background image

15

8.  Remove the manometer hose from the hose barb 

fitting or inlet pressure Tap.

9.  Replace inlet pressure tap:

a.  White-Rodgers Valve:

Turn inlet pressure test screw in to seal pressure 

port (clockwise, 7 in-lb minimum).

10. Retest for leaks. If bubbles form, shut down gas and   

repair leaks immediately.

11.  If there are no leaks, turn ON electrical power and gas 

supply to the system.

12. Turn valve switch ON.

NOTE: If measuring gas pressure at the drip leg, a 

field-supplied hose barb fitting must be installed 

prior to making the hose connection. If using 

the inlet pressure Tap on the White-Rodgers gas 

valve, then use the 36G/J Valve Pressure Check Kit, 

Goodman Part No. 0151K00000S.



.

Measuring Inlet Gas Pressure (Alt. Method)

Gas Manifold Pressure Measurement and 

Adjustment

CAUTION

To prevent unreliable operation or equipment damage, the 

gas manifold pressure must be as specified on the unit rating 

plate. Only minor adjustments should be made by adjusting 

the gas valve pressure regulator.

Only small variations in gas pressure should be made by 

adjusting the gas valve pressure regulator. The manifold 

pressure must be measured with the burners operating. 

To measure and adjust the manifold pressure, use the 

following procedure.

1. 

Turn OFF gas to furnace at the manual gas shutoff 

valve external to the furnace.

2.  Turn OFF all electrical power to the system.

3.  Outlet pressure tap connections:

a.  White-Rodgers Valve:

Back outlet pressure test screw (outlet pressure 

Tap) out one turn (counterclockwise, not more than 

one turn).

4.  Connect manometer (or appropriate pressure gauge) 

at the gas valve outlet pressure tap. See White-

Rodgers 36J22Y-204 gas valve for location of outlet 

pressure tap.

5.  Turn ON the gas supply.

6.  Turn ON power and close thermostat “R” and “W” 

contacts to provide a call for heat.

7.  Using a leak detection solution or soap suds, check 

for leaks at outlet pressure tap screw (White-Rodgers 

valve). Bubbles forming indicate a leak. SHUT OFF 

GAS AND REPAIR ALL LEAKS IMMEDIATELY!

8. 

Measure the gas manifold pressure with burners firing. 

Adjust manifold pressure using the following

 Manifold 

Gas Pressure 

table.

Natural Gas

2.8" - 3.2" w.c.

Manifold Gas Pressure

The Manifold Gas Pressure must be within the range 

specified.

9.  Remove regulator cover screw from the outlet 

pressure regulator and turn screw clockwise to 

increase pressure or counterclockwise to decrease 

pressure. Replace regulator cover screw.

10. Turn OFF all electrical power and gas supply to the 

system.

11.  Remove the manometer hose from the hose barb 

fitting or outlet pressure tap.

12. Replace outlet pressure tap:

a.  White-Rodgers Valve: Turn outlet pressure test 

screw in to seal pressure port (clockwise, 7 in-lb 

minimum).

14. Turn ON electrical power and gas supply to the 

system.

15. Close thermostat contacts to provide a call for heat.

16. Retest for leaks. If bubbles form, SHUT OFF GAS 

AND REPAIR ALL LEAKS IMMEDIATELY!

Gas BTU Input (Natural Gas Only) Check 

To measure the gas input use a gas meter and proceed as 

follows:

1. 

Turn off gas supply to all other appliances except the 

unit.

2.  With the unit operating, time the smallest dial on the 

meter for one complete revolution. If this is a 2 cubic 

foot dial, divide the seconds by 2; if it is a 1 cubic foot 

dial, use the seconds as is. This gives the seconds per 

cubic foot of gas being delivered to the unit.

3.  INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC 

FOOT

 

Example:

 Natural gas with a heating value of 1000 

BTU per cubic foot and 36 seconds per cubic foot as 

determined by  

 

Step 2, then: 

Input = 1000 x 3600 / 36 = 100,000 BTU per Hour.  

 

Summary of Contents for A/GPU14 M Series

Page 1: ...Please contact your distributor or our website for the applicable Specification Sheets referred to in this manual This Forced Air Central Unit Design Complies With Requirements Embodied In The America...

Page 2: ...djustments 16 EEM Motors 16 Limit Check 17 Unit Shut Down 17 Compression Protection Devices 17 Refrigerant Charge Check 17 Cooling Refrigerant Charging Models with TXV 17 Superheat Adjustment 17 Cooli...

Page 3: ...seated and attached with the PCB or else the unit might not function as intended ID Plug PCB Terminal J9 Adjusting Gas Manifold Pressure Use the below manifold pressure settings Gas Input BTU HR Manif...

Page 4: ...uilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must b...

Page 5: ...n est n cessaire pour viter le danger d intoxica on au CO pouvant survenir si un appareil produisant du monoxyde de carbone con nue de fonc onner au sein de la zone confin e Esta ven laci n es necesar...

Page 6: ...n monoxide poisoning or death The following steps shall be followed with each appliance connected to the venting system placed in operation while any other appliances connected to the venting system a...

Page 7: ...observed when installing the unit IMPORTANT NOTE Remove wood shipping rails prior to installation of the unit All Installations For proper flame pattern within the heat exchanger and proper condensate...

Page 8: ...constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Curb insulation cant strips flashing and general roofing material are furnished b...

Page 9: ...400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 50 PSIG or less and Pressure Drop of 0 3 W C Based on 0 60 Specific Gravity Gas Natural Gas Capac...

Page 10: ...ermostat Location Mount the thermostat approximately five feet above the floor in an area that has an inside vibration free wall and has good air circulation Movement of air must not be obstructed by...

Page 11: ...30 35 40 45 50 SUPPLY WIRE LENGTH FEET 200 6 4 4 4 3 3 2 2 150 8 6 6 4 4 4 3 3 100 10 8 8 6 6 6 4 4 50 14 12 10 10 8 8 6 6 Wiring Table CIRCULATING AIR AND FILTERS Airflow Conversion Units can easily...

Page 12: ...All units may be externally filtered Refer to the unit filter size chart in the appendix for filter size information Filters installed external to the unit should be sized in accordance with their man...

Page 13: ...tisfied 5 The compressor and outdoor fan will be de energized when the thermostat opens 6 The indoor blower continues to run at low cool speed for approximately 60 seconds after the thermostat is sati...

Page 14: ...be as specified on the unit rating plate with all other household gas fired appliances operating The line pressure supplied to the gas valve must be within the Inlet Gas Supply Pressure range specifie...

Page 15: ...ressure tap 5 Turn ON the gas supply 6 Turn ON power and close thermostat R and W contacts to provide a call for heat 7 Using a leak detection solution or soap suds check for leaks at outlet pressure...

Page 16: ...give the correct air temperature rise through the unit as marked on the rating plate External Static Pressure Check The total external static pressure must be checked on this unit to determine if the...

Page 17: ...ect electrical power before inspecting or servicing the unit NOTE All compressor protection devices reset automatically energizing the contactor and outdoor fan WARNING Do not bypass safety devices Re...

Page 18: ...Record the gauge pressure and the temperature of the line 4 Compare the hi pressure reading to the Required Liquid Line Temperature chart Find the hi pressure value on the left column Follow that line...

Page 19: ...is outside the acceptable range for the null value the control enters a five minute lockout After the lockout timer has expired the control resumes normal operation During inducer operation including...

Page 20: ...nlet and flue outlet hoods are not blocked by debris which would prevent adequate combustion air and a properly operating vent system Filter Replacement or Cleaning A return air filter is not supplied...

Page 21: ...ormation on the yearly inspection consult the User Manual It is recommended that a qualified servicer inspect and service the unit at least once each year Turn the unit on at the thermostat Wait a few...

Page 22: ...LASH RETRIES EXCEEDED RED 1 HOUR FIXED 10 FLASHES HIGH LIMIT SWITCH RECOVERY TIMER EXPIRED RED 1 HOUR OR HARD LOCKOUT RAPID FLASH CLEAR ERROR HISTORY GREEN N A 2 FLASHES PRESSURE SENSOR NULL ERROR RED...

Page 23: ...U1442 M41 47 51 40 42 1 2 Large A GPU1448 M41 47 51 40 42 1 2 Large A GPU1461 M41 47 51 40 42 1 2 Large Model Unit Dimensions Inches Height Chassis Size W H W H A GPU1424 M41 16 16 16 16 A GPU1430 M41...

Page 24: ...PRIMARY LIMIT SWITCH RC RUN CAPACITOR TON ON DELAY TIMER RELAY TR TRANSFORMER VM VENT MOTOR WIRE CODE BLACK BLUE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW BK BL BR GR GY OR PK PU RD TN...

Page 25: ...2 R2 PU 3 5 4 3 2 1 YL GR LINE VOLTAGE 208 230V 1PH 60Hz R C RD L1 L2 G R W Y C 5 4 3 2 1 GR COM TR BR RD BK RD YL OR BR WH BK OR YL BR 1 2 BK WH VM GR GR GR BL BL HPS LPS PU R C G Y2 Y1 W1 1 TO THERM...

Page 26: ...instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant NOTE Roof overhang should be no more than 36 RECO...

Page 27: ...38 41 502 159 X 773 237 1011 324 0 8 444 165 828 245 42 444 165 X 690 245 948 329 PU1430060M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 COOLING SPEED T5 COOLING SP...

Page 28: ...677 0 7 644 196 966 305 52 899 278 56 1451 550 1629 686 0 8 587 206 901 315 54 832 285 59 1397 556 1578 693 PU1448080M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 C...

Page 29: ...ssor motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified installer or service agency at l...

Page 30: ...iquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suction L...

Page 31: ...31 PAGE LEFT INTENTIONALLY BLANK...

Page 32: ...out us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page Our continuing commitment to quality products may mean a change in...

Reviews: