Altitude:  

3,000m (10,000 ft) max. Operating; 

  

12,000m (40,000 ft) max. Shipment/Storage

Safety Agency and EMC Compliance: 

All Units are Listed by UL and Marked With the UL/cUL Marking

Standard UPM: 

Products Listed to: 

•  UL, IEC62042, CE Mark with CB Report

 

Medical UPM:

Products Listed To:

•  UL60601-1 2nd and 3rd Edition, CE Mark with CB Report

•  CSA 22.2 No. 601.1-M89

•  CSA 22.2 No. 107-1-M91

•  CSA 22.2 Nos. 0-M1982

•  CSA 22.2 Nos. 0.4-M1982

Products in Compliance with:

• 

FCC-Part 15, Subpart B, Sections 15.107b & 15.109b

Class A Digital Device*

•  CISPR11:2009, A1; 2010, Class A*

•  EN60601-1-2 : 2007

*Note: Class B is Available as an Option

Please Consult Your Powervar Sales Representative 

RoHS Compliance: 

All Products (Standard and Medical) are RoHS Compliant 

1000 VA MODELS TYPICAL RUN-TIMES (MINs)

10% 

(90W)

20% 

(180W)

30% 

(270W)

40% 

(360W)

50% 

(450W)

60% 

(540W)

70% 

(630W)

80% 

(720W)

90% 

(810W)

100% 

(900W)

Internal Batteries Only

105

52

30

20

15

12

10

8

6

5

In 1) E4804-12

585

292

180

120

90

72

66

53

41

35

In 2) E4804-12

1065

532

330

220

165

132

122

98

76

65

In 3) E4804-12

1545

772

480

320

240

192

178

143

111

95

In 4) E4804-12

2025

1012

630

420

315

252

234

188

146

125

In 5) E4804-12

2505

1252

780

520

390

312

290

233

181

155

In 6) E4804-12

2985

1492

930

620

465

372

346

278

216

185

In 7) E4804-12

3465

1732

1080

720

540

432

402

323

251

215

In 8) E4804-12

3945

1972

1230

820

615

492

458

368

286

245

NOISE REJECTION-ISOLATION: 

With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise 

output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).

SURGE VOLTAGE WITHSTAND CAPABILITY:

 Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200 amps, 0.5 

usec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 usec risetime, 100 kHZ decay.

Warranty/Support: 

Powervar warrants the electronics and transformers used in its uninterruptible power managers to be free from defects in materials and work-

manship for a period of five years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment. For service or support on 

any Powervar product, please contact Powervar Technical Support at (800) 369-7179 or visit the Powervar website at 

www.powervar.com

.

Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power, 

except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge 

cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially 

reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and 

intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.

Security II Rackmount UPM Specifications

International 1000 VA Models - Medical

Summary of Contents for ABCE1002-11R 58100-01R

Page 1: ...Security II Rackmount Series Uninterruptible Power Manager For use with 700VA 1000VA 1440VA 2200VA and 3000VA...

Page 2: ...0071 Rev F www powervar com 1 0 Introduction 6 2 0 Safety Instructions 8 3 0 Installation 12 4 0 Operation 17 5 0 Maintenance 22 6 0 Troubleshooting 27 7 0 Warranty 29 8 0 Specifications 30 TABLE OF C...

Page 3: ...ed to AC mains power except during utility outages Products regularly and intentionally disconnected from AC mains power will experience substantially reduced battery life AMETEK Powervar s standard w...

Page 4: ...s and conditions that can cause operator injury and or equipment damage Other warning symbols may appear along with the Danger and Caution symbol and are used to specify special hazards These warnings...

Page 5: ...5 A01 00071 Rev F www powervar com Alternating Current Refer to instruction manual booklet Two person lift...

Page 6: ...ual you have any questions at all please feel free to contact our technical support team by phone 1 800 369 7179 or email us at service powervar ametek com AMETEK Powervar is a global provider of powe...

Page 7: ...M contains a low impedance isolation transformer it completely eliminates common mode neutral to ground voltages that are a constant threat to the reliable operation of microprocessor based systems Wh...

Page 8: ...ad acid and are maintenance free Proper disposal of batteries is required Refer to your local codes for disposal of batteries UPM Rating Quantity and Battery Rating 700 VA 4 X 23W 12 VOLT 1000 VA 4 X...

Page 9: ...f a life support device Do not use this UPM near or around flammable gases Do not use this UPM within oxygen enriched atmospheres Do not disassemble the UPM UPM is CLASS 1 equipment Do not attempt to...

Page 10: ...by unplugging at its quick connectors when maintenance or service work inside the UPM is necessary Do not dispose of batteries in a fire batteries may explode Do not open or mutilate batteries Doing s...

Page 11: ...ause harmful interference to radio communications However there is no guaran tee that interference will not occur in a particular installation If this equipment does cause harmful interference to radi...

Page 12: ...uide This unit is shipped with the internal batteries disconnected Before starting the UPM please follow these battery connection instructions 1 Remove UPM from the box 2 Attached included outlet cord...

Page 13: ...13 A01 00071 Rev F www powervar com...

Page 14: ...r carton 3 Store the carton for future use Place the unit in a protected area that has adequate airflow and is free of humidity flammable gas and corrosion NOTE Before installation please read and und...

Page 15: ...cabinet using the 8 screws provided 6 For 4U UPMs attach 2 angled mounting brackets to each side of the UPM using the 16 screws provided 7 Lift the battery cabinets and UPM onto the mounting rails an...

Page 16: ...2 Send a copy of the damage claim within 15 days to your service representative WARNINGS Use all supplied mounting hardware on each UPM and External Battery Cabinet NEVER depend on devices installed...

Page 17: ...ry with no incoming AC present When the UPM is on pressing the On Off button for more than 2 seconds will turn off the UPM output power Test Silence Button The Test Silence button is a dual function c...

Page 18: ...nt panel of the UPM if it is connected to an improperly wired AC receptacle This is to indicate a missing safety ground wire or a reversal in phase and neutral wiring If the SF is displayed on the fro...

Page 19: ...on the UPM by pressing and holding the front panel On Off switch for 3 seconds Operational Tests Observe the front panel of the UPM The following table shows system status behavior UPM LED DISPLAY UNI...

Page 20: ...UPM backup function by pressing the Test Silence button on the front pan el During this test the Battery LED on the front panel should briefly illuminate It is also possible to test the backup functio...

Page 21: ...f test periodically The UPM is shipped with a charged battery but some discharge naturally occurs during storage and shipment You may use the UPM immediately but you should realize that backup time ma...

Page 22: ...hysical orientation The batteries are designed to last from two to five years Their actual life span will depend on several factors including how often power outages occur how long power outages last...

Page 23: ...re contained in this UPM Do not remove any cover other than the front battery access panels A battery even a depleted one can deliver very high currents when short circuited There is a danger of elect...

Page 24: ...while the system is running NOTE Changing the batteries in this UPM is designed to be a safe and simple procedure Batteries may be replaced while the UPM is on and providing power to the connected loa...

Page 25: ...rcuit current The following precautions should be observed when working with batteries Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not...

Page 26: ...ery s to AMETEK Powervar A01 00074 Rev C AMETEK Powerver battery packs can be replaced without turning off the power or disrupting the protected equipment After replacing the batteries in the Security...

Page 27: ...anel circuit breaker is tripped 1 Press and hold the On Off switch for 3 seconds min 2 Check wall socket and test for proper line voltage 3 Plug in input power cord 4 Reduce load and reset circuit bre...

Page 28: ...50 VAC 5 A ABCE1442 11R ABCE1442 11RMED 250 VAC 12 5 A ABCE1442 22R ABCE1442 22RMED 250 VAC 6 3 A Technical Support AMETEK Powervar provides technical product support during our regular business hours...

Page 29: ...hipment from AMETEK Powervar on the batteries This warranty is limited to repairing replacing or refurbishing at AMETEK Powervar s option any defective component circuit board or module within the Pro...

Page 30: ...20 120 Input Current 8 70 Amps 8 70 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 5 85 5 25 Amps 5 85 5 25 Amps Output Regul...

Page 31: ...52 38 23 20 15 12 10 9 Internal 1 E4804 12 1030 480 292 188 143 110 85 77 66 64 Internal 2 E4804 12 1930 870 532 338 263 200 155 142 122 119 Internal 3 E4804 12 2830 1260 772 488 383 290 225 207 178...

Page 32: ...Input Voltage 120 120 Input Current 8 70 Amps 8 70 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 5 85 5 25 Amps 5 85 5 25 A...

Page 33: ...ernal 2 E4804 12 1930 870 532 338 263 200 155 142 122 119 Internal 3 E4804 12 2830 1260 772 488 383 290 225 207 178 174 Internal 4 E4804 12 3730 1650 1012 638 503 380 295 272 234 229 Internal 5 E4804...

Page 34: ...nline Efficiency w o Charger 91 Input Voltage 230 Input Current 4 54 Amps Output Voltage 230 Output Current VA Watts 3 05 2 75 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regula...

Page 35: ...378W 70 441W 80 504W 90 567W 100 630W Internal Batteries Only 130 90 52 38 23 20 15 12 10 9 Internal 1 E4804 12 1030 480 292 188 143 110 85 77 66 64 Internal 2 E4804 12 1930 870 532 338 263 200 155 14...

Page 36: ...ry Online Efficiency w o Charger 91 Input Voltage 230 Input Current 4 54 Amps Output Voltage 230 Output Current VA Watts 3 05 2 75 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Re...

Page 37: ...0 292 188 143 110 85 77 66 64 Internal 2 E4804 12 1930 870 532 338 263 200 155 142 122 119 Internal 3 E4804 12 2830 1260 772 488 383 290 225 207 178 174 Internal 4 E4804 12 3730 1650 1012 638 503 380...

Page 38: ...t Voltage 120 120 Input Current 12 0 Amps 12 0 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 8 35 7 5 Amps 8 35 7 5 Amps Out...

Page 39: ...90 810W 100 900W Internal Batteries Only 105 52 30 20 15 12 10 8 6 5 Internal 1 E4804 12 585 292 180 120 90 72 66 53 41 35 Internal 2 E4804 12 1065 532 330 220 165 132 122 98 76 65 Internal 3 E4804 12...

Page 40: ...1 Input Voltage 120 120 Input Current 12 0 Amps 12 0 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 8 35 7 5 Amps 8 35 7 5 Am...

Page 41: ...Internal 2 E4804 12 1065 532 330 220 165 132 122 98 76 65 Internal 3 E4804 12 1545 772 480 320 240 192 178 143 111 95 Internal 4 E4804 12 2025 1012 630 420 315 252 234 188 146 125 Internal 5 E4804 12...

Page 42: ...nline Efficiency w o Charger 91 Input Voltage 230 Input Current 6 25 Amps Output Voltage 230 Output Current VA Watts 4 35 3 90 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regula...

Page 43: ...450W 60 540W 70 630W 80 720W 90 810W 100 900W Internal Batteries Only 105 52 30 20 15 12 10 8 6 5 Internal 1 E4804 12 585 292 180 120 90 72 66 53 41 35 Internal 2 E4804 12 1065 532 330 220 165 132 122...

Page 44: ...ry Online Efficiency w o Charger 91 Input Voltage 230 Input Current 6 25 Amps Output Voltage 230 Output Current VA Watts 4 35 3 90 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Re...

Page 45: ...85 292 180 120 90 72 66 53 41 35 Internal 2 E4804 12 1065 532 330 220 165 132 122 98 76 65 Internal 3 E4804 12 1545 772 480 320 240 192 178 143 111 95 Internal 4 E4804 12 2025 1012 630 420 315 252 234...

Page 46: ...Using Battery 96 to 144 Volts 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 120 Output Current VA Watts 12 0 10 8 Amps 12 0 10 8 Amps 12 0 10 8 Amps Output Regulation On Mains 10 10 10 Output...

Page 47: ...Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290 192 159...

Page 48: ...Using Battery 96 to 144 Volts 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 120 Output Current VA Watts 12 0 10 8 Amps 12 0 10 8 Amps 12 0 10 8 Amps Output Regulation On Mains 10 10 10 Output...

Page 49: ...Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290 192 159...

Page 50: ...Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 12 0 10 8 Amps 12 0 10 8 Amps Output Regulation On Mains 10 10 Output Regulation O...

Page 51: ...0 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290 192 159 141 95 82 71 8 68 5 Internal 4 E4804 12 1650 618 380 252 209 186 125 108 94 8 90 5 Internal 5 E4804 12 2040 763 470 312 259 231 15...

Page 52: ...iciency w o Charger 91 Input Voltage 230 Input Current 8 54 Amps Output Voltage 230 Output Current VA Watts 6 30 5 65 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On M...

Page 53: ...1296W Internal Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260...

Page 54: ...e Efficiency w o Charger 91 Input Voltage 230 Input Current 8 54 Amps Output Voltage 230 Output Current VA Watts 6 30 5 65 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation...

Page 55: ...8W 70 907W 80 1036W 90 1166W 100 1296W Internal Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48...

Page 56: ...ut Voltage 120 Input Current 24 0 Amps Output Voltage 120 Output Current VA Watts 18 5 16 5 Amps Input Voltage Range w o Using Battery 96 to 144 Volts Output Regulation On Mains 10 Output Regulation O...

Page 57: ...5 23 5 19 5 Internal 3 E4804 12 653 315 195 139 98 76 5 53 44 32 5 27 Internal 4 E4804 12 839 405 250 179 126 98 5 68 56 5 41 5 34 5 Internal 5 E4804 12 1025 495 305 219 154 120 5 83 69 50 5 42 Intern...

Page 58: ...ut Voltage 230 Input Current 16 0 Amps Output Voltage 230 Output Current VA Watts 9 55 8 60 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On Mains 10 Output Regulation...

Page 59: ...4 12 467 225 140 99 70 54 5 38 31 5 23 5 19 5 Internal 3 E4804 12 653 315 195 139 98 76 5 53 44 32 5 27 Internal 4 E4804 12 839 405 250 179 126 98 5 68 56 5 41 5 34 5 Internal 5 E4804 12 1025 495 305...

Page 60: ...ge 230 and 115 230 and 115 Output Current VA Watts 12 0 11 5 and 24 0 21 6 Amps 12 0 11 5 and 24 0 21 6 Amps Input Voltage Range w o Using Battery 166 to 250 Volts 184 to 276 Volts Output Regulation O...

Page 61: ...389 298 104 70 50 41 26 16 8 15 2 12 Internal 3 E4804 12 539 418 146 98 70 58 36 22 8 21 2 16 5 Internal 4 E4804 12 689 538 188 126 90 75 46 28 8 27 2 21 Internal 5 E4804 12 839 658 230 154 110 92 56...

Page 62: ...Input Voltage 230 Input Current 16 0 Amps Output Voltage 230 Output Current VA Watts 12 0 10 8 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On Mains 10 Output Regulat...

Page 63: ...2 E4804 12 389 298 104 70 50 41 26 16 8 15 2 12 Internal 3 E4804 12 539 418 146 98 70 58 36 22 8 21 2 16 5 Internal 4 E4804 12 689 538 188 126 90 75 46 28 8 27 2 21 Internal 5 E4804 12 839 658 230 15...

Page 64: ...tput Voltage 120 120 Output Current VA Watts 15 0 13 5 Amps 15 0 13 5 Amps Input Voltage Range w o Using Bat tery 96 to 144 Volts 96 to 144 Volts Output Regulation On Mains 10 10 Output Regulation On...

Page 65: ...300 188 115 96 72 54 43 35 5 29 5 Internal 3 E4804 12 975 420 263 160 136 101 76 60 49 5 41 5 Internal 4 E4804 12 1265 540 338 205 176 130 98 77 63 5 53 5 Internal 5 E4804 12 1555 660 413 250 216 159...

Page 66: ...egan IL 60085 1 800 369 7179 P 847 596 7000 F 847 596 7100 Canada Address 700 Finley Avenue Unit 3 Ajax Ontario L1S 3Z2 P 905 239 9284 Europe Asia Address Unit 5 Birch Kembrey Park Swindon Wilts SN2 8...

Reviews: