american flame AF-4000 Series Manual Download Page 10

 

 

 

REV. 4-6-2010   

Page 10 of 11

   

 
 
 

Equipment Danger Hazard. Improper adjustment of gas input and burner can cause carboning and/or 
unnecessary shutdown of the system.

 

1.  Do not exceed the input rating stamped on the appliance nameplate, or manufacture recommended burner orifice 

pressure for size orifice(s) used. Be sure primary air supply to the main burner is properly adjusted for complete 
combustion. Follow the instructions of the appliance manufacturer. 

2.  IF CHECKING GAS INPUT BY CLOCKING GAS METER: Be sure there is no gas flow through the meter other that to 

the appliance being checked. Other appliances must remain off with the pilots extinguished (or the consumption must 
be deducted from the meter reading). Convert the flow rate to Btuh as described in the GAS Controls Handbook, from 
70-2602, and compare to the Btuh input rating on the appliance nameplate. 

3. 

IF CHECKING GAS INPUT WITH MANOMETER: Both the input and output pressure taps have a captive screw. To 
measure the pressure of the tap, loosen, but do not remove the captive screw, attach a plastic tube with a 1/3 in. shell 
I.D. and connect the manometer. After checking the pressure, turn the gas control knob to the OFF position, Before 
opening the outlet pressure tap, be sure the gas control knob is in the OFF position. Before opening the inlet pressure 
tap, shut the gas supply at the manual valve in the gas piping to the appliance or, for LP, at the tank. Repeat the Gas 
LeakTest at the pressure tap with mainburner operating.

 

 

MAINTENANCE 

 
 
 
Fire or explosion hazard. Can cause property damage, severe injury or death. 

Do not attempt to take a part the gas control or to clean it. Improper assembly and cleaning can cause unreliable 
operation. 
Regular preventive maintenance is important in applications that place a heavy load on the system such as those used in 
commerical cooking, agricultural, and industrial application because: 
 

  In many such applications, particularly commerical cooking, the equipment operates 100,000 to 200,000 cycles per 

year. Such heavy cycling can wear out the gas control in one to two years. 

  Exposure to water, dirt, chemicals, and heat can damage the gas control and shut down the control system. 

The maintance program should include regular checkout of the system as outlined in the Checkout section, and checkout 
the system as discribed in the appliance manufacturers literature.  
Maintance frequency must be determined individually for each application, Some considerations are: 
 

  Cycling frequency. Appliances that may cycle 20,000 times annually should be checked monthly. 

  Intermittent use. Appliances that are used seasonally should be checked before shutdown and again before the next 

use. 

  Consequence of unexpected shutdown, where the cost of an unexpected shutdown would be high, and the system 

should be checked more often. 

  Dusty, wet, or corrosive envirornment. Because these environments can cause the gas control to deteriorate more 

rapidly, the system should be checked more often. 

Any control should be replaced if it does not perform properly on checkout or service. In addition, replace any module if it 
is wet or looks like it has been wet. 
 

SERVICE

 

 
 
 
Fire or explosion hazard. Can cause property damage, severe injury or death. 

Do not disassemble the gas control; it contains non replaceable components. Attempted disassembly or repair can 
damage the control.

 

 
 
 
Fire or explosion hazard. Can cause property damage, severe injury or death. 

Exactly follow the warnings and the lighting instructions. 
 

 

 

 

 

f i r e - p a r t s . c o m

Summary of Contents for AF-4000 Series

Page 1: ...ith High Low Variable DC Motor Drive Remote 4 With High Low Step Motor Model AF 4000MOT Type of Valve 0 Vented Control Valve 1 Ventfree Control Valve FEATURES Multi positional All Plans Versatile Moun...

Page 2: ...s Side Back of valve Ambient Temperature Range 0 0 F to 175 0 F 18 0 C to 79 0 C Voltage 6 Volt DC Powered Approvals CSA International Valve Report Number 224930 1546330 Module Report Number 224930 19...

Page 3: ...REV 4 6 2010 Page 3 of 11 DIMENSIONS fire parts com...

Page 4: ...hnician Force or any attempt to repair the gas control valve can result in fire or explosion Location Locate the AF 4000 gas control where it cannot be affected by steam cleaning high humidity drippin...

Page 5: ...re 4 1 Unscrew and remove the cover cap Note the position of the marker on the shaft of the Simple Rotary knob This mark will point to NAT or LP that indicates the type of gas the valve is set on 2 To...

Page 6: ...onic control valve is eqiuped with a HI LO solenoid HI LO DC motor drive or HI LO Step Motor locate the wiring connections on the HI LO device Note Figure 8 Figure 7 Figure 8 Wiring The AF 4000 MOD Mo...

Page 7: ...6 volt transformer to the 2 1 4 male terminals marked POWER on the module Note location on Figure 11 Optional If an AF 4000 BP battery pack is used follow the Wiring The AF 4000 BP Battery Pack secti...

Page 8: ...DC adaptor This adaptor is connected to the AF 4000 MOD by connecting the 2 1 4 female terminals from the adaptor to the 2 1 4 male terminals located on the AF 4000 MOD marked power Using the 6 0 volt...

Page 9: ...dden gas leaks can cause flashbacks in the appliance 2 Check for gas leaks with rich soap and water solution any time work is done on a gas system Gas Leak Test 1 Paint the pipe connectors upstream of...

Page 10: ...assembly and cleaning can cause unreliable operation Regular preventive maintenance is important in applications that place a heavy load on the system such as those used in commerical cooking agricul...

Page 11: ...F 4000 MOD module 3 Check the power sorce 1 the 6 volt power adaptor or the AF 4000 BP battery pack connections and condition of batteries 4 Optional check the position of the CONTINUOUS PILOT switch...

Reviews: