15
A01-00071 Rev F
www.powervar.com
Rackmount Installation Guide
** Example of 4U unit
* Example of a 2U unit
1.
Assemble the side rails and
secure each with (2) screws.
DO NOT TIGHTEN.
2.
Attach front of the rails to
front of rack with (1) fastener
for each side in the upper
mounting hole.
3.
Attach rear of rails to rear of
rack with the (2) fasteners for
each side.
4.
Tighten the (2) screws used to
assemble each rail in step 1.
5.
For 2U
*
UPMs and battery
cabinets, attach (1) angled
mounting bracket to each side
of the UPM and/or each side
of the battery cabinet using
the (8) screws provided.
6.
For 4U
**
UPMs - attach (2)
angled mounting brackets to
each side of the UPM using
the (16) screws provided.
7.
Lift the battery cabinets and
UPM onto the mounting rails
and slide each into position.
8.
Secure the 2U UPM and
battery cabinet with (4)
fasteners and the 4U UPMs
with (8) fasteners provided.
Rackmount UPM and the
external battery cabinet are
designed to be floor standing as
an alternative to rack mounting.
The UPM and external battery
cabinets use identical mounting
hardware and the procedure for
mounting is the same for both.
Each unit and each battery
cabinet must be mounted
to their own rail kits that
are included.
Floor Standing Installtion
Middle Rack Installation
Standard Rack Installation