25 MAY 2009
Page 41
000744MAN-02
HYDRONIC OPERATION TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
Low Suction
Pressure
(continued)
Faulty compressor, not
pumping.
Pressures change only slightly from
static values when compressor is
started.
Replace compressor.
Loop piping interchanged
(ie Loop 1 connected be-
tween Vapour 1 and
Liquid 2)
Affected TXV’s do not seem to oper-
ate properly. Switch to cooling
mode and verify all liquid line tem-
peratures for each individual loop
switch. The liquid line for the loop in
use should be warmer than the oth-
ers, If loops are interchanged, the
wrong liquid line will be warmer.
Pump the unit down and swap
the interchanged lines.
Loop field too small
Charge is good, superheats are
good, vapor line temperatures are
low.
Increase loop size.
High Suction
Pressure
(may appear to
not be pumping)
Leaking reversing valve.
Reversing valve is the same tem-
perature on both ends of body,
common suction line is warm, com-
pressor is running hot.
Replace reversing valve.
Heating TXV’s adjusted
too far open.
Verify superheat. It should be be-
tween 8-14°F (3-8°C). Superheat
will be low if TXV’s are open too far.
Adjust TXV to obtain 8-14°F
(3-8°C) superheat.
One or more heating
TXV’s stuck (too far
open).
Adjusting the TXV does not affect
the superheat of the loop or the suc-
tion pressure. Low super heat, low
discharge pressure.
Attempt to adjust the TXV all the
way out and all the way in a few
times to loosen it. Replace TXV if
this does not work.
Faulty cooling check valve
(leaking)
Also low discharge pressure. Switch
to cooling mode. Unit operates cor-
rectly when loop is in use. Loop
lines get cold when loop not in use
instead of warming to ambient, com-
pressor frosts up.
Identify the check valve. Try
switching modes a few times.
Replace if problem continues.
Compressor
frosting up
See Low Suction
Pressure in this section.
Heating TXV
frosting up heav-
ily
TXV stuck almost closed
or partially blocked by for-
eign object.
Adjusting the TXV does not affect
the superheat or the suction pres-
sure.
Attempt to adjust the TXV all the
way out and all the way in a few
times to loosen it. Replace TXV
if this does not work.
Random high
pressure trip
(does not occur
while on site)
Intermittent Indoor circula-
tor.
Verify wiring is good
Correct the wiring or replace the
circulator.
Random manual
high pressure
trip (does not
occur while on
site)
Faulty compressor contac-
tor.
Points pitted or burned. Contactor
sometimes sticks causing the com-
pressor to run without the fan, trip-
ping the high pressure control.
Replace contactor.
Summary of Contents for Copper Series
Page 9: ...25 MAY 2009 Page 9 000744MAN 02...
Page 10: ...Page 10 000744MAN 02 25 MAY 2009...
Page 13: ...25 MAY 2009 Page 13 000744MAN 02...
Page 16: ...Page 16 000744MAN 02 25 MAY 2009...
Page 18: ...Page 18 000744MAN 02 25 MAY 2009...
Page 19: ...25 MAY 2009 Page 19 000744MAN 02...
Page 20: ...Page 20 000744MAN 02 25 MAY 2009...
Page 22: ...Page 22 000744MAN 02 25 MAY 2009...
Page 45: ...25 MAY 2009 Page 45 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS...
Page 46: ...Page 46 000744MAN 02 25 MAY 2009 REFRIGERATION CIRCUIT DIAGRAMS continued...
Page 47: ...25 MAY 2009 Page 47 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS continued...
Page 53: ...25 MAY 2009 Page 53 000744MAN 02 ELECTRICAL DIAGRAMS 230 1 60...
Page 54: ...Page 54 000744MAN 02 25 MAY 2009 ELECTRICAL DIAGRAMS 230 1 60 continued...
Page 58: ...Page 58 000744MAN 02 25 MAY 2009...