18-CE15D1-1C-EN
43
Setting Airflow
With all ductwork connected and a clean filter in place, measure the
External Static Pressure (ESP) of the unit in locations below. Use the
appropriate airflow table for the furnace and outdoor unit installed.
Measurements must be made prior to the evaporator coil, if equipped,
and after the filter.
Evaporator
Coil
Clean
Filter
Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static Pressure with Filter
Model
Airflow
Setting
CFM/Ton
EXTERNAL STATIC PRESSURE (IN. W. C.)
0.1
0.3
0.5
0.7
0.9
L8V1C100U5VSAA
450
CFM
1773
1769
1765
1760
1754
WATTS
364
430
501
576
653
420
CFM
1654
1652
1649
1646
1640
WATTS
301
364
431
503
577
400
CFM
1575
1574
1572
1569
1564
WATTS
264
324
390
459
530
370
CFM
1456
1456
1455
1452
1447
WATTS
214
271
333
399
467
350
CFM
1378
1377
1377
1374
1368
WATTS
184
239
299
363
429
330
CFM
1299
1299
1297
1294
1288
WATTS
158
210
268
330
394
310
CFM
1220
1219
1217
1213
1206
WATTS
134
185
240
300
362
290
CFM
1141
1140
1137
1131
1122
WATTS
113
161
215
272
333
This is an example Airflow Table only. See Service Facts for complete airflow data.