12
SPECIFICATIONS
ELECTRIC HEAT PERFORMANCE
PTH G SERIES
HEH H SERIES
PMH & PMC SERIES
EER -
Energy Efficiency Ratio per The Air-
Conditioning, Heating, and Refrigeration
Institute (AHRI) Test Procedures and
Canadian Standards Association (CSA)
Test Procedures.
COP -
Coefficient of Performance per AHRI
Test Procedures
Notes:
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
5
Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.
7
Specify two-digit heater kW size to complete model number.
8
R-410A refrigerant used in all systems.
9
All units meet or exceed ASHRAE 90.1 standards.
10
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
4
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay fuses
(included and factory-installed on all Amana® brand 265-volt chassis).
6
Total watts for 15,000 BTU/h models; subtract 20 watts for PT07/09/12 & HEH07/09/12
@ 230V @ 208V @ 265V
230/208V
2.5
1
8,500
6,800
- -
2,545 / 2,090 11.2 / 10.2
14.1
15
6-15 P
230/208V
3.5
1
12,000
9,900
- -
3,545 / 2,905 15.6 / 14.1
19.5
20
6-20 P
230/208V
5
1
17,100
14,000
- -
5,045 / 4,130 22.0 / 20.0
27.6
30
6-30 P
265V
2.5
1
- -
- -
8,500
2,550
9.6
12.0
15
7-20 P
265V
3.7
1
- -
- -
12,600
3,750
14.2
17.7
20
7-20 P
265V
5
1
- -
- -
17,100
5,050
19.1
23.8
25
7-30 P
Min. Circuit
Ampacity²
MOD
4
(amps)
Power Cord
Voltage
Electric
Heater Size
(kW)
No. of
Stages
Nominal Heating (BTU/h)
Total
Watts
6
Total
Amps