Page 34
000744MAN-02
25 MAY 2009
AIR OPERATION TROUBLESHOOTING - HEATING MODE
Fault
Possible Cause
Verification
Recommended Action
High Discharge
Pressure
Air Flow.
See Fan Troubleshooting section.
Correct the problem.
Heating TXV’s adjusted
too far closed.
Verify superheat. It should be be-
tween 8-14°F (3-8°C). Superheat will
be high if TXV’s are closed too far.
Adjust TXV to obtain 8-14°F
(3-8°C) superheat.
One or more heating
TXV’s stuck (too far
closed).
Adjusting the TXV does not affect the
superheat or the suction pressure.
Adjust the TXV all the way in and out
a few times to loosen it. Replace
TXV if this does not work.
Faulty Normally Open so-
lenoid valve (stuck
closed).
A click can be heard when the coil is
energized but the valve is cold in-
stead of warm.
Replace NO valve.
Filter-drier plugged.
Feel each end of the filter- drier, it
should be the same temperature. If
there is a temperature difference then
it is plugged. Also causes low suc-
tion pressure.
Replace filter-drier.
Unit is overcharged.
High sub-cooling, low delta T across
air coil.
Remove 1/2lb of refrigerant at a
time and verify that the discharge
pressure reduces.
Surging
Discharge
Pressure
Heating TXV’s adjusted
too far closed.
Verify superheat. It should be be-
tween 8-14°F (3-8°C). Superheat will
be high if TXV is closed too far.
Adjust TXV to obtain 8-14°F
(3-8°C) superheat.
Low Suction
Pressure
Heating TXV’s adjusted
too far closed.
Adjusting the TXV does not affect the
superheat or the suction pressure.
TXV may be frosting up.
Adjust TXV to obtain 8-14°F
(3-8°C) superheat.
One or more heating
TXV’s stuck (too far
closed).
Adjusting the TXV does not affect the
superheat or the suction pressure.
Adjust the TXV all the way in and out
a few times to loosen it. Replace
TXV if this does not work.
Faulty Normally Open so-
lenoid valve (stuck
closed).
** May actually draw a
vacuum.**
A click can be heard when the coil is
energized but the valve is cold in-
stead of warm.
Replace NO valve.
Filter-drier plugged.
Feel each end of the filter- drier, it
should be the same temperature. If
there is a temperature difference then
it is plugged. Also causes low suc-
tion pressure.
Replace filter-drier.
Low refrigerant charge.
Check static refrigeration pressure of
the unit for a very low value. Low
discharge pressure when running.
Locate the leak and repair it.
Spray nine, a sniffer and dye are
common methods of locating a
leak.
Faulty compressor, not
pumping.
Pressures change only slightly from
static values when compressor is
started.
Replace compressor.
Summary of Contents for Copper Series
Page 9: ...25 MAY 2009 Page 9 000744MAN 02...
Page 10: ...Page 10 000744MAN 02 25 MAY 2009...
Page 13: ...25 MAY 2009 Page 13 000744MAN 02...
Page 16: ...Page 16 000744MAN 02 25 MAY 2009...
Page 18: ...Page 18 000744MAN 02 25 MAY 2009...
Page 19: ...25 MAY 2009 Page 19 000744MAN 02...
Page 20: ...Page 20 000744MAN 02 25 MAY 2009...
Page 22: ...Page 22 000744MAN 02 25 MAY 2009...
Page 45: ...25 MAY 2009 Page 45 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS...
Page 46: ...Page 46 000744MAN 02 25 MAY 2009 REFRIGERATION CIRCUIT DIAGRAMS continued...
Page 47: ...25 MAY 2009 Page 47 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS continued...
Page 53: ...25 MAY 2009 Page 53 000744MAN 02 ELECTRICAL DIAGRAMS 230 1 60...
Page 54: ...Page 54 000744MAN 02 25 MAY 2009 ELECTRICAL DIAGRAMS 230 1 60 continued...
Page 58: ...Page 58 000744MAN 02 25 MAY 2009...