background image

NOTE: L.P. (propane bottled) gas models have reverse (left

handed) thread on the manifold.

WARNING

DO NOT apply any thread sealant (pipe dope, teflon tape, etc.)

to these connections.

REMOVAL OF THE BURNER ASSEMBLY

For your safety the following procedure should be performed

by qualified service personnel or someone familiar with gas

appliances, as it involves disconnection of gas piping and leak

testing .
1.  Turn gas control knob clockwise to “OFF” position. (Page

9 or 10).

2.  Open outer and inner doors.
3. Disconnect the thermocouple, pilot tube, and manifold

tube at the thermostat (Figure 7). Note that the propane
(LPG) manifold has left hand thread rotation.

4.  Remove the burner spreader by removing the nuts on top

of the spreader.

5.  Pull the burner toward the front until the holding bracket

slides out of the slot in the bottom pan. If the burner is
dirty or clogged it cab be cleaned with soap and water.

REPLACING THE BURNER ASSEMBLY

1.  Insert the burner assembly into the opening in the bottom

pan and slide toward the rear so that the burner holding

bracket slides into the slot in the bottom pan. Reinsert the

spreader on to the burner post and replace the two nuts.

2. The manifold tube will now line up to the thermostat

connection.

3.  Reconnect the manifold tube and pilot tube. Do not cross

thread these fittings (Figure 7) . Note that the propane

(LPG) manifold has left hand thread rotation.

4.  Reconnect the thermocouple.The thermocouple nut should

be started and turned all the way in by hand. An additional

one-quarter turn with a 3/8” open end wrench will be

sufficient to set the lockwasher (Figure 7).

CAUTION: OVERTIGHTENING MAY DAMAGE
THE THERMOCOUPLE OR THERMOS TAT.

5. Follow Lighting Instructions to relight water heater.

6. Check for gas leaks with soap and water solution (soap

suds) or liquid detergent. Bubble forming indicates a leak.

FIX ALL LEAKS  IMMEDIATELY.

WARNING

DO NOT US E OPEN FLAME OR ANY KIND OF
S PARK TO CHECK FOR LEAKS .

12

130931 Rev April ʻ07

THERMOCOUPLE AND/OR
PILOT REPLACEMENT

1.  Remove burner assembly. (See “REMOVAL OF BURNER

ASSEMBLY” section.)

2.  Grasp the thermocouple line and moderately pull the ther-

mocouple from the pilot burner assembly. NOTE: If for

any reason the thermocouple will not disengage from the

pilot bracket assembly, replace the complete pilot

assembly, follow steps 4 and 5, otherwise go to next step.

3. Push replacement thermocouple through hole in pilot

bracket until it snaps in place. The end of a properly

installed thermocouple should extend approximately 1/4

inch past the tip of the pilot assembly (Go to step 6).

4. Remove No. 8-32 screw holding pilot assembly and pilot

shield (if provided) to main burner (Figure 8, Page 16).

5. Re-install replacement pilot assembly to main burner mak-

ing sure that pilot shield (if provided) is in the right

location. (Figure 8, Page 16).

6. Replace burner assembly (See “REPLACING THE

BURNER ASSEMBLY” section).

DRAINING AND FLUSHING
INTERIOR OF TANK

The water heater should be drained if being shut down during

freezing temperatures. Also periodic draining and cleaning of

sediment from the tank may be necessary.
1. “TURN OFF GAS TO APPLIANCE.” (Figure 6)
2. Close the cold water inlet valve to the heater (Figure 6).
3. Open a nearby hot water faucet.
4. Open the heater drain valve. (Figure 6).

WARNING

THIS  WATER CAN BE HOT.

5.  If the heater is going to be shut down and drained for an

extended period, the drain valve should be left open. Refer

to “Hydrogen Gas” warning, Page 8.

6. To start heater again, read paragraph “Operation” and

“LIGHTING INSTRUCTIONS”.

VENTING SYSTEM INSPECTION

Check the draft hood relief opening (Figure 6) using a match

flame after 15 minutes of operation. Pass the match flame

around the relief opening of the draft hood. A steady flame

drawn into the opening indicates proper draft. If the flame

flutters or is blown out this would indicate spillage and

corrective action must be made to the vent. (Figure 6).

At least every 3 months a visual inspection should be made of

the venting system. You should look for:
• Obstructions which cause improper venting.

• Damage or deterioration which could cause improper

venting or leakage of combustion products.

TAMPERING

Tampering with the thermostat, gas valve, pilot, burner, or

temperature and pressure relief valve is DANGEROUS and

voids all warranties. Only qualified personnel should service

these components.

C

A

U

T I

O

N

LOOSEN
THREAD

ROTATION

SEE NOTE BELOW

TIGHTEN

THREAD

ROTATION

SEE NOTE BELOW

Right Hand

Right Hand

thermocouple

pilot tube 

manifold

Summary of Contents for 100-83 AS

Page 1: ...type gas only Check the data plate near the gas control valve for the correct gas DO NOT USE THIS WATER HEATER WITH ANY GAS OTHER THEN THE ONE LISTED ON THE DATA PLATE Failure to use the correct gas c...

Page 2: ...e same room or area near the water heater Keep flammable products 1 far away from heater 2 in approved containers 3 tightly closed and 4 out of children s reach Installation Do not install water heate...

Page 3: ...IONS TEMPERATURE ADJUSTMENT BURNER ADJUSTMENT BURNER MAINTENANCE EMERGENCY SHUT DOWN REMOVAL OF BURNER ASSEMBLY REPLACING BURNER ASSEMBLY THERMOCOUPLE AND OR PILOT REPLACEMENT DRAINING AND FLUSHING IN...

Page 4: ...EATER AND TO PROVIDE IMPORTANT SAFETY INFORMATION WE URGE YOU TO READ ALL INSTRUCTIONS THOROUGHLY before attempting installation or operation of your water heater Keep these instructions for future re...

Page 5: ...ld include those areas where flam mable liquids such as gasoline solvents liquefied propane or butane etc or other substances such as adhesives etc all of which emit flammable vapors may be improperly...

Page 6: ...nimum free area of 1 square inch per 4 000 BTU per hour of total input rating of all equipment in the enclosure Figure 4 3 When communicating with the outdoors through horizontal ducts each duct openi...

Page 7: ...130931 Rev April 07 4...

Page 8: ...t cracking of the gas valve inlet housing The suggested maximum torque is 31 5 ft Ibs The manufacturer of this water heater will not be liable for any damage or injury caused as a result of a cracked...

Page 9: ...treatment or any chemicals to any heat piping since the piping contains potable water DO NOT use with ferrous piping The system should be installed only with new piping that is suitable for potable w...

Page 10: ...ided in flue tube heater fittings as they may contain nonmetallic parts When making these connections always use a good grade of pipe joint compound and be certain that all fittings are drawn up tight...

Page 11: ...light matches Do not smoke 4 DO NOT touch electrical switches on or off 5 Extinguish any open flames 6 Shut off gas at manual shut off valve 8 130931 Rev April 07 7 Use an outside phone and immediate...

Page 12: ...uld remain lit If it goes out repeat steps 3 through 8 8b For Gas LP Light match and hold to pilot While holding lightedmatch to pilot depress the gas control knob all the way hold until pilot lights...

Page 13: ...4 Depress gas control knob slightly and turn clockwise to OFF If knob is in ON turn clock wise to PILOT then depress knob slightly and turn clockwise to OFF NOTE Knob cannot be turned from PILOT to O...

Page 14: ...gy Cut Off The Energy Cut Off will shut off all gas supplied to the Burner and pilot Burner in the event the water temperature exceeds 180 F The Energy Cut Off switch is a single use switch and is not...

Page 15: ...he pilot burner assembly NOTE If for any reason the thermocouple will not disengage from the pilot bracket assembly replace the complete pilot assembly follow steps 4 and 5 otherwise go to next step 3...

Page 16: ...ATER DO NOT ATTEMPT TO SERVICE THE WATER HEATER OR PERFORM OTHER RECOMMENDATIONS ON THIS LIST UNLESS YOU ARE TRAINED AND QUALIFIED TO DO SO SYMPTOM Burner will not ignite Burner flame floats Lifts off...

Page 17: ...tacking 3 Closed water system CORRECTIVE ACTION 1 Check with utility 2 Replace with new thermostat 1 Check with utility 2 Check with utility 3 Notify utility install dirt trap in gas lines 4 Clean che...

Page 18: ...ice clogged 3 Wrong pilot burner 1 Wrong pilot burner 1 Sulfides in the water CORRECTIVE ACTION 1 Replace with new thermostat control value 2 Replace control valve 1 See page 8 and 11 1 Provide ventil...

Page 19: ...17 19 8 10 16 LEGEND Special anode rod see page 13 Temperature Pressure Relief Valve is required but may not be factory installed It is imperative the replacement main burner main burner orifice mani...

Reviews: