24
TWO JUMPERS MOVED TO
“EXT POWR”
TERMINAL BLOCK
POWERED CONNECTION
NOTE:
For powered connection, the 2 jumpers must be
positioned as shown above, with jumpers on the center &
right pins.
MOUNTING SENSOR/DOOR MAGNET
INSTALLATION FOR DD01E AND DD01F KITS
DDO1E and DD01F must be mounted on the top door frame
as close to the door as possible in the horizontal position.
A DT01A must be installed in the PTAC unit for the DD01E
or DD01F to be operable.
Skip these steps if not installing.
1. Remove motion sensor from mounting plate by pulling
apart.
2. Mount the back plate on the door trim directly above
the door using the enclosed screws. (Position so the UP
arrow is pointing up.) Mount the DD01E as low as pos-
sible on the door frame to be as close to the moving
part of the door as possible without interfering with
the door opening or closing. Choose a location for mount-
ing the back plate that will provide good coverage of
the PIR for motion into the room. Make sure that the
DD01E will not interfere with the normal opening and
closing of the door.
DO NOT SNAP MOTION SENSOR IN PLACE UNTIL
AFTER BINDING PROCESS.
See Binding instructions.
DOOR
DOOR TRIM
(CENTER MAGNET WITH
01*)
DD
DD01*
DD01E and DD01F Mounting
3. Install two (2) AA batteries (included) into the back of
the thermostat. Terminals are marked “+” and “-” for
polarity.
Do NOT put batteries into the device until
AFTER the magnet location is selected to test.
WIRED
WIRED MAGNET AND POWERED DOOR SENSOR
OPTION
In cases where there is no top door frame, the sensor will
need to be mounted on the wall next to the door. In these
cases a wired magnet (a field supplied single pole single
throw wired magnet) can be recessed or surface mounted
and wired to the door sensor. The magnet will be a recessed
style magnet with wired switch. The wires for the sensor
(20 gauge field supplied) in the magnet will need to be run
during construction. Two wires will be run from the door
sensor location to the PTAC unit; the remaining two wires
will be run from the magnet location to the sensor location.
The door sensor has four (4) terminal locations for wired
power and/or wired magnets. The two (2) terminals closest
to the binding button are for wired magnet and the top two
(2) terminals are for wired power.
Run the magnet wires through the opening in the center of
the door sensor wall plate.
CONNECTING MAGNET
Using a pocket size straight blade screw driver push down
on the terminal button to open the socket, insert wire into
socket and release the terminal button. Insert one wire into
each of the two (2) terminals. See image below for wire
locations.
POWER CONNECTION
If using the wired powered option for the door sensor, us-
ing a pocket size straight blade screw driver, push down on
the terminal button to open the socket. Insert wire into
socket and release the terminal button. Insert one wire into
each of the two (2) terminals. See following for wire loca-
tions. Connect the power wires from the door sensor to the
PTAC on terminals C & R. The wire harness kit PWHK01C is
required for this connection.
PROPER INSTALLATION