14
E. EXHAUST REQUIREMENTS
1. General Exhaust Ductwork Information
Exhaust ductwork
should be
designed and installed by a qualified professional. Improperly sized ductwork
will create excessive back pressure which results in slow drying, increased use of energy, overheating of the
dryer, and shutdown of the burner by the airflow (sail) switches, burner hi-limits, or basket (tumbler) hi-heat
thermostats.
CAUTION
: DRYER
MUST BE
EXHAUSTED TO THE OUTDOORS.
CAUTION
:
IMPROPERLY
SIZED
or
INSTALLED
EXHAUST
DUCTWORK
CAN
CREATE
A
POTENTIAL
FIRE
HAZARD.
The ductwork
should be
laid out in such a way that the ductwork travels as directly as possible to the
outdoors with as few turns as possible. Single or independent dryer venting is recommended.
Horizontal Venting:
When single dryer venting is used, the length of ductwork from the dryer to the outside exhaust outlet,
must
not
exceed
15 feet (4.6 meters). The minimum diameter of this ductwork
must be
at least 8-inches (20.32
cm). In the case of multiple (common) dryer venting, the distance from the last dryer to the outside exhaust
outlet
must not
exceed
15 feet (4.6 meters). The shape of the ductwork is not critical so long as the
minimum cross-sectional area is provided. It is suggested that the use of 90° turns be avoided; use 30° and/
or 45° angles instead. The radius of the elbows
should preferably be
1-1/2 times the diameter of the duct.
Including basket (tumbler)/dryer elbow connections or elbows used for outside protection from the weather,
no more than two (2) elbows
should be
used in the exhaust duct run. If more than two (2) elbows are used,
the cross-sectional area of the ductwork
must be
increased.
ALL
ductwork
should be
smooth inside with
no projections from sheet metal screws or other obstructions, which will collect lint. When adding ducts, the
duct to be added should overlap the duct to which it is to be connected.
ALL
ductwork joints
must be
taped
to prevent moisture and lint from escaping into the building. Inspection doors
should be
installed at strategic
points in the exhaust ductwork for periodic inspection and cleaning of lint from the ductwork.
Vertical Venting:
When single dryer venting is used, the length of the ductwork from the dryer to the outside exhaust outlet
must not exceed
15 feet (4.6 meters). The minimum diameter of this ductwork
must be
at least 8-inches
(20.32 cm). In the case of multiple (common) dryer venting, the distance from the last dryer to the outside
exhaust outlet
must not exceed
15 feet (4.6 meters). The shape of the ductwork is not critical so long as
the minimum cross-sectional area is provided. It is suggested that the use of 90º turns be avoided; use 30º
and/or 45º angle instead. The radius of the elbows
should preferably be
1-1/2 times the diameter of the
duct.
ALL
ductwork
should be
smooth inside with no projections from sheet metal screws or other
obstructions, which will collect lint. When adding ducts, the duct to be added should overlap the duct to
which it is to be connected.
ALL
ductwork joints
must be
taped to prevent moisture and lint from escaping
into the building. Inspection doors
should be
installed at strategic points in the exhaust ductwork for
periodic inspection and cleaning of lint from the ductwork.
IMPORTANT
: Exhaust back pressure measured by a manometer in the exhaust duct
must not
exceed
0.3 inches (0.74 mb) of water column (W.C.).
IMPORTANT
: Minimum ductwork diameter for horizontal venting is 8-inches (20.32 cm) and for
vertical venting the minimum is 8-inches (20.32 cm).
Summary of Contents for Gas/Electric/Steam ML-55HS
Page 21: ...17 ...
Page 56: ...ADC 113000 9 11 23 05 0 ...