background image

29

7. Replace regulator screw cover and finger-tighten securely.
8. Turn OFF all electrical power to the system.
9. Remove manometer and hose from outlet pressure tap.
10. Tighten outlet pressure tap clockwise 7 in-lbs minimum to

seal port.

11. Turn ON system power and set thermostat to call for heat.
12. Using a leak detection solution or non-chlorine soap suds,

check for leaks at hose connection.  Bubbles forming
indicate a leak.  SHUT OFF GAS AND FIX ALL LEAKS
IMMEDIATELY!

Measure gas manifold pressure with burners firing.  Adjust mani-
fold pressure per the 

Manifold Gas Pressure

 table.

Any necessary major changes in gas flow rate should be made by
changing the size of the burner orifice.

G

AS

 I

NPUT

 R

ATE

 M

EASUREMENT

 (N

ATURAL

 G

AS

 O

NLY

)

The gas input rate to the furnace must never be greater than that
specified on the unit rating plate.  To measure natural gas input
using the gas meter, use the following procedure.

1. Turn OFF the gas supply to all other gas-burning appliances

except the furnace.

2. While the furnace is operating, time and record one

complete revolution of the smallest gas meter dial.

3. Calculate the number of seconds per cubic foot (sec/ft

3

) of

gas being delivered to the furnace.  If the dial is a one cubic
foot dial, divide the number of seconds recorded in step 2
by one.  If the dial is a two cubic foot dial, divide the number
of seconds recorded in step 2 by two.

4. Calculate the furnace input in BTUs per hour (BTU/hr).  Input

equals the installation’s gas heating value multiplied with
a conversion factor (hours to seconds), divided by the
number of seconds per cubic foot.  The measured input
must not be greater than the input indicated on the unit
rating plate.
EXAMPLE:
Installation’s gas heating (HTG) value: 1,000 BTU/ft

3

(Obtained from gas supplier)
Installation’s seconds per cubic foot: 34 sec/ ft

3

Conversion Factor (hours to seconds): 3600 sec/hr
Input  = (Htg. value x 3600) ÷ seconds per cubic foot
Input = (1,000 BTU/ft

3

 x 3600 sec/hr) ÷ 34 sec/ ft

3

Input = 106,000 BTU/hr

Minor changes to the input rate may be accomplished through
manifold pressure adjustments at the gas valve.  Refer to 

Section

XIV, Startup Procedure and Adjustment - Gas Manifold Pressure
Measurement and Adjustment

 for details.  

NOTE:

  The final mani-

fold pressure cannot vary by more than ± 0.3” w.c. from the speci-
fied setting.  Consult your local gas supplier if additional input rate
adjustment is required.

5. Turn ON gas to and relight all other appliances turned off in

step 1.  Be certain that all appliances are functioning properly
and that all pilot burners are operating.

T

EMPERATURE

 R

ISE

Temperature rise must be within the range specified on the unit
rating plate. An incorrect temperature rise may result in condens-
ing in or overheating of the heat exchanger.  An airflow and tem-
perature rise table is provided in the Product Data Book applicable
to your model*.  Determine and adjust temperature rise as fol-
lows:

1. Operate furnace with burners firing for approximately ten

minutes.  Ensure all registers are open and all duct
dampers are in their final (fully or partially open) position.

2. Place thermometers in the return and supply ducts as close

to the furnace as possible.  Thermometers must not be
influenced by radiant heat by being able to “see” the heat
exchanger.

RISE = 

SUPPLY
    AIR

RETURN
    AIR 

HEAT EXCHANGER

RADIATION "LINE OF SIGHT"

T

RETURN

T

SUPPLY

 

T

SUPPLY

 

T

RETURN

Temperature Rise Measurement

3. Subtract the return air temperature from the supply air

temperature to determine the air temperature rise.  Allow
adequate time for thermometer readings to stabilize.

4. Adjust temperature rise by adjusting the circulator blower

speed. Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.  Refer
to 

Section XIV, Startup Procedure and Adjustment -Circulator

Blower Speeds

 for speed changing details.

C

IRCULATOR

 B

LOWER

 S

PEEDS

WARNING

T

O PREVENT PREMATURE FAILURE OF HEAT EXCHANGER, PROPERTY DAMAGE,

PERSONAL INJURY OR DEATH, DO NOT ADJUST THE LIMIT CONTROL (FACTORY

SET).

This furnace is equipped with a multi-speed circulator blower.  This
blower provides ease in adjusting blower speeds.  The Product
Data Book applicable to your model* provides an airflow table,
showing the relationship between airflow (CFM) and external static
pressure (E.S.P.), for the proper selection of heating and cooling
speeds.  The cooling blower speed is shipped set on HIGH, and
the heating blower speed is set as indicated in the Product Data
Book applicable to your model*.  These blower speeds should be
adjusted by the installer to match the installation requirements so
as to provide the correct heating temperature rise and correct cool-
ing CFM.

To adjust the circulator blower speed, proceed as follows:

1. Turn OFF power to the furnace.
2. Select the heating and cooling blower speeds that match

the installation requirements from the 

airflow table in the

Product Data Book

.

3. Relocate desired motor leads  to the circulator blower heat

and cool speed terminals on the integrated control module.
(Terminals are identified as HEAT and COOL  (hot)). If heating
and cooling blower speeds are the same, a jumper wire
must be used between the heat and cool terminals.

4. Connect all unused blower motor leads to the “PARK”

terminals on the integrated control module.  Any leads not
connected to the “PARK” terminals must be taped.

5. Turn ON power to furnace.

Summary of Contents for AMS95

Page 1: ...is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to b...

Page 2: ...D JOINING METHODS 12 PROPER VENT FLUE AND COMBUSTION AIR PIPING PRACTICES 13 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 13 STANDARD FURNACE CONNECTIONS 13 ALTERNATE FURNACE CONNECTIONS 14...

Page 3: ...ty Circuit Description 31 GENERAL 31 INTEGRATED CONTROL MODULE 31 PRIMARY LIMIT 31 AUXILIARY LIMIT 31 ROLLOUT LIMIT 31 PRESSURE SWITCHES 31 FLAME SENSOR 31 XVIII Troubleshooting 31 ELECTROSTATIC DISCH...

Page 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty cer tificate in a safe location for future reference If additional informatio...

Page 5: ...r Pressure Tap 20 Coil Front Cover Drain Port 21 Drain Line Penetrations 22 Drain Trap 23 Blower Door Interlock Switch 24 Capacitor 25 Integrated Control Module with fuse and diagnostic LED 26 24 Volt...

Page 6: ...ing to the installation and application of this product WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSTAION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY...

Page 7: ...e access doors must be vertical so that the burners fire horizontally into the heat exchanger Do not install the unit with the access doors on the up top or down bottom side of the furnace WARNING TO...

Page 8: ...reas behind the thermostat such as an outside wall CLEARANCES AND ACCESSIBILITY Installations must adhere to the clearances to combustible mate rials to which this furnace has been design certified Th...

Page 9: ...less than 100 square inches One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure DRAFTS OR DEAD SPOTS BEHIND DOORS IN CORNERS UNDER CABINETS Thermo...

Page 10: ...equip ment in the enclosure but not less than the sum of the areas of all vent connectors in the confined space Alternate Opening Location Equipment Located in Confined Spaces All Air from Outdoors Si...

Page 11: ...RAL Horizontal applications in particular may dictate many of the installation s specifics such as airflow direction ductwork connec tions flue and combustion air pipe connections etc The basic ap pli...

Page 12: ...ce change to compensate for the energy content difference between natural and propane gas High altitude installations may require both a pressure switch and an orifice change These changes are necessa...

Page 13: ...vent flue pipe and a combustion air intake pipe Refer to the appropriate section for details concerning piping size length number of elbows furnace connections and terminations MATERIALS AND JOINING M...

Page 14: ...DIRECT VENT INSTALLATIONS On upflow units secure the combustion air intake pipe directly to the air intake coupling On counterflow units secure the combus tion air intake pipe to the air intake coupl...

Page 15: ...e piping to the rubber elbow using a worm gear hose clamp NOTE Use of the alternate vent flue location for upright installations requires the drain trap be installed on the same side of the unit as th...

Page 16: ...uld be in stalled on either side of the wall and solvent cemented to a length of pipe connecting the two couplings The length of pipe should be the wall thickness plus the depth of the socket fittings...

Page 17: ...er of elbows and or tees in each Vent Flue Combustion Air Intake pipe Elbows and or tees used in the terminations must be included when determining the number of elbows in the piping systems If the co...

Page 18: ...ualPipe In a basement installation the pipes may be run between the joist spaces If the pipes must go below the joist and then up into the last joist space to penetrate the header two 45 elbows should...

Page 19: ...stallations using the standard vent flue outlet require drain hoses to be connected as follows The following quantity of hoses tubes and hose clamps are provided with the unit HOSE A QTY 1 HOSE B QTY...

Page 20: ...ow models relocation of the front cover pressure switch hose is required Make connections as follows 1 Remove the rubber plug from the coil front cover drain port Counterflow furnaces Relocate the fro...

Page 21: ...ed for identification purposes Refer to the wiring dia gram for wire routings If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring ma terial having...

Page 22: ...CHANGING ANY ELECTRICAL WIRING The furnace s integrated control module is equipped with line volt age accessory terminals for controlling power to an optional field supplied humidifier and or electro...

Page 23: ...it must be applied for propane gas installations Refer to the Section VIII Propane Gas High Altitude Installations section for details GAS VALVE This unit is equipped with a 24 volt gas valve controll...

Page 24: ...s and semirigid tubing against physical and thermal damage when installed Ensure aluminum alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry plas...

Page 25: ...ace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the liquid and wetted surface area of th...

Page 26: ...0 F FILTERS READ THIS SECTION BEFORE INSTALLING THE RETURN AIR DUCTWORK Filters must be used with this furnace Discuss filter maintenance with the building owner Filters do not ship with this furnace...

Page 27: ...e the burner compartment door 9 Open the manual gas shutoff valve external to the furnace 10 Turn on the electrical power to the furnace 11 Adjust the thermostat to a setting above room temperature 12...

Page 28: ...VENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATO...

Page 29: ...Temperature rise must be within the range specified on the unit rating plate An incorrect temperature rise may result in condens ing in or overheating of the heat exchanger An airflow and tem perature...

Page 30: ...ized Circulator blower is energized on cool speed following a fixed five second on delay Electronic air cleaner terminals are energized with circulator blower Furnace circulator blower and outdoor coo...

Page 31: ...heat exchanger and or blocked condensate drain con ditions FLAME SENSOR The flame sensor is a probe mounted to the burner manifold as sembly which uses the principle of flame rectification to determin...

Page 32: ...power to furnace MEDIA AIR FILTER OR ELECTRONIC AIR CLEANER REMOVAL Follow the manufacturer s directions for service BURNERS Visually inspect the burner flames periodically during the heating season...

Page 33: ...t Filter Front of Furnace Blower 4 Angle filter toward the blower until filter clears bottom rail 5 Lower filter down and pull outward Front of Furnace Blower Front of Furnace Blower 6 Replace filter...

Page 34: ...ecessary Correct pressure switch setpoint or contact motion Tighten or correct wiring connection Pressure switch hose blocked pinched or connected improperly Blocked flue and or inlet air pipe blocked...

Page 35: ...nfo Adjust as Turn power OFF prior to repair Sand flame sensor with emery clot See Vent Flue Pipe section for piping details See rating plate for proper gas pressure 7 7 FLASHES Flame sensor is coated...

Page 36: ...EC T L N P O W E R S U P P L Y W I T H O V E R C U R R E N T P R O T E C T I O N D E V I C E WH JUNCTION BOX 1 T O 1 1 5 V A C 1 0 6 0 H Z ID BLOWER PRSEEURE SWITCH HEAT H GND WH RD WH GND BURNER COM...

Page 37: ...37 2005 Goodman Company L P is a trademark of Maytag Corporation and is used under license to Goodman Company L P All rights reserved 1810 Wilson Parkway Fayetteville TN 37334 www amana hac com...

Reviews: