background image

18

increase superheat or counterclockwise (out) to decrease 

superheat. Replace adjustment cap. Wait a minimum of 10 

minutes between adjustments to allow time for the TXV and 

pressures to stabilize.

SUPERHEAT

Checking Superheat

Refrigerant gas is considered superheated whenever its 

temperature is higher than the saturation temperature 

corresponding to its pressure. The degree of superheat 

equals the degrees of temperature increase above 

the saturation temperature at existing pressure. See 

Temperature - Pressure Chart.

1.  Run system at least 10 minutes to allow pressure to 

stabilize.

2.  Temporarily install thermometer on suction (large) line 

near compressor with adequate contact and insulate 

for best possible reading.

3.  Refer to the superheat table provided for proper system 

superheat. Add charge to lower superheat or recover 

charge to raise superheat.

Superheat Formula = Suct. Line Temp. - Sat. Suct. 

Temp.

65

70

75

80

85

100

-

-

-

10

10

95

-

-

10

10

10

90

-

-

12

15

18

85

-

10

13

17

20

80

-

10

15

21

26

75

10

13

17

25

29

70

10

17

20

28

32

65

13

19

26

32

35

60

17

25

30

33

37

Ambient Condenser Inlet 

Temp (°F Drybulb)

Return Air Temp. (°F Drybulb)

EXAMPLE:

a.  Suction Pressure = 143

b.  Corresponding Temp. °F. = 50

c.  Thermometer on Suction Line = 59°F.

To obtain the degrees temperature of superheat, subtract 

50.0 from 59.0°F.

The difference is 9° Superheat. The 9° Superheat would fall 

in the ± range of allowable superheat.

Checking Subcooling

Refrigerant liquid is considered subcooled when its 

temperature is lower than the saturation temperature 

corresponding to its pressure. The degree of subcooling 

equals the degrees of temperature decrease below the 

saturation temperature at the existing pressure.

1.  Attach an accurate thermometer or preferably a 

thermocouple type temperature tester to the liquid line 

close to the pressure switch.

2.  Install a high side pressure gauge on the liquid access 

fitting.

3.  Record the gauge pressure and the temperature of the 

line.

4.  Compare the hi-pressure reading to the “Required 

Liquid Line Temperature” chart. Find the hi-pressure 

value on the left column. Follow that line right to the 

column under the design subcooling value. Where the 

two intersect is the required liquid line temperature. 

Alternately you can convert the liquid line pressure 

gauge reading to temperature by finding the gauge 

reading in Temperature - Pressure Chart and reading to 

the left, find the temperature in the °F. Column.

5. 

The difference between the thermometer reading and 

pressure to temperature conversion is the amount of 

subcooling.

Subcooling Formula = Sat. Liquid Temp. - Liquid Line 

Temp.

EXAMPLE:

a.  Liquid Line Pressure = 417

b.  Corresponding Temp. °F. = 120°

c.  Thermometer on Liquid line = 109°F.

To obtain the amount of subcooling, subtract 109°F 

from 120°F The difference is 11° subcooling. See the 

specification sheet or technical information manual for the 

design subcooling range for your unit.

See R410A Pressure vs. Temperature chart.

Cooling Operation

NOTE: Mechanical cooling cannot be reliably 

provided at ambient temperatures below 50° F. 

1.  Turn on the electrical power supply to the unit. 

2.  Place the room thermostat selector switch in the 

COOL position (or AUTO if available, and if automatic 

changeover from cooling to heating is desired).

3.  Set the room thermostat to the desired temperature. 

TROUBLESHOOTING

Ignition Control Error Codes

The following presents probable causes of questionable 

unit operation. Refer to Diagnostic Indicator Chart for 

an interpretation of the signal and to this section for an 

explanation.

Remove the control box access panel and note the number 

of diagnostic LED flashes. Refer to Diagnostic Indicator 

Chart for an interpretation of the signal and to this section 

for an explanation.

Fault Recall

The ignition control is equipped with a momentary push-

button switch that can be used to display on the diagnostic 

LED the last five faults detected by the control. Any time the 

control is powered, the fault code history can be retrieved 

Summary of Contents for A/GPU14 M Series

Page 1: ...Please contact your distributor or our website for the applicable Specification Sheets referred to in this manual This Forced Air Central Unit Design Complies With Requirements Embodied In The America...

Page 2: ...djustments 16 EEM Motors 16 Limit Check 17 Unit Shut Down 17 Compression Protection Devices 17 Refrigerant Charge Check 17 Cooling Refrigerant Charging Models with TXV 17 Superheat Adjustment 17 Cooli...

Page 3: ...seated and attached with the PCB or else the unit might not function as intended ID Plug PCB Terminal J9 Adjusting Gas Manifold Pressure Use the below manifold pressure settings Gas Input BTU HR Manif...

Page 4: ...uilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must b...

Page 5: ...n est n cessaire pour viter le danger d intoxica on au CO pouvant survenir si un appareil produisant du monoxyde de carbone con nue de fonc onner au sein de la zone confin e Esta ven laci n es necesar...

Page 6: ...n monoxide poisoning or death The following steps shall be followed with each appliance connected to the venting system placed in operation while any other appliances connected to the venting system a...

Page 7: ...observed when installing the unit IMPORTANT NOTE Remove wood shipping rails prior to installation of the unit All Installations For proper flame pattern within the heat exchanger and proper condensate...

Page 8: ...constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Curb insulation cant strips flashing and general roofing material are furnished b...

Page 9: ...400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 50 PSIG or less and Pressure Drop of 0 3 W C Based on 0 60 Specific Gravity Gas Natural Gas Capac...

Page 10: ...ermostat Location Mount the thermostat approximately five feet above the floor in an area that has an inside vibration free wall and has good air circulation Movement of air must not be obstructed by...

Page 11: ...30 35 40 45 50 SUPPLY WIRE LENGTH FEET 200 6 4 4 4 3 3 2 2 150 8 6 6 4 4 4 3 3 100 10 8 8 6 6 6 4 4 50 14 12 10 10 8 8 6 6 Wiring Table CIRCULATING AIR AND FILTERS Airflow Conversion Units can easily...

Page 12: ...All units may be externally filtered Refer to the unit filter size chart in the appendix for filter size information Filters installed external to the unit should be sized in accordance with their man...

Page 13: ...tisfied 5 The compressor and outdoor fan will be de energized when the thermostat opens 6 The indoor blower continues to run at low cool speed for approximately 60 seconds after the thermostat is sati...

Page 14: ...be as specified on the unit rating plate with all other household gas fired appliances operating The line pressure supplied to the gas valve must be within the Inlet Gas Supply Pressure range specifie...

Page 15: ...ressure tap 5 Turn ON the gas supply 6 Turn ON power and close thermostat R and W contacts to provide a call for heat 7 Using a leak detection solution or soap suds check for leaks at outlet pressure...

Page 16: ...give the correct air temperature rise through the unit as marked on the rating plate External Static Pressure Check The total external static pressure must be checked on this unit to determine if the...

Page 17: ...ect electrical power before inspecting or servicing the unit NOTE All compressor protection devices reset automatically energizing the contactor and outdoor fan WARNING Do not bypass safety devices Re...

Page 18: ...Record the gauge pressure and the temperature of the line 4 Compare the hi pressure reading to the Required Liquid Line Temperature chart Find the hi pressure value on the left column Follow that line...

Page 19: ...is outside the acceptable range for the null value the control enters a five minute lockout After the lockout timer has expired the control resumes normal operation During inducer operation including...

Page 20: ...nlet and flue outlet hoods are not blocked by debris which would prevent adequate combustion air and a properly operating vent system Filter Replacement or Cleaning A return air filter is not supplied...

Page 21: ...ormation on the yearly inspection consult the User Manual It is recommended that a qualified servicer inspect and service the unit at least once each year Turn the unit on at the thermostat Wait a few...

Page 22: ...LASH RETRIES EXCEEDED RED 1 HOUR FIXED 10 FLASHES HIGH LIMIT SWITCH RECOVERY TIMER EXPIRED RED 1 HOUR OR HARD LOCKOUT RAPID FLASH CLEAR ERROR HISTORY GREEN N A 2 FLASHES PRESSURE SENSOR NULL ERROR RED...

Page 23: ...U1442 M41 47 51 40 42 1 2 Large A GPU1448 M41 47 51 40 42 1 2 Large A GPU1461 M41 47 51 40 42 1 2 Large Model Unit Dimensions Inches Height Chassis Size W H W H A GPU1424 M41 16 16 16 16 A GPU1430 M41...

Page 24: ...PRIMARY LIMIT SWITCH RC RUN CAPACITOR TON ON DELAY TIMER RELAY TR TRANSFORMER VM VENT MOTOR WIRE CODE BLACK BLUE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW BK BL BR GR GY OR PK PU RD TN...

Page 25: ...2 R2 PU 3 5 4 3 2 1 YL GR LINE VOLTAGE 208 230V 1PH 60Hz R C RD L1 L2 G R W Y C 5 4 3 2 1 GR COM TR BR RD BK RD YL OR BR WH BK OR YL BR 1 2 BK WH VM GR GR GR BL BL HPS LPS PU R C G Y2 Y1 W1 1 TO THERM...

Page 26: ...instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant NOTE Roof overhang should be no more than 36 RECO...

Page 27: ...38 41 502 159 X 773 237 1011 324 0 8 444 165 828 245 42 444 165 X 690 245 948 329 PU1430060M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 COOLING SPEED T5 COOLING SP...

Page 28: ...677 0 7 644 196 966 305 52 899 278 56 1451 550 1629 686 0 8 587 206 901 315 54 832 285 59 1397 556 1578 693 PU1448080M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 C...

Page 29: ...ssor motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified installer or service agency at l...

Page 30: ...iquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suction L...

Page 31: ...31 PAGE LEFT INTENTIONALLY BLANK...

Page 32: ...out us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page Our continuing commitment to quality products may mean a change in...

Reviews: