59
A01-00071 Rev F
www.powervar.com
A03-00435 - Rev. D 2
www.powervar.com
Front Panel Controls
Power On/Off
Test
Load Level LED Gauge
Battery Charge LED Gauge
Voltage Manager Boost LED
Voltage Output On LED
Voltage Manager Buck LED
On Battery LED
Replace Battery LED
Overload LED
Fault Code LED
System Over Temperature LED
Rear Panel Information and Controls
1.8 Meter Power Cord with C20 to C19 IEC300
Configuration Manager DIP Switches
Communications Manager DB9 Port, USB Port
Circuit Breaker
AC Inlet Module
SNMP Slot (Contact Factory)
Internal Batteries
User Hot-Swappable (See Instruction Manual)
Type: 12 Volt, High Rate 23W
Quantity: 8 Batteries
Recharge Time: 8 Hours to 80%, 24 Hours to Full Charge
Environmental
Temperature: 0 - +40
0
C (32 to 104
0
F) Operating
-20 to 60
0
C (-40 to 140
0
F) Shipment/
Storage
Humidity: 5 to 90% Non-Condensing (Operating,
Shipment/Storage)
Altitude: 3,000m (10,000 ft) max. Operating;
12,000m (40,000 ft) max. Shipment/Storage.
Safety Agency and EMC Compliance:
All Units are Listed by UL and Marked with the UL/cUL Marking.
Standard UPM:
Products Listed To:
UL IEC62040, CE Mark with CB Report
Products in compliance with:
FCC-Part 15, Subpart B, Sections 15.107b & 15.109b
Class A Digital Device*
CISPR11:2009, A1; 2010, Class A*
IEC61000-4-2, Electrostatic Discharge
IEC61000-4-3, Radiated Electromagnetic Field Immunity
IEC61000-4-4, Electrical Fast Transient/Burst Immunity
IEC61000-4-5, Surge Immunity
IEC61000-4-6, Immunity to Conducted Radio Frequency
Disturbances
IEC61000-4-8, Power Frequency Magnetic Field Immunity
IEC61000-4-11, Voltage Dips, Short Interruptions, and
Voltage Variations
*Note: Class B is Available as an Option
Please Consult Your Powervar Sales Representative
RoHS Compliance:
All Products (Standard and Medical) are RoHS Compliant
2200VA TYPICAL RUN-TIMES (MINs)
10% (198W) 20% (396W) 30% (594W) 40% (792W) 50% (990W) 60% (1188W) 70% (1386W) 80% (1584W) 90% (1782W)
100%
(1980W)
Internal Batteries Only
95
45
30
19
14
10.5
8
6.5
5.5
4.5
In 1) E4804-12
281
135
85
59
42
32.5
23
19
14.5
12
In 2) E4804-12
467
225
140
99
70
54.5
38
31.5
23.5
19.5
In 3) E4804-12
653
315
195
139
98
76.5
53
44
32.5
27
In 4) E4804-12
839
405
250
179
126
98.5
68
56.5
41.5
34.5
In 5) E4804-12
1025
495
305
219
154
120.5
83
69
50.5
42
In 6) E4804-12
1211
585
360
259
182
142.5
98
81.5
59.5
49.5
In 7) E4804-12
1397
675
415
299
210
164.5
113
94
68.5
57
In 8) E4804-12
1583
765
470
339
238
186.5
128
106.5
77.5
64.5
NOISE REJECTION-ISOLATION:
With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode
at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-
NM, CM-CM, NM-COM).
SURGE VOLTAGE WITHSTAND CAPABILITY:
Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A -
6000V @ 200 amps, 0.5 usec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 usec risetime, 100 kHZ decay.
Warranty/Support:
POWERVAR warrants the electronics and transformers used in its uninterruptible power managers to be free from
defects in materials and workmanship for a period of five years from the date of shipment. Batteries are warranted for a period of two years from
the date of shipment. For service or support on any POWERVAR product, please contact POWERVAR Technical Support at (800) 369-7179 or
visit the POWERVAR website at
ww.powervar.com
.
Battery Life Disclaimer
: POWERVAR’s standard battery warranty applies only to UPS and UPM products which are continuously connected to
AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will
experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products
used in such applications will experience substantially reduced battery life. For that reason, POWERVAR’s standard battery warranty does not
apply for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. POWERVAR UPS and
UPM products used in such applications shall receive a 90 day warranty on batteries.
Security II UPM Specifications
International Models ABCE2202-22R