13
PROPER INSTALLATION
OPERATING VOLTAGES
WARNING
USE EXTREME CAUTION WHEN CHECKING HIGH VOLTAGE.
Use a voltmeter, check the voltage at the outlet.
The reading must be within the minimums and maximums shown below for the operating voltage.
Unit Voltage
Rating
Minimum Voltage
Maximum Voltage
115
104
127
230/208
197
253
265
238
292
Operating Voltages
Voltage Utilization Range
•
LCDI or AFCI Power Cords
- Underwrites Laboratories and the National Electric Code (NEC) now require power cords that
sense current leakage and can open the electrical circuit to the unit on units rated at 250 volts or less. In the event that
unit does not operate, check the reset button located on or near the head of the power cord as part of the normal
troubleshooting procedure.
LCDI Power Cord