PROPER INSTALLATION
CONFIGURATION SETTINGS
7 BUTTON TOUCH PAD WITH DISPLAY
The control can be configured to operate a wide range of
options. The options listed below with the * are the factory
default settings. If these are acceptable, then the unit does
not require any additional configuration and is fully oper-
able. To configure the unit, first select the configuration
feature code setting and then an option code to change
from the factory default setting.
To
enter configuration feature mode
:
1.
Press
and
hold
the up and down
arrow keys at the
same time and
press
the
OFF
key
twice within
a two (2) second time frame then release the
.
The display will indicate = = if the security code (con-
figuration code
uL
) has been previously set. The dis-
play alternates between
= =
and
00
. Use the up and
down
arrow keys to change
00
to the previously
selected security code.
NOTE:
The control will not proceed to the next step
until the correct code is entered. The security code
step will be skipped if no code has been set or if it has
been set back to
00
.
The display will indicate
- -
. Press the
key one
time. The display will then alternate between
C1
and
0
.
To select a different configuration
feature code
,
press the
HEAT
key until the desired configu-
ration comes up. To scroll to a previously viewed con-
figuration codes press the
COOL
key.
Once you have scrolled to the correct feature, then to
select the
option code
for your desired configuration,
press either the up or down key
to scroll through
the options of the selected feature code.
To
exit configuration mode
:
1.
Press
the
OFF
key. Configuration feature
mode will also exit
if no keys are pressed
for a pe-
riod of
two (2) minutes
.