g. Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly causing
steam coil damage.
ALL
horizontal runs of steam supply piping
should be
pitched 1/4-inch (6.35 mm)
for every 1 foot (0.30 meters) back towards the steam supply header causing the condensate in the line
to drain to the header. Install a bypass trap in any low point to eliminate wet steam.
IMPORTANT
: Flexible hose/coupling
must be
used. Coil failure due to hard plumbing connections
will
VOID THE WARRANTY.