
4
The heating and cooling capacities of the unit should be
greater than or equal to the design heating and cooling
loads of the area to be conditioned. The loads should
be calculated by an approved method or in accordance
with A.S.H.R.A.E. Guide or Manual J - Load Calcula-
tions published by the Air Conditioning Contractors of
America.
Obtain from:
American National Standards Institute
1430 Broadway
New York, NY 10018
Transportation Damage
All units are securely packed in shipping containers
approved by the International Safe Transit Association.
The carton should be checked upon arrival for external
damage. If damage is found, a request for inspection by
carrier agent should be made in writing immediately.
The unit should be carefully inspected upon arrival for
damage and bolts or screws which may have loosened
in transit. In the event of damage, the consignee should:
1. Make notation on delivery receipt of any visible
damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, carrier should be
notified as soon as possible-preferably within 5 days.
4. File the claim with the following supporting docu-
ments within the 9 month statute of limitations.
a. Original Bill of Lading, certified copy, or indemnity
bond.
b. Original paid freight bill or indemnity in lieu thereof.
c. Original invoice or certified copy thereof, showing
trade and other discounts or reductions.
d. Copy of the inspection report issued by carrier
representative at the time damage is reported to
the carrier. The carrier is responsible for making
prompt inspection of damage and for a thorough
investigation of each claim. The distributor or
manufacturer will not accept claims from dealers
for transportation damage.
NOTE: When inspecting the unit for transportation dam-
age, remove all packaging materials. Recycle or dis-
pose the packaging material according to local codes.
III. Rigging and Handling
CAUTION
To prevent property damage, the unit
should remain in an upright position dur-
ing all rigging and moving operations.
To facilitate lifting and moving when a
crane is used, place the unit in an ad-
equate cable sling.
Important: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to install-
ing the unit. Ductwork dimensions are shown in Amana
roof curb installation instructions.
Refer to the Amana Roof Curb Installation Instructions
for proper curb installation. Curbing must be installed in
compliance with the National Roofing Contractors As-
sociation Manual.
Lower unit carefully onto roof mounting curb. While
rigging unit, center of gravity will cause condenser end
to be lower than supply air end.
If using a fork lift, see Figure 1 for location of fork
prongs. Make certain prongs support unit weight.
Figure 1
Rigging