background image

Page   6 

000744MAN-02 

25 MAY 2009 

UNIT DESCRIPTION 

Your American Dream Geothermal unit is a high efficiency 

two stage triple function heat pump with R410a refrigerant. It 
extracts and rejects heat from the earth via direct contact with 
copper loops, eliminating the need for a secondary heat ex-
changer and associated components. The FCTF unit can pro-
vide air heating, air cooling, and hydronic heating.    

 
Freon Copper units require less “loop” per ton and are 

more efficient than conventional ground loop systems.  The re-
duced thermal resistance between the earth and the refrigerant 
circuit provides better heat transfer, resulting in a higher suction 
pressure and increased output.

 

 

An electrically commutated (ECM) fan with several speed 

options is standard.  The motor has a soft start function for im-
proved efficiency and reduced wear. 

 

The unit has several key features that are described in the 

specifications document for the particular heat pump. Please 
request a copy if desired or visit 

www.AmericanDreamGeothermal.com 

UNPACKING THE UNIT 

When the heat pump reaches its destination it should be 

unpacked to determine if any damage has occurred during 
shipment. Any visible damage should be noted on the carrier's 
freight bill and a suitable claim filed at once. 

 
The heat pump is well constructed and every effort has 

been made to ensure that it will arrive intact, however it is in the 
customer's best interest to examine the unit thoroughly when it 
arrives. 

OPTIMUM PLACEMENT 

For air units, to achieve the greatest efficiency, the heat 

pump should be centrally located in the home with respect to the 
conditioned space. This design provides the utmost in economy 
and comfort and usually can be accomplished in harmony with 
the design of the home. A heating system cannot be expected to 
produce an even warmth throughout the household when it is 
located at one end of the structure and the warm air is 
transmitted with uninsulated metal ductwork. 

 

If possible the access panels should remain clear of 

obstruction for a distance of  

two feet 

to facilitate servicing and 

general maintenance.  

 

 Raising the heat pump off the floor a few inches is generally 

a good practice since this will prevent rusting of the bottom 
panel of the unit.  We recommend that the heat pump be placed 
on a piece of 2'' thick styrofoam.  The styrofoam will smooth out 
any irregularities in the cement floor and deaden any 
compressor noise emitted from the bottom of the cabinet. 

 
AMERICAN DREAM Ultra Performance® heat pumps have 

an air-filter rack which can be installed with the removable end 
(where the filter is inserted) on either side to facilitate changing 
the filter.  

ELECTRICAL CONNECTIONS 

The heat pump has a concentric 1.093” / 0.875” knockout 

for power supply connection to the electrical box, as well as one 

for connection to the circulator pump module for ground loop 
applications.  There are  two 1/2” openings with plastic grom-
mets (grommet hole is 3/8”) in the upper section of the electrical 
box, one for the thermostat connections, and one for the op-
tional plenum heater connections.   

 
A schematic diagram and electrical box layout diagram 

(ELB) can be found inside the electrical box cover of the unit as 
well as in the 

Model Specific 

section of this manual.  The Electri-

cal Tables in the 

Model Specific 

section

 

and the ELB diagram 

contain information about the size of wire for the connections, as 
well as the recommended breaker size.  

A properly qualified 

electrician should be retained to make the connections to 
the heat pump and associated controls.  The connections to 
the heat pump MUST CONFORM TO LOCAL CODES.  

THERMOSTAT REQUIREMENTS 

The FCTF-Series unit includes a three-stage heating and 

two stage cooling thermostat with relay outputs for proper air 
mode operation.  

Triac output thermostats are incompatible 

with the control board in the heat pump.  

The stages are  S1 

= heat pump stage 1 , S2 = heat pump stage 2S3 = electric aux-
iliary (heating only).  One can be purchased with the unit, or 
other thermostats with the same number of stages can be used.  

The thermostat signals connect to the geothermal unit Control 
box as per 

TABLE 1

.   

AQUASTAT REQUIREMENTS

 

For water mode operation, a two stage aquastat is re-

quired to provide the appropriate control signals.  The connec-
tions to the FCTF Control Box are shown in 

TABLE 2

.  

The aquastat can be placed anywhere within the range of 

the probe cable.  The probe should be inserted into a dry well in 
or near the top of the tank for optimal operation 

(refer to  draw-

ing 000533PDG)

.  If a dry well is not available, it may be possi-

ble to fix the probe to the tank inside the insulation.   

 

Installation Information 

TABLE 1 - 

Thermostat to FCTF Control Box Signals 

 

Signal

 

Description

 

24VAC Common (Ground) 

Fan low speed (for air circulation) 

Y

1

  

Heat Pump Stage 1 (Compressor stage 1) 

R

H

 

24VAC Hot 

Fault (24VAC when fault condition) 

W

2

 

Heat Pump Stage 3 (auxiliary heat) / Emer-
gency Heat 

O/B/W

1

 

Cooling Mode (reversing valve) 

Y

2

  

Heat Pump Stage 2 (Compressor stage 2) 

TABLE 2 - 

Aquastat to FCTF Control Box Signals 

 

Signal*

 

Description

 

CA 

24VAC Common (Ground) 

RA 

24VAC Hot 

Y1A 

Heat Pump Stage 1 (Compressor stage 1) 

Y2A 

Heat Pump Stage 2 (Compressor stage 2) 

* Refer to 000139CDG (included with the FCTF Control Box)  
for a complete description of  the connections to the aquastat.  

Summary of Contents for Copper Series

Page 1: ...Vegas Nevada 89169 AMERICAN DREAM Freon Copper Series Triple Function Installation and Service Manual Email info AmericanDreamGeothermal com Web www AmericanDreamGeothermal com Document Number 000744M...

Page 2: ...ced A fire extinguisher and proper ventilation should be present whenever brazing is performed CAUTION Venting refrigerant to atmosphere is illegal A proper refrigerant recovery system must be employe...

Page 3: ...INDOOR COIL FAN CASE REVISIONS 3 Ton HACW P 1 T BLANK or H C or Z SDETV 02 2 T 02 6 S 02 7 T 02 4 Ton HACW P 1 T BLANK or H C or Z SDETV 02 2 T 02 6 S 02 7 T 02 5 Ton P BLANK or H C or Z SDETV HACW 1...

Page 4: ...l Page 15 Hydronic System Connections Page 15 Duct Sizing Guide Page 17 Freon Copper LOOP CONNECTION AND CHARGING PAGE 21 Line Set Interconnect Tubing Page 21 Pipe Insulation Page 21 Silver Soldering...

Page 5: ...Ratings Hydronic Heating 60Hz Page 48 Table 21 Heat Pump Electrical Information 230 1 60 Page 52 Table 22 Heat Pump Electrical Information 208 3 60 Page 52 Table 23 Heat Pump Electrical Information 2...

Page 6: ...talled with the removable end where the filter is inserted on either side to facilitate changing the filter ELECTRICAL CONNECTIONS The heat pump has a concentric 1 093 0 875 knockout for power supply...

Page 7: ...er of the plenum heater for more information NOTE Some models are not available in two stage at the pre sent time see Electrical Tables The Y2 signal is not used for these units INDOOR LOOP CIRCULATOR...

Page 8: ...ures equalize in the unit The unit may restart after the timer period has expired Should the unit trip on the safety con trol again the compressor will once again shut down and the counter will be inc...

Page 9: ...25 MAY 2009 Page 9 000744MAN 02...

Page 10: ...Page 10 000744MAN 02 25 MAY 2009...

Page 11: ...7 As the transition from summer to fall begins and the cool ing load is greatly reduced the loops begin to cool down on their own Eventually a point is reached at which the loops are cooled down enou...

Page 12: ...he COP must be unlocked by command U before using command C to change system settings The list of settings for command C is shown in TABLE 11 It is recommended that the settings be left at the default...

Page 13: ...25 MAY 2009 Page 13 000744MAN 02...

Page 14: ...EAT PUMP SIZING TABLE 12 depicts averages WILL VARY WITH ENVELOP EFFICIENCY as a rough guideline to the size of home each heat pump size can handle THE TABLE ABOVE IS FOR INFORMATION ONLY IT SHOULD NO...

Page 15: ...pass through it to prevent any hot spots in the heater elements TABLE 14 shows the recommended size plenum heater as well as the wire size and breaker size needed to provide power to the plenum heate...

Page 16: ...Page 16 000744MAN 02 25 MAY 2009...

Page 17: ...6 15 x 15 20 684 201 1750 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 20 826 254 2000 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 22 944 254 2250 20 10 x 38 12 x 30 14 x 26 16 x 22...

Page 18: ...Page 18 000744MAN 02 25 MAY 2009...

Page 19: ...25 MAY 2009 Page 19 000744MAN 02...

Page 20: ...Page 20 000744MAN 02 25 MAY 2009...

Page 21: ...ine set tubing The line sets can be connected to the ports on the heat pump using couplings or alternately the tubing can be swaged The joints should be silver soldered with 5 silfos AMERICAN DREAM Ge...

Page 22: ...Page 22 000744MAN 02 25 MAY 2009...

Page 23: ...ation Record the type of antifreeze and the mixture value on the startup sheet circle Vol or Weight 4 Record the static loop pressure on the startup sheet Line Sets Inside structure 1 Verify that all...

Page 24: ...l box and compressor 4 Adjust the thermostat setpoint to the desired room temperature and let the unit run through a cycle Record the setpoint and the discharge pressure when the unit shuts off 5 For...

Page 25: ...connections are correct and securely fastened Circuit breaker or fuse size and wire gauge for Heat Pump A Ga Circuit breaker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connect...

Page 26: ...oop Out Hot Out temperature 7 Indoor Delta T should be between 8 12 F 4 6 C 8 Compressor L1 C current black wire place meter between electrical box and compressor 4 Adjust the aquastat setpoint to the...

Page 27: ...aker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connections are correct and securely fastened Unit Charge Refrigerant charge be fore power is turned on Lbs kg STARTUP DATA Prep...

Page 28: ...ction at the top of the adjustment record sheet Circle F or C at the top right 2 Record all data for the initial readings elapsed time 0 Adjust the TXV for the loop that is the furthest out Record the...

Page 29: ...lation Site City Province Country Serial Installer Company Date Model F C TIME COMMON LOOP 1 LOOP 2 LOOP 3 LOOP 4 LOOP 5 LOOP 6 ADJUSTMENT Actual EL S ET D P1 V1 S1 P2 V2 S2 P3 V3 S3 P4 V4 S4 P5 V5 S5...

Page 30: ...lter 6 months Inspect for dirt Replace if necessary Contactor 1 year Inspect for pitted or burned points Replace if necessary Condensate Drain 1 year Inspect for clogs Remove and clean if necessary Ci...

Page 31: ...roceed to POWER SUPPLY TROUBLESHOOTING otherwise proceed to STEP 2 STEP 2 Remove the door and electrical box cover and check to see if the HI or LOW LED s are flashing or on Record The results Turn th...

Page 32: ...AC signal present across C and Stage 1 of the thermo stat Correct the setup Faulty thermostat to heat pump wiring 24VAC signal present across Stage 1 and C of the thermostat but not pre sent across Y1...

Page 33: ...infinite resistance between any two terminals Note Be sure compressor overload has had a chance to reset If compressor is hot this may take several hours Replace the compressor Burned out motor shorte...

Page 34: ...Pressure Heating TXV s adjusted too far closed Verify superheat It should be be tween 8 14 F 3 8 C Superheat will be high if TXV is closed too far Adjust TXV to obtain 8 14 F 3 8 C superheat Low Sucti...

Page 35: ...e or more heating TXV s stuck too far open Adjusting the TXV does not affect the superheat of the loop or the suc tion pressure Low super heat low discharge pressure Adjust the TXV all the way in and...

Page 36: ...g S and S does not cause the Loop Switch LED to come on or does not cause a loop change Replace the control board High Pressure control and man ual high pressure control trips very fast Faulty reclaim...

Page 37: ...ir flow are good but suction is low Check static refrigeration pressure of unit for very low value Locate the leak and repair it Spray nine a sniffer and dye are common methods of locating a leak Leak...

Page 38: ...en White pin 3 and the following at the fan con trol signal harness insert probes in connector where wire is inserted do not unplug the connector Circulation Grey pin 15 Stage 1 Yellow pin 6 Stage 2 Y...

Page 39: ...at to DXTF Control Box wiring 24VAC not present across Stage 1 C and COM of the aquastat Correct or replace wiring Faulty aquastat to DXTF Control Box wiring 24VAC signal present across Stage 1 NO and...

Page 40: ...he discharge pressure reduces Surging Discharge Pressure Heating TXV s adjusted too far closed Verify superheat It should be be tween 8 14 F 3 8 C Superheat will be high if TXV s are closed too far Ad...

Page 41: ...F 3 8 C superheat One or more heating TXV s stuck too far open Adjusting the TXV does not affect the superheat of the loop or the suc tion pressure Low super heat low discharge pressure Attempt to adj...

Page 42: ...anual Faulty thermostat Thermostat doesn t indicate a call for auxiliary or emergency when it should Replace thermostat Faulty thermostat Thermostat indicates auxiliary or emergency but no 24VAC signa...

Page 43: ...spect the pump to see if shaft is turning Use an amprobe to measure current draw Replace if faulty Insufficient hot water Heat Pump Prob lem Blockage or restriction in the water line or hot water heat...

Page 44: ...gerant circuit pressure and connect the vacuum pump to the charging manifold Start the vacuum pump and open the charging manifold valves Vacuum until the vacuum gauge remains at less than 500 microns...

Page 45: ...25 MAY 2009 Page 45 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS...

Page 46: ...Page 46 000744MAN 02 25 MAY 2009 REFRIGERATION CIRCUIT DIAGRAMS continued...

Page 47: ...25 MAY 2009 Page 47 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS continued...

Page 48: ...0 802 3 375 43 500 12 7 3 78 65 5 Stage 1 1700 802 2 930 41 900 12 3 4 19 Stage 2 2100 991 4 180 53 300 15 6 3 74 Table 19 Standard Capacity Ratings Cooling 60Hz EAT 80 F 26 7 C STAGE 1 LIQUID LINE 68...

Page 49: ...g Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pres Cond Temp...

Page 50: ...0 Hz Cooling Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pre...

Page 51: ...Hz Cooling Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pres...

Page 52: ...58 3 5 16 9 20 0 30 10 4 55 15 0 88 4 0 20 0 23 8 40 8 4 65 19 6 123 5 5 26 1 31 0 50 8 4 Models are single stage Table 23 Heat Pump Electrical Information 220 1 50 Model Compressor Fan FLA MCA Max F...

Page 53: ...25 MAY 2009 Page 53 000744MAN 02 ELECTRICAL DIAGRAMS 230 1 60...

Page 54: ...Page 54 000744MAN 02 25 MAY 2009 ELECTRICAL DIAGRAMS 230 1 60 continued...

Page 55: ...25 MAY 2009 Page 55 000744MAN 02 CASE DETAILS Front View Back View Left Side View Right Side View...

Page 56: ...Page 56 000744MAN 02 25 MAY 2009 Top View Size 2 3 4 Ton CASE DETAILS continued Top View Size 5 Ton...

Page 57: ...H STAGE 2 STAGE 1 FAN ONLY Recirculation Model Nom Size Full Reduced Full Reduced Full Reduced Tons CFM L s CFM L s CFM L s CFM L s CFM L s CFM L s 25 2 848 400 721 340 721 340 613 289 475 224 404 191...

Page 58: ...Page 58 000744MAN 02 25 MAY 2009...

Page 59: ...25 MAY 2009 Page 59 000744MAN 02...

Page 60: ...only to the completely finished and insulated structure Startup of the unit shall not be scheduled prior to completion of construction and final duct installation for validation of this warranty 4 It...

Reviews: