background image

25 MAY 2009 

Page   15 

000744MAN-02 

 

The total number of supply grills available is based on the 

heat pump nominal airflow.  

TABLE  13 

shows the number of 

grills available per heat pump size. 

Return grills should be mounted on the floor.  At minimum 

they should be the same size as the supply grill, 

it is highly 

recommended that they be 25% to 50% larger than the total 
supply.

 They should be placed opposite the supply grills when 

possible to ensure distribution across the room.  For rooms re-
quiring more than one supply grill,  it may be possible to use one 
larger return grill if it can be centrally positioned opposite of the 
supply grills, however it is preferred to have one return for each 
supply to maximize heat distribution across the room. 

THERMOSTAT LOCATION 

Most homes are a single zone with one thermostat.  The ther-

mostat should be centrally located within the home, typically on 
the main floor.  It should be placed away from any supply grills, 
and should not be positioned directly above a return grill.  Most 
installations have the thermostat located in a hallway, or in the 
inner wall of  the living room.  It should be noted that most  
homes do not have any supply ducts in the hallway.  This can 
lead to a temperature lag at the thermostat if there is very little 
air movement in the hallway, causing the home to be warmer 
than indicated by the thermostat. 

PLENUM HEATER (OPTIONAL) 

For installations that do not already have a backup heat 

source such as electric baseboard, wood stove, propane etc,  it 
is recommended that a plenum heater be installed.  This pro-
vides two functions.   

 
The first function of the plenum heater is to act as an auxiliary  

heat source.  As such it will provide additional heat on extremely 
cold days if the heat pump is unable to bring the home tempera-
ture up quickly enough, eliminating any discomfort to the home-
owner. 

 
The second function of the plenum heater is to provide emer-

gency heat should a problem occur that causes the heat pump 
to be locked out.  This can be engaged by setting the thermostat 
to emergency heat, allowing the plenum heater to function while 
preventing the heat pump from operating.  Should the heat 
pump fail while the home is vacant, the auxiliary function of the 
thermostat will maintain the temperature setting of the thermo-
stat. 

 
The plenum heater is powered separately from the heat 

pump.  Only two control wires are needed to connect the  ple-
num heater to the heat pump.  Refer to the label on the plenum 
heater or the electrical box diagram on the inside of the electri-
cal box cover of the unit for details on the connections.  

 
The plenum heater should be mounted in the supply duct in a 

manner that allows all of the airflow to pass through it to prevent 
any hot spots in the heater elements.  

 

TABLE  14 

shows the recommended size plenum heater, as 

well as the wire size and breaker size needed to provide power  
to the plenum heater. 

CONDENSATE DRAIN 

The unit comes equipped with a 3/4” PVC socket fitting 

(female) labeled “Condensate Drain”.  This drain allows the con-
densate which forms during the air-conditioning cycle to be re-
moved from the unit.  The drain should be connected as per 
local codes.  During high humidity weather, there could be as 
much as 25 gallons of water formed per day.  

 
Care should be taken in the spring to ensure that this pipe is 

not plugged with dust that has collected during the winter caus-
ing the condensate to overflow into the bottom of the heat pump 
and onto the floor.  

The condensate drain is internally 

trapped;

  

however, proper venting is required external to 

the heat pump. Refer to local codes to ensure the installa-
tion is done properly.  

Drawing 000606CDG 

shows a typical 

installation. 

HYDRONIC SYSTEMS - GENERAL 

The most common applications for the hydronic heating are: 

(see 

drawing 000530PDG 

for typical zone types)  

 

radiant in-floor heating 

 

On-demand domestic hot water 

 

Swimming  pool or spa 

 
The radiant in-floor areas of the home may be sectioned into 

several areas called zones.  Each zone has its own thermostat, 
allowing simple separate temperature control of the individual 
areas in the home. A typical system consists of the heat pump, 
the buffer tank and the zones.  The sole purpose of the heat 
pump is to maintain the buffer tank set point.  Its operation is 
independent of the zone operation. 

HYDRONIC SYSTEM CONNECTIONS 

The unit has 1” copper pipe connections for the hydronic sys-

tem, labeled INDOOR IN and INDOOR OUT.  Flow through the 
unit is provided by an external circulator powered by the control 
box. 

 

NOTE:  Depending on how the system is connected, an ex-
ternal water valve may be required in the INDOOR OUT line 
to prevent draw through the water coil while in air heating 
mode.  The 24VAC coil of the water valve can be connected 
across Y1A and CA in the heat pump.  

 
Drawing 000533PDG 

shows a typical piping configuration for 

a single unit with a buffer tank.  This is a guideline for a simple 
installation.  There are many other configurations, such as, mul-
tiple units connected to one buffer tank, on-demand domestic 
only, etc…  It is recommended that the hydronic system be de-
signed by a qualified system designer to ensure proper function-
ality.   

 

Drawing 000627PDG 

shows two typical on-demand domestic 

hot water systems, dedicated and zoned.  For a dedicated 
setup, there are no zones and the home is heated solely by air.  
The unit can very easily be switched between air or hydronic 
priority during installation. 

 

TABLE 14 - Plenum Heater Sizing 

Heat 

Pump 

Plenum Heater (230-1-60)  

Size  

(Tons) 

Size  

(kW) 

Current 

(A) 

Breaker 

(A) 

Wire 

Size 

28 

40 

#6 

10 

42 

60 

#6 

15 

62 

100 

#3 

20 

84 

125 

#3 

Summary of Contents for Copper Series

Page 1: ...Vegas Nevada 89169 AMERICAN DREAM Freon Copper Series Triple Function Installation and Service Manual Email info AmericanDreamGeothermal com Web www AmericanDreamGeothermal com Document Number 000744M...

Page 2: ...ced A fire extinguisher and proper ventilation should be present whenever brazing is performed CAUTION Venting refrigerant to atmosphere is illegal A proper refrigerant recovery system must be employe...

Page 3: ...INDOOR COIL FAN CASE REVISIONS 3 Ton HACW P 1 T BLANK or H C or Z SDETV 02 2 T 02 6 S 02 7 T 02 4 Ton HACW P 1 T BLANK or H C or Z SDETV 02 2 T 02 6 S 02 7 T 02 5 Ton P BLANK or H C or Z SDETV HACW 1...

Page 4: ...l Page 15 Hydronic System Connections Page 15 Duct Sizing Guide Page 17 Freon Copper LOOP CONNECTION AND CHARGING PAGE 21 Line Set Interconnect Tubing Page 21 Pipe Insulation Page 21 Silver Soldering...

Page 5: ...Ratings Hydronic Heating 60Hz Page 48 Table 21 Heat Pump Electrical Information 230 1 60 Page 52 Table 22 Heat Pump Electrical Information 208 3 60 Page 52 Table 23 Heat Pump Electrical Information 2...

Page 6: ...talled with the removable end where the filter is inserted on either side to facilitate changing the filter ELECTRICAL CONNECTIONS The heat pump has a concentric 1 093 0 875 knockout for power supply...

Page 7: ...er of the plenum heater for more information NOTE Some models are not available in two stage at the pre sent time see Electrical Tables The Y2 signal is not used for these units INDOOR LOOP CIRCULATOR...

Page 8: ...ures equalize in the unit The unit may restart after the timer period has expired Should the unit trip on the safety con trol again the compressor will once again shut down and the counter will be inc...

Page 9: ...25 MAY 2009 Page 9 000744MAN 02...

Page 10: ...Page 10 000744MAN 02 25 MAY 2009...

Page 11: ...7 As the transition from summer to fall begins and the cool ing load is greatly reduced the loops begin to cool down on their own Eventually a point is reached at which the loops are cooled down enou...

Page 12: ...he COP must be unlocked by command U before using command C to change system settings The list of settings for command C is shown in TABLE 11 It is recommended that the settings be left at the default...

Page 13: ...25 MAY 2009 Page 13 000744MAN 02...

Page 14: ...EAT PUMP SIZING TABLE 12 depicts averages WILL VARY WITH ENVELOP EFFICIENCY as a rough guideline to the size of home each heat pump size can handle THE TABLE ABOVE IS FOR INFORMATION ONLY IT SHOULD NO...

Page 15: ...pass through it to prevent any hot spots in the heater elements TABLE 14 shows the recommended size plenum heater as well as the wire size and breaker size needed to provide power to the plenum heate...

Page 16: ...Page 16 000744MAN 02 25 MAY 2009...

Page 17: ...6 15 x 15 20 684 201 1750 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 20 826 254 2000 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 22 944 254 2250 20 10 x 38 12 x 30 14 x 26 16 x 22...

Page 18: ...Page 18 000744MAN 02 25 MAY 2009...

Page 19: ...25 MAY 2009 Page 19 000744MAN 02...

Page 20: ...Page 20 000744MAN 02 25 MAY 2009...

Page 21: ...ine set tubing The line sets can be connected to the ports on the heat pump using couplings or alternately the tubing can be swaged The joints should be silver soldered with 5 silfos AMERICAN DREAM Ge...

Page 22: ...Page 22 000744MAN 02 25 MAY 2009...

Page 23: ...ation Record the type of antifreeze and the mixture value on the startup sheet circle Vol or Weight 4 Record the static loop pressure on the startup sheet Line Sets Inside structure 1 Verify that all...

Page 24: ...l box and compressor 4 Adjust the thermostat setpoint to the desired room temperature and let the unit run through a cycle Record the setpoint and the discharge pressure when the unit shuts off 5 For...

Page 25: ...connections are correct and securely fastened Circuit breaker or fuse size and wire gauge for Heat Pump A Ga Circuit breaker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connect...

Page 26: ...oop Out Hot Out temperature 7 Indoor Delta T should be between 8 12 F 4 6 C 8 Compressor L1 C current black wire place meter between electrical box and compressor 4 Adjust the aquastat setpoint to the...

Page 27: ...aker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connections are correct and securely fastened Unit Charge Refrigerant charge be fore power is turned on Lbs kg STARTUP DATA Prep...

Page 28: ...ction at the top of the adjustment record sheet Circle F or C at the top right 2 Record all data for the initial readings elapsed time 0 Adjust the TXV for the loop that is the furthest out Record the...

Page 29: ...lation Site City Province Country Serial Installer Company Date Model F C TIME COMMON LOOP 1 LOOP 2 LOOP 3 LOOP 4 LOOP 5 LOOP 6 ADJUSTMENT Actual EL S ET D P1 V1 S1 P2 V2 S2 P3 V3 S3 P4 V4 S4 P5 V5 S5...

Page 30: ...lter 6 months Inspect for dirt Replace if necessary Contactor 1 year Inspect for pitted or burned points Replace if necessary Condensate Drain 1 year Inspect for clogs Remove and clean if necessary Ci...

Page 31: ...roceed to POWER SUPPLY TROUBLESHOOTING otherwise proceed to STEP 2 STEP 2 Remove the door and electrical box cover and check to see if the HI or LOW LED s are flashing or on Record The results Turn th...

Page 32: ...AC signal present across C and Stage 1 of the thermo stat Correct the setup Faulty thermostat to heat pump wiring 24VAC signal present across Stage 1 and C of the thermostat but not pre sent across Y1...

Page 33: ...infinite resistance between any two terminals Note Be sure compressor overload has had a chance to reset If compressor is hot this may take several hours Replace the compressor Burned out motor shorte...

Page 34: ...Pressure Heating TXV s adjusted too far closed Verify superheat It should be be tween 8 14 F 3 8 C Superheat will be high if TXV is closed too far Adjust TXV to obtain 8 14 F 3 8 C superheat Low Sucti...

Page 35: ...e or more heating TXV s stuck too far open Adjusting the TXV does not affect the superheat of the loop or the suc tion pressure Low super heat low discharge pressure Adjust the TXV all the way in and...

Page 36: ...g S and S does not cause the Loop Switch LED to come on or does not cause a loop change Replace the control board High Pressure control and man ual high pressure control trips very fast Faulty reclaim...

Page 37: ...ir flow are good but suction is low Check static refrigeration pressure of unit for very low value Locate the leak and repair it Spray nine a sniffer and dye are common methods of locating a leak Leak...

Page 38: ...en White pin 3 and the following at the fan con trol signal harness insert probes in connector where wire is inserted do not unplug the connector Circulation Grey pin 15 Stage 1 Yellow pin 6 Stage 2 Y...

Page 39: ...at to DXTF Control Box wiring 24VAC not present across Stage 1 C and COM of the aquastat Correct or replace wiring Faulty aquastat to DXTF Control Box wiring 24VAC signal present across Stage 1 NO and...

Page 40: ...he discharge pressure reduces Surging Discharge Pressure Heating TXV s adjusted too far closed Verify superheat It should be be tween 8 14 F 3 8 C Superheat will be high if TXV s are closed too far Ad...

Page 41: ...F 3 8 C superheat One or more heating TXV s stuck too far open Adjusting the TXV does not affect the superheat of the loop or the suc tion pressure Low super heat low discharge pressure Attempt to adj...

Page 42: ...anual Faulty thermostat Thermostat doesn t indicate a call for auxiliary or emergency when it should Replace thermostat Faulty thermostat Thermostat indicates auxiliary or emergency but no 24VAC signa...

Page 43: ...spect the pump to see if shaft is turning Use an amprobe to measure current draw Replace if faulty Insufficient hot water Heat Pump Prob lem Blockage or restriction in the water line or hot water heat...

Page 44: ...gerant circuit pressure and connect the vacuum pump to the charging manifold Start the vacuum pump and open the charging manifold valves Vacuum until the vacuum gauge remains at less than 500 microns...

Page 45: ...25 MAY 2009 Page 45 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS...

Page 46: ...Page 46 000744MAN 02 25 MAY 2009 REFRIGERATION CIRCUIT DIAGRAMS continued...

Page 47: ...25 MAY 2009 Page 47 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS continued...

Page 48: ...0 802 3 375 43 500 12 7 3 78 65 5 Stage 1 1700 802 2 930 41 900 12 3 4 19 Stage 2 2100 991 4 180 53 300 15 6 3 74 Table 19 Standard Capacity Ratings Cooling 60Hz EAT 80 F 26 7 C STAGE 1 LIQUID LINE 68...

Page 49: ...g Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pres Cond Temp...

Page 50: ...0 Hz Cooling Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pre...

Page 51: ...Hz Cooling Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pres...

Page 52: ...58 3 5 16 9 20 0 30 10 4 55 15 0 88 4 0 20 0 23 8 40 8 4 65 19 6 123 5 5 26 1 31 0 50 8 4 Models are single stage Table 23 Heat Pump Electrical Information 220 1 50 Model Compressor Fan FLA MCA Max F...

Page 53: ...25 MAY 2009 Page 53 000744MAN 02 ELECTRICAL DIAGRAMS 230 1 60...

Page 54: ...Page 54 000744MAN 02 25 MAY 2009 ELECTRICAL DIAGRAMS 230 1 60 continued...

Page 55: ...25 MAY 2009 Page 55 000744MAN 02 CASE DETAILS Front View Back View Left Side View Right Side View...

Page 56: ...Page 56 000744MAN 02 25 MAY 2009 Top View Size 2 3 4 Ton CASE DETAILS continued Top View Size 5 Ton...

Page 57: ...H STAGE 2 STAGE 1 FAN ONLY Recirculation Model Nom Size Full Reduced Full Reduced Full Reduced Tons CFM L s CFM L s CFM L s CFM L s CFM L s CFM L s 25 2 848 400 721 340 721 340 613 289 475 224 404 191...

Page 58: ...Page 58 000744MAN 02 25 MAY 2009...

Page 59: ...25 MAY 2009 Page 59 000744MAN 02...

Page 60: ...only to the completely finished and insulated structure Startup of the unit shall not be scheduled prior to completion of construction and final duct installation for validation of this warranty 4 It...

Reviews: